Heating · HxAR training film

Boiler thermistor and safety thermostat faults

Enter your boiler’s fault code to see which thermistor or thermostat it relates to on your model. To learn how engineers distinguish a sensor fault from a wiring or PCB fault, watch the worked examples on a Baxi Main Eco Compact Combi.

15:44 · George’s UK narration · English captions · 10 chapters

Film chapters

Choose a test to jump to it. Press Play if the film is paused.

  1. 00:00Find the four thermistors and the safety thermostat
  2. 01:11How the boiler PCB reads the flow thermistor
  3. 02:59Multimeter test on the heating pad | NTC vs PTC
  4. 03:58Where NTC and PTC thermistors are used
  5. 06:09No hot water | E28 flue sensor wiring fault
  6. 08:07No central heating | E40 return thermistor fault
  7. 10:26E40 again | Sensor and wiring test good
  8. 12:24Open circuit (OL) vs short circuit on a thermistor
  9. 13:40Safety thermostat continuity and trip tests
  10. 14:44Try the fault codes yourself in HxAR

Which boilers show this fault code?

Enter the code from the boiler display to see which makes and models use it for a thermistor or thermostat fault. Select a make beside a fault meaning to see the exact models and manual pages.

Browse all thermistor and thermostat fault codes
0
Fault meaningModels and manual pages
The S1/S2 sensor self-check failed.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
2
Fault meaningModels and manual pages
The S1 flow and S2 return sensor connections appear interchanged.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
The safety thermostat has operated and the boiler has locked out.
Biasi (2)
  • Antares 25C, Antares 30C, Antares 35Cbiasi-antares-combi · PDF p. 10
  • Antares 30Sbiasi-antares-system · PDF p. 10
6
Fault meaningModels and manual pages
Fault on the central-heating flow NTC circuit.
Biasi (2)
  • Antares 25C, Antares 30C, Antares 35Cbiasi-antares-combi · PDF p. 10
  • Antares 30Sbiasi-antares-system · PDF p. 10
7
Fault meaningModels and manual pages
Open circuit at the hot-water cylinder temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 63
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 68
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 52
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 70
Fault on the hot-water or cylinder temperature probe, according to the installation.
Biasi (2)
  • Antares 25C, Antares 30C, Antares 35Cbiasi-antares-combi · PDF p. 10
  • Antares 30Sbiasi-antares-system · PDF p. 10
8
Fault meaningModels and manual pages
Short circuit at the hot-water cylinder temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 63
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 68
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 52
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 70
Fault on the outdoor temperature probe circuit.
Biasi (2)
  • Antares 25C, Antares 30C, Antares 35Cbiasi-antares-combi · PDF p. 10
  • Antares 30Sbiasi-antares-system · PDF p. 10
8C 373
Fault meaningModels and manual pages
Repeated overheat indications from the thermostat have triggered lockout.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 64
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 64
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 66
10
Fault meaningModels and manual pages
The S1 heating flow temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
Short circuit at the outside temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 48
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 33
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
Flue probe or thermal-fuse protection has tripped.
Biasi (2)
  • Antares 25C, Antares 30C, Antares 35Cbiasi-antares-combi · PDF p. 10
  • Antares 30Sbiasi-antares-system · PDF p. 10
11
Fault meaningModels and manual pages
The S1 heating flow temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
Open circuit at the solar collector temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 68
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 70
12
Fault meaningModels and manual pages
The S1 heating flow temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
Fault on the central-heating return NTC circuit.
Biasi (2)
  • Antares 25C, Antares 30C, Antares 35Cbiasi-antares-combi · PDF p. 10
  • Antares 30Sbiasi-antares-system · PDF p. 10
Short circuit at the solar collector temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 68
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 70
13
Fault meaningModels and manual pages
The S1 heating flow temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
Open circuit at the outdoor temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 63
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 68
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 53
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 70
14
Fault meaningModels and manual pages
The S1 heating flow temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
Short circuit at the outdoor temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 63
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 68
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 53
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 70
15
Fault meaningModels and manual pages
Open circuit at the solar hot-water cylinder temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 68
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 70
16
Fault meaningModels and manual pages
Short circuit at the solar hot-water cylinder temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 69
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 71
18
Fault meaningModels and manual pages
Open circuit at the outside temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 48
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 33
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
20
Fault meaningModels and manual pages
The S2 heating return temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
High-limit thermostat or flue thermostat has operated.
Vokèra (1)
  • Linea One (38 kW DHW) ErPLinea One Installation & Servicing Instructions · 07/11 - Ed.0 · PDF p. 31
21
Fault meaningModels and manual pages
The S2 heating return temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
22
Fault meaningModels and manual pages
The S2 heating return temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
23
Fault meaningModels and manual pages
The S2 heating return temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
24
Fault meaningModels and manual pages
The S2 heating return temperature sensor reports a fault.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
26
Fault meaningModels and manual pages
The two heating NTC readings disagree beyond the permitted range.
Biasi (2)
  • Antares 25C, Antares 30C, Antares 35Cbiasi-antares-combi · PDF p. 10
  • Antares 30Sbiasi-antares-system · PDF p. 10
27
Fault meaningModels and manual pages
The optional outdoor temperature sensor circuit reads short.
Intergas (5)
  • Combi Compact ECO RF 24, 30, 3688458804 · PDF p. 49
  • Combi Compact HRE 24/18, 28/24, 36/30, 36/4088287806 · PDF p. 49
  • Compact HRE 18 OV, 24 OV, 30 OV88324804 · PDF p. 45
  • Compact HRE 18 SB, 24 SB, 30 SB, 40 SB88322805 · PDF p. 48
  • Rapid 25, 32; Rapid Plus 25, 32 (Intergas also links this Rapid manual for Plus)88923806 · PDF p. 55
29
Fault meaningModels and manual pages
Open circuit at the low-loss header temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 69
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 71
30
Fault meaningModels and manual pages
Short circuit at the boiler water temperature sensor.
Viessmann (4)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 48
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 33
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
Short circuit at the low-loss header temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 69
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 71
38
Fault meaningModels and manual pages
Open circuit at the boiler water temperature sensor.
Viessmann (4)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 48
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 33
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
49
Fault meaningModels and manual pages
Open circuit at the flue gas temperature sensor.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 63
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 69
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 53
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 71
50
Fault meaningModels and manual pages
Short circuit at the flue gas temperature sensor.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 63
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 69
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 53
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 71
Short circuit at the hot-water cylinder temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
51
Fault meaningModels and manual pages
Short circuit at the hot-water outlet temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 48
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
57
Fault meaningModels and manual pages
Open circuit at the external room temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 63
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 69
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 53
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 71
58
Fault meaningModels and manual pages
Short circuit at the external room temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 63
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 69
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 53
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 71
Open circuit at the hot-water cylinder temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
59
Fault meaningModels and manual pages
Open circuit at the hot-water outlet temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 49
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
60
Fault meaningModels and manual pages
Short circuit at the return temperature sensor.
Viessmann (1)
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 33
The domestic hot-water temperature probe circuit reports a fault.
Vokèra (1)
  • Linea One (38 kW DHW) ErPLinea One Installation & Servicing Instructions · 07/11 - Ed.0 · PDF p. 31
62
Fault meaningModels and manual pages
The high-limit safety cut-out has tripped.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 64
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 69
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 53
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 71
63
Fault meaningModels and manual pages
The flue gas temperature limiter has tripped.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 64
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 70
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 54
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 72
68
Fault meaningModels and manual pages
Open circuit at the return temperature sensor.
Viessmann (1)
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 33
70
Fault meaningModels and manual pages
Flow NTC fault on the second heating circuit.
Vokèra (1)
  • Linea One (38 kW DHW) ErPLinea One Installation & Servicing Instructions · 07/11 - Ed.0 · PDF p. 31
71
Fault meaningModels and manual pages
Flow NTC fault on the second heating circuit.
Vokèra (1)
  • Linea One (38 kW DHW) ErPLinea One Installation & Servicing Instructions · 07/11 - Ed.0 · PDF p. 31
72
Fault meaningModels and manual pages
Return NTC fault on the second heating circuit.
Vokèra (1)
  • Linea One (38 kW DHW) ErPLinea One Installation & Servicing Instructions · 07/11 - Ed.0 · PDF p. 31
77
Fault meaningModels and manual pages
Underfloor overheat thermostat has operated on the second heating circuit.
Vokèra (1)
  • Linea One (38 kW DHW) ErPLinea One Installation & Servicing Instructions · 07/11 - Ed.0 · PDF p. 31
182
Fault meaningModels and manual pages
Short circuit at the outlet temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 66
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 73
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 56
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 75
183
Fault meaningModels and manual pages
Open circuit at the outlet temperature sensor, where fitted.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 66
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 73
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 56
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 75
184
Fault meaningModels and manual pages
Short circuit at the combined heating flow sensor and high-limit cut-out circuit.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 67
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 74
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 56
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 76
185
Fault meaningModels and manual pages
Open circuit at the combined heating flow sensor and high-limit cut-out circuit.
Viessmann (3)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 74
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 56
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 76
222
Fault meaningModels and manual pages
The fault table groups these codes as an interruption in the heating flow NTC wiring.
Worcester Bosch (1)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 87
223
Fault meaningModels and manual pages
The fault table groups these codes as an interruption in the heating flow NTC wiring.
Worcester Bosch (1)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 87
224
Fault meaningModels and manual pages
The flue or heat exchanger high-limit thermostat circuit has operated.
Worcester Bosch (12)
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 72
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 71
  • Greenstar 8000 Life GR8300iW combi 30, 35, 40, 45, 50 C6720883865 · 2021/11 · PDF p. 75
  • Greenstar 8000 Life GR8300iW regular 30, 35, 40, 45, 50 R6720883866 · 2021/09 · PDF p. 69
  • Greenstar 8000 Life GR8300iW system 30, 35 S6720883858 · 2021/09 · PDF p. 71
  • Greenstar 8000 Style GR8700iW combi 30, 35, 40, 45, 50 C/CB6720883864 · 2021/09 · PDF p. 74
  • Greenstar 8000 Style GR8700iW system 30, 35 S/SB6720883855 · 2021/09 · PDF p. 74
  • Greenstar 8000+ GR8701iW combi 32 C V2, 36/40/45/50 C; Style 32 CB V2, 36 CB6721108973 · 2025/06 · PDF p. 74
  • Greenstar 8000+ GR8701iW regular 30, 35, 40, 45, 50 R6721891104 · 2024/06 · PDF p. 70
  • Greenstar 8000+ GR8701iW system 30, 35 S6721891100 · 2024/06 · PDF p. 75
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 81
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 75
The safety temperature limiter has tripped.
Worcester Bosch (2)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 87
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 79
240
Fault meaningModels and manual pages
The fault table groups these codes as an interruption in the heating return NTC wiring.
Worcester Bosch (1)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 88
241
Fault meaningModels and manual pages
The fault table groups these codes as an interruption in the heating return NTC wiring.
Worcester Bosch (1)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 88
324
Fault meaningModels and manual pages
DHW outlet thermistor fault (information-menu cause code).
Worcester Bosch (2)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 63
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 65
325
Fault meaningModels and manual pages
DHW outlet thermistor incorrectly installed (information-menu cause code).
Worcester Bosch (2)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 63
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 65
345
Fault meaningModels and manual pages
The temperature limiter has tripped.
Viessmann (3)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 74
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 57
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 76
350
Fault meaningModels and manual pages
Heating flow temperature sensor circuit reads short.
Worcester Bosch (1)
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 82
351
Fault meaningModels and manual pages
The heating flow temperature sensor circuit is interrupted.
Worcester Bosch (2)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 90
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 82
373
Fault meaningModels and manual pages
Heat transfer during calibration was insufficient and the temperature limiter shut the burner down.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 70
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 77
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 60
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 79
393
Fault meaningModels and manual pages
Short circuit at the second flue temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 73
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 81
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 83
394
Fault meaningModels and manual pages
Open circuit at the second flue temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 73
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 81
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 83
416
Fault meaningModels and manual pages
The flue gas temperature sensor is incorrectly positioned.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 74
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 82
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 62
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 84
446
Fault meaningModels and manual pages
The flow sensor and high-limit channel give inconsistent readings.
Viessmann (4)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 74
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 83
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 63
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 85
544
Fault meaningModels and manual pages
Open circuit at the mixed heating circuit 2 flow temperature sensor.
Viessmann (3)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 86
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 66
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 88
545
Fault meaningModels and manual pages
Short circuit at the mixed heating circuit 2 flow temperature sensor.
Viessmann (3)
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 86
  • Vitodens 100-W Heat Only B1GA6194585 GB · 3/2023 · PDF p. 66
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 88
574
Fault meaningModels and manual pages
The room sensor for heating circuit 1 is unavailable, where fitted.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 77
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 86
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 88
575
Fault meaningModels and manual pages
The room sensor for heating circuit 1 is open-circuit, where fitted.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 78
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 86
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 88
576
Fault meaningModels and manual pages
The room sensor for heating circuit 1 is short-circuited, where fitted.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 78
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 86
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 88
577
Fault meaningModels and manual pages
The room sensor for heating circuit 2 is unavailable, where fitted.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 78
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 86
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 88
578
Fault meaningModels and manual pages
The room sensor for heating circuit 2 is open-circuit, where fitted.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 78
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 86
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 88
579
Fault meaningModels and manual pages
The room sensor for heating circuit 2 is short-circuited, where fitted.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 78
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 87
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 89
694
Fault meaningModels and manual pages
The flue high-limit safety signals disagree.
Viessmann (3)
  • Vitodens 050-W B0HA, B0KA and B0KA-M6194588 GB · 12/2022 · PDF p. 78
  • Vitodens 100-W B1HF/B1KF and B1HF-M/B1KF-M6167586 GB · 3/2023 · PDF p. 87
  • Vitodens 111-W B1LF and B1LF-M6167585 GB · 3/2023 · PDF p. 89
815
Fault meaningModels and manual pages
Low-loss header temperature sensor circuit fault, where that accessory is fitted.
Worcester Bosch (10)
  • Greenstar 8000 Life GR8300iW combi 30, 35, 40, 45, 50 C6720883865 · 2021/11 · PDF p. 77
  • Greenstar 8000 Life GR8300iW regular 30, 35, 40, 45, 50 R6720883866 · 2021/09 · PDF p. 72
  • Greenstar 8000 Life GR8300iW system 30, 35 S6720883858 · 2021/09 · PDF p. 73
  • Greenstar 8000 Style GR8700iW combi 30, 35, 40, 45, 50 C/CB6720883864 · 2021/09 · PDF p. 76
  • Greenstar 8000 Style GR8700iW system 30, 35 S/SB6720883855 · 2021/09 · PDF p. 76
  • Greenstar 8000+ GR8701iW combi 32 C V2, 36/40/45/50 C; Style 32 CB V2, 36 CB6721108973 · 2025/06 · PDF p. 76
  • Greenstar 8000+ GR8701iW regular 30, 35, 40, 45, 50 R6721891104 · 2024/06 · PDF p. 73
  • Greenstar 8000+ GR8701iW system 30, 35 S6721891100 · 2024/06 · PDF p. 77
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 84
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 79
1021
Fault meaningModels and manual pages
Domestic hot-water or cylinder charging temperature sensor fault, according to the hot-water arrangement.
Worcester Bosch (8)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 91
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 84
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 75
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 74
  • Greenstar 8000 Life GR8300iW combi 30, 35, 40, 45, 50 C6720883865 · 2021/11 · PDF p. 78
  • Greenstar 8000 Style GR8700iW combi 30, 35, 40, 45, 50 C/CB6720883864 · 2021/09 · PDF p. 76
  • Greenstar 8000+ GR8701iW combi 32 C V2, 36/40/45/50 C; Style 32 CB V2, 36 CB6721108973 · 2025/06 · PDF p. 76
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 85
1022
Fault meaningModels and manual pages
On a system with a cylinder sensor, the cylinder temperature signal or its connection is faulty.
Worcester Bosch (7)
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 74
  • Greenstar 8000 Life GR8300iW regular 30, 35, 40, 45, 50 R6720883866 · 2021/09 · PDF p. 72
  • Greenstar 8000 Life GR8300iW system 30, 35 S6720883858 · 2021/09 · PDF p. 74
  • Greenstar 8000 Style GR8700iW system 30, 35 S/SB6720883855 · 2021/09 · PDF p. 77
  • Greenstar 8000+ GR8701iW regular 30, 35, 40, 45, 50 R6721891104 · 2024/06 · PDF p. 73
  • Greenstar 8000+ GR8701iW system 30, 35 S6721891100 · 2024/06 · PDF p. 78
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 79
1025
Fault meaningModels and manual pages
Heating return thermistor circuit fault.
Worcester Bosch (2)
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 85
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 79
1027
Fault meaningModels and manual pages
The optional DHW preheat kit inlet temperature sensor is disconnected.
Worcester Bosch (1)
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 84
1037
Fault meaningModels and manual pages
Outside temperature sensor signal fault on a weather-compensated installation. Heating can enter backup operation.
Worcester Bosch (13)
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 84
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 75
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 74
  • Greenstar 8000 Life GR8300iW combi 30, 35, 40, 45, 50 C6720883865 · 2021/11 · PDF p. 78
  • Greenstar 8000 Life GR8300iW regular 30, 35, 40, 45, 50 R6720883866 · 2021/09 · PDF p. 72
  • Greenstar 8000 Life GR8300iW system 30, 35 S6720883858 · 2021/09 · PDF p. 74
  • Greenstar 8000 Style GR8700iW combi 30, 35, 40, 45, 50 C/CB6720883864 · 2021/09 · PDF p. 77
  • Greenstar 8000 Style GR8700iW system 30, 35 S/SB6720883855 · 2021/09 · PDF p. 77
  • Greenstar 8000+ GR8701iW combi 32 C V2, 36/40/45/50 C; Style 32 CB V2, 36 CB6721108973 · 2025/06 · PDF p. 77
  • Greenstar 8000+ GR8701iW regular 30, 35, 40, 45, 50 R6721891104 · 2024/06 · PDF p. 73
  • Greenstar 8000+ GR8701iW system 30, 35 S6721891100 · 2024/06 · PDF p. 78
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 85
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 79
1068
Fault meaningModels and manual pages
Outside-temperature sensor or lambda probe fault, as applicable to the fitted equipment.
Worcester Bosch (14)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 91
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 84
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 75
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 75
  • Greenstar 8000 Life GR8300iW combi 30, 35, 40, 45, 50 C6720883865 · 2021/11 · PDF p. 78
  • Greenstar 8000 Life GR8300iW regular 30, 35, 40, 45, 50 R6720883866 · 2021/09 · PDF p. 72
  • Greenstar 8000 Life GR8300iW system 30, 35 S6720883858 · 2021/09 · PDF p. 74
  • Greenstar 8000 Style GR8700iW combi 30, 35, 40, 45, 50 C/CB6720883864 · 2021/09 · PDF p. 77
  • Greenstar 8000 Style GR8700iW system 30, 35 S/SB6720883855 · 2021/09 · PDF p. 77
  • Greenstar 8000+ GR8701iW combi 32 C V2, 36/40/45/50 C; Style 32 CB V2, 36 CB6721108973 · 2025/06 · PDF p. 77
  • Greenstar 8000+ GR8701iW regular 30, 35, 40, 45, 50 R6721891104 · 2024/06 · PDF p. 73
  • Greenstar 8000+ GR8701iW system 30, 35 S6721891100 · 2024/06 · PDF p. 78
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 85
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 79
1073
Fault meaningModels and manual pages
Heating flow temperature sensor circuit reads short.
Worcester Bosch (4)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 91
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 84
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 76
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 75
1074
Fault meaningModels and manual pages
No signal reaches the boiler from the flow temperature sensor.
Worcester Bosch (4)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 91
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 84
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 76
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 75
1075
Fault meaningModels and manual pages
Heat exchanger temperature sensor circuit reads short.
Worcester Bosch (13)
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 84
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 76
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 75
  • Greenstar 8000 Life GR8300iW combi 30, 35, 40, 45, 50 C6720883865 · 2021/11 · PDF p. 78
  • Greenstar 8000 Life GR8300iW regular 30, 35, 40, 45, 50 R6720883866 · 2021/09 · PDF p. 72
  • Greenstar 8000 Life GR8300iW system 30, 35 S6720883858 · 2021/09 · PDF p. 74
  • Greenstar 8000 Style GR8700iW combi 30, 35, 40, 45, 50 C/CB6720883864 · 2021/09 · PDF p. 77
  • Greenstar 8000 Style GR8700iW system 30, 35 S/SB6720883855 · 2021/09 · PDF p. 77
  • Greenstar 8000+ GR8701iW combi 32 C V2, 36/40/45/50 C; Style 32 CB V2, 36 CB6721108973 · 2025/06 · PDF p. 77
  • Greenstar 8000+ GR8701iW regular 30, 35, 40, 45, 50 R6721891104 · 2024/06 · PDF p. 73
  • Greenstar 8000+ GR8701iW system 30, 35 S6721891100 · 2024/06 · PDF p. 78
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 86
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 79
1076
Fault meaningModels and manual pages
The heat exchanger temperature sensor circuit is disconnected.
Worcester Bosch (13)
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 84
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 76
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 75
  • Greenstar 8000 Life GR8300iW combi 30, 35, 40, 45, 50 C6720883865 · 2021/11 · PDF p. 78
  • Greenstar 8000 Life GR8300iW regular 30, 35, 40, 45, 50 R6720883866 · 2021/09 · PDF p. 73
  • Greenstar 8000 Life GR8300iW system 30, 35 S6720883858 · 2021/09 · PDF p. 74
  • Greenstar 8000 Style GR8700iW combi 30, 35, 40, 45, 50 C/CB6720883864 · 2021/09 · PDF p. 77
  • Greenstar 8000 Style GR8700iW system 30, 35 S/SB6720883855 · 2021/09 · PDF p. 77
  • Greenstar 8000+ GR8701iW combi 32 C V2, 36/40/45/50 C; Style 32 CB V2, 36 CB6721108973 · 2025/06 · PDF p. 77
  • Greenstar 8000+ GR8701iW regular 30, 35, 40, 45, 50 R6721891104 · 2024/06 · PDF p. 74
  • Greenstar 8000+ GR8701iW system 30, 35 S6721891100 · 2024/06 · PDF p. 78
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 86
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 80
2963
Fault meaningModels and manual pages
Heat exchanger or flow temperature signals are implausible.
Worcester Bosch (14)
  • Greenstar 1000 GR1000W 24 C NG, 30 C NG6721835943 · 2023/08 · PDF p. 93
  • Greenstar 2000 GR2301iW 25 C, 30 C6721839340 · 2023/06 · PDF p. 87
  • Greenstar 4000 GR4700iW combi 25 C, 30 C6720891161 · 2021/10 · PDF p. 78
  • Greenstar 4000 GR4700iW system 12 S, 15 S, 18 S, 21 S, 24 S6720891162 · 2020/09 · PDF p. 77
  • Greenstar 8000 Life GR8300iW combi 30, 35, 40, 45, 50 C6720883865 · 2021/11 · PDF p. 80
  • Greenstar 8000 Life GR8300iW regular 30, 35, 40, 45, 50 R6720883866 · 2021/09 · PDF p. 74
  • Greenstar 8000 Life GR8300iW system 30, 35 S6720883858 · 2021/09 · PDF p. 76
  • Greenstar 8000 Style GR8700iW combi 30, 35, 40, 45, 50 C/CB6720883864 · 2021/09 · PDF p. 78
  • Greenstar 8000 Style GR8700iW system 30, 35 S/SB6720883855 · 2021/09 · PDF p. 79
  • Greenstar 8000+ GR8701iW combi 32 C V2, 36/40/45/50 C; Style 32 CB V2, 36 CB6721108973 · 2025/06 · PDF p. 78
  • Greenstar 8000+ GR8701iW regular 30, 35, 40, 45, 50 R6721891104 · 2024/06 · PDF p. 75
  • Greenstar 8000+ GR8701iW system 30, 35 S6721891100 · 2024/06 · PDF p. 80
  • Greenstar 8000F GR8700iF 35 C, 50 C6721106419 · 2024/11 · PDF p. 88
  • Greenstar 8000F GR8700iF 35 R, 50 R6721106420 · 2024/11 · PDF p. 82
A02
Fault meaningModels and manual pages
The high-limit thermostat circuit has triggered a fault.
Vokèra (4)
  • Compact 25A DIN, Compact 32A DIN20166162 · 06/2019 Edition0 · PDF p. 7
  • Compact 29A DINCod. 20099258 - Ed. 2 - 03/17 · Cod. 20099258 - Ed. 2 - 03/17 · PDF p. 6
  • Easi-Heat Plus 25Ci, Easi-Heat Plus 29Ci, Easi-Heat Plus 32CiCod. 20158260 - 06/19 - Ed. 0 · Cod. 20158260 - 06/19 - Ed. 0 · PDF p. 8
  • Mynute i25 ErP (GC 41-094-96)Cod. 20100889 - 11/16 - Ed. 4 · Cod. 20100889 - 11/16 - Ed. 4 · PDF p. 7
A3
Fault meaningModels and manual pages
The flue temperature sensor is incorrectly positioned.
Viessmann (2)
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
A06
Fault meaningModels and manual pages
The domestic hot-water temperature probe circuit reports a fault.
Vokèra (3)
  • Compact 25A DIN, Compact 32A DIN20166162 · 06/2019 Edition0 · PDF p. 7
  • Compact 29A DINCod. 20099258 - Ed. 2 - 03/17 · Cod. 20099258 - Ed. 2 - 03/17 · PDF p. 6
  • Easi-Heat Plus 25Ci, Easi-Heat Plus 29Ci, Easi-Heat Plus 32CiCod. 20158260 - 06/19 - Ed. 0 · Cod. 20158260 - 06/19 - Ed. 0 · PDF p. 8
A07
Fault meaningModels and manual pages
Flow-side alarm. The manual lists a probe fault, excessive flow temperature or a flow/return temperature difference.
Vokèra (4)
  • Compact 25A DIN, Compact 32A DIN20166162 · 06/2019 Edition0 · PDF p. 7
  • Compact 29A DINCod. 20099258 - Ed. 2 - 03/17 · Cod. 20099258 - Ed. 2 - 03/17 · PDF p. 6
  • Easi-Heat Plus 25Ci, Easi-Heat Plus 29Ci, Easi-Heat Plus 32CiCod. 20158260 - 06/19 - Ed. 0 · Cod. 20158260 - 06/19 - Ed. 0 · PDF p. 8
  • Mynute i25 ErP (GC 41-094-96)Cod. 20100889 - 11/16 - Ed. 4 · Cod. 20100889 - 11/16 - Ed. 4 · PDF p. 7
A7
Fault meaningModels and manual pages
Domestic hot-water thermistor circuit fault.
Worcester Bosch (2)
  • Greenstar CDi Classic ErP combi 29, 34, 38, 42 CDi6720815725 · 2015/11 · PDF p. 54
  • Greenstar Highflow 440CDi and 550CDi ErP6720818077 · 2016/04 · PDF p. 47
The hot-water NTC circuit reports a fault, where a cylinder sensor is fitted.
Worcester Bosch (1)
  • Greenstar CDi Classic ErP system 30, 35 CDi6720815724 · 2015/11 · PDF p. 52
A7 808
Fault meaningModels and manual pages
Domestic hot-water thermistor circuit fault.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 64
  • Greenstar 25i and 30i ErP combi6720806944 · 2015/07 · PDF p. 67
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 66
A08
Fault meaningModels and manual pages
Return-side alarm. The manual lists a probe fault, excessive return temperature or a flow/return temperature difference.
Vokèra (4)
  • Compact 25A DIN, Compact 32A DIN20166162 · 06/2019 Edition0 · PDF p. 7
  • Compact 29A DINCod. 20099258 - Ed. 2 - 03/17 · Cod. 20099258 - Ed. 2 - 03/17 · PDF p. 6
  • Easi-Heat Plus 25Ci, Easi-Heat Plus 29Ci, Easi-Heat Plus 32CiCod. 20158260 - 06/19 - Ed. 0 · Cod. 20158260 - 06/19 - Ed. 0 · PDF p. 8
  • Mynute i25 ErP (GC 41-094-96)Cod. 20100889 - 11/16 - Ed. 4 · Cod. 20100889 - 11/16 - Ed. 4 · PDF p. 7
A09
Fault meaningModels and manual pages
Flue probe alarm. The table includes a probe or counter fault and a high flue-temperature trip.
Vokèra (4)
  • Compact 25A DIN, Compact 32A DIN20166162 · 06/2019 Edition0 · PDF p. 7
  • Compact 29A DINCod. 20099258 - Ed. 2 - 03/17 · Cod. 20099258 - Ed. 2 - 03/17 · PDF p. 6
  • Easi-Heat Plus 25Ci, Easi-Heat Plus 29Ci, Easi-Heat Plus 32CiCod. 20158260 - 06/19 - Ed. 0 · Cod. 20158260 - 06/19 - Ed. 0 · PDF p. 8
  • Mynute i25 ErP (GC 41-094-96)Cod. 20100889 - 11/16 - Ed. 4 · Cod. 20100889 - 11/16 - Ed. 4 · PDF p. 7
A20
Fault meaningModels and manual pages
The high-limit thermostat circuit has triggered a fault.
Vokèra (4)
  • Easi-Heat i 20S, Easi-Heat i 25SCod. 20206105 - 02/26 - Ed. 2 · Cod. 20206105 - 02/26 - Ed. 2 · PDF p. 7
  • Easi-Heat i 25C / 29C (GC 47-364-71, -72 NG; -73, -74 LPG)20195442 · 10/22 Ed.3 · PDF p. 8
  • Vibe MAX 20S, Vibe MAX 25SCod. 20188984 - 10/22 - Ed. 2 · Cod. 20188984 - 10/22 - Ed. 2 · PDF p. 7
  • Vibe MAX 26C, Vibe MAX 30CCod. 20188246 - 11/22 - Ed. 3 · Cod. 20188246 - 11/22 - Ed. 3 · PDF p. 8
A60
Fault meaningModels and manual pages
The domestic hot-water temperature probe circuit reports a fault.
Vokèra (2)
  • Easi-Heat i 25C / 29C (GC 47-364-71, -72 NG; -73, -74 LPG)20195442 · 10/22 Ed.3 · PDF p. 8
  • Vibe MAX 26C, Vibe MAX 30CCod. 20188246 - 11/22 - Ed. 3 · Cod. 20188246 - 11/22 - Ed. 3 · PDF p. 8
A70
Fault meaningModels and manual pages
Flow-side alarm. The manual lists a probe fault, excessive flow temperature or a flow/return temperature difference.
Vokèra (4)
  • Easi-Heat i 20S, Easi-Heat i 25SCod. 20206105 - 02/26 - Ed. 2 · Cod. 20206105 - 02/26 - Ed. 2 · PDF p. 7
  • Easi-Heat i 25C / 29C (GC 47-364-71, -72 NG; -73, -74 LPG)20195442 · 10/22 Ed.3 · PDF p. 8
  • Vibe MAX 20S, Vibe MAX 25SCod. 20188984 - 10/22 - Ed. 2 · Cod. 20188984 - 10/22 - Ed. 2 · PDF p. 7
  • Vibe MAX 26C, Vibe MAX 30CCod. 20188246 - 11/22 - Ed. 3 · Cod. 20188246 - 11/22 - Ed. 3 · PDF p. 8
A77
Fault meaningModels and manual pages
Low-temperature thermostat circuit alarm.
Vokèra (4)
  • Compact 25A DIN, Compact 32A DIN20166162 · 06/2019 Edition0 · PDF p. 7
  • Compact 29A DINCod. 20099258 - Ed. 2 - 03/17 · Cod. 20099258 - Ed. 2 - 03/17 · PDF p. 6
  • Easi-Heat Plus 25Ci, Easi-Heat Plus 29Ci, Easi-Heat Plus 32CiCod. 20158260 - 06/19 - Ed. 0 · Cod. 20158260 - 06/19 - Ed. 0 · PDF p. 8
  • Mynute i25 ErP (GC 41-094-96)Cod. 20100889 - 11/16 - Ed. 4 · Cod. 20100889 - 11/16 - Ed. 4 · PDF p. 7
A80
Fault meaningModels and manual pages
Return-side alarm. The manual lists a probe fault, excessive return temperature or a flow/return temperature difference.
Vokèra (4)
  • Easi-Heat i 20S, Easi-Heat i 25SCod. 20206105 - 02/26 - Ed. 2 · Cod. 20206105 - 02/26 - Ed. 2 · PDF p. 7
  • Easi-Heat i 25C / 29C (GC 47-364-71, -72 NG; -73, -74 LPG)20195442 · 10/22 Ed.3 · PDF p. 8
  • Vibe MAX 20S, Vibe MAX 25SCod. 20188984 - 10/22 - Ed. 2 · Cod. 20188984 - 10/22 - Ed. 2 · PDF p. 7
  • Vibe MAX 26C, Vibe MAX 30CCod. 20188246 - 11/22 - Ed. 3 · Cod. 20188246 - 11/22 - Ed. 3 · PDF p. 8
A90
Fault meaningModels and manual pages
The flue temperature probe circuit reports a fault.
Vokèra (4)
  • Easi-Heat i 20S, Easi-Heat i 25SCod. 20206105 - 02/26 - Ed. 2 · Cod. 20206105 - 02/26 - Ed. 2 · PDF p. 7
  • Easi-Heat i 25C / 29C (GC 47-364-71, -72 NG; -73, -74 LPG)20195442 · 10/22 Ed.3 · PDF p. 8
  • Vibe MAX 20S, Vibe MAX 25SCod. 20188984 - 10/22 - Ed. 2 · Cod. 20188984 - 10/22 - Ed. 2 · PDF p. 7
  • Vibe MAX 26C, Vibe MAX 30CCod. 20188246 - 11/22 - Ed. 3 · Cod. 20188246 - 11/22 - Ed. 3 · PDF p. 8
A 02
Fault meaningModels and manual pages
The high-limit thermostat circuit has triggered a fault.
Vokèra (1)
  • Verve (47 kW input / about 50 kW condensing output)20040022 — 09/11 Ed.1 · PDF p. 6
A 04
Fault meaningModels and manual pages
Overheating may have tripped the safety thermostat.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
A 07
Fault meaningModels and manual pages
Flow-side alarm. The manual lists a probe fault, excessive flow temperature or a flow/return temperature difference.
Vokèra (1)
  • Verve (47 kW input / about 50 kW condensing output)20040022 — 09/11 Ed.1 · PDF p. 6
The low-temperature zone safety thermostat has operated, where fitted.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
A 08
Fault meaningModels and manual pages
Return-side alarm. The manual lists a probe fault, excessive return temperature or a flow/return temperature difference.
Vokèra (1)
  • Verve (47 kW input / about 50 kW condensing output)20040022 — 09/11 Ed.1 · PDF p. 6
A 09
Fault meaningModels and manual pages
Flue probe alarm. Its LED pattern distinguishes probe or heat-exchanger cleaning indications from the flue high-limit trip.
Vokèra (1)
  • Verve (47 kW input / about 50 kW condensing output)20040022 — 09/11 Ed.1 · PDF p. 6
A 77
Fault meaningModels and manual pages
The underfloor heating thermostat has raised an alarm.
Vokèra (1)
  • Verve (47 kW input / about 50 kW condensing output)20040022 — 09/11 Ed.1 · PDF p. 6
A.00.28
Fault meaningModels and manual pages
Solar temperature sensor is disconnected or reads below its range, where fitted.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 76
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 50
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 76
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 48
A.00.29
Fault meaningModels and manual pages
Solar temperature sensor is short-circuited or reads above its range, where fitted.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 76
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 50
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 76
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 48
A.00.34
Fault meaningModels and manual pages
An outdoor temperature sensor is configured but its signal is missing.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 76
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 50
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 76
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 48
AL20
Fault meaningModels and manual pages
The high-limit thermostat circuit has triggered a fault.
Vokèra (2)
  • Mynute 15VHE10030244 — 07/07 Ed.1 · PDF p. 29
  • Mynute 20VHEvokera-mynute-20vhe · PDF p. 29
Limit thermostat or flue thermostat fault.
Vokèra (1)
  • Easi-Heat Plus 18Vvokera-easiheat-plus-18v · PDF p. 30
AL71
Fault meaningModels and manual pages
The central-heating flow probe circuit reports a fault.
Vokèra (3)
  • Easi-Heat Plus 18Vvokera-easiheat-plus-18v · PDF p. 30
  • Mynute 15VHE10030244 — 07/07 Ed.1 · PDF p. 29
  • Mynute 20VHEvokera-mynute-20vhe · PDF p. 29
AL73
Fault meaningModels and manual pages
The heating return probe circuit reports a fault.
Vokèra (3)
  • Easi-Heat Plus 18Vvokera-easiheat-plus-18v · PDF p. 30
  • Mynute 15VHE10030244 — 07/07 Ed.1 · PDF p. 29
  • Mynute 20VHEvokera-mynute-20vhe · PDF p. 29
b0
Fault meaningModels and manual pages
Short circuit at the flue gas temperature sensor.
Viessmann (4)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 49
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 33
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
b8
Fault meaningModels and manual pages
Open circuit at the flue gas temperature sensor.
Viessmann (4)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 49
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 49
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 33
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 41
CC 800
Fault meaningModels and manual pages
The optional outdoor sensor reports a fault.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 64
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 64
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 66
The accessory outside temperature sensor is reporting a fault.
Worcester Bosch (2)
  • Greenstar 25i and 30i ErP combi6720806944 · 2015/07 · PDF p. 66
  • Greenstar 9i, 12i, 15i, 18i, 21i and 24i System ErP6720806945 · 2015/07 · PDF p. 68
D1 240
Fault meaningModels and manual pages
Return temperature sensor circuit reads short.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 70
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 70
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 72
D1 241
Fault meaningModels and manual pages
Return temperature sensor circuit is disconnected.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 70
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 70
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 72
d3
Fault meaningModels and manual pages
The external temperature limiter connection reports an interruption.
Worcester Bosch (2)
  • Greenstar FS 30CDi and 42CDi Regular ErP6720818079 · 2016/04 · PDF p. 41
  • Greenstar Highflow 440CDi and 550CDi ErP6720818077 · 2016/04 · PDF p. 47
E02
Fault meaningModels and manual pages
The safety thermostat has operated and the boiler has locked out.
Biasi (7)
  • Basica Cond 24C, Basica Cond 28C, Basica Cond 32Cbiasi-basica-combi · PDF p. 10
  • Basica Cond 28Sbiasi-basica-system · PDF p. 10
  • Dina 25C, Dina 30C, Dina 35Cbiasi-dina-combi · PDF p. 9
  • Inovia 25C ErP, Inovia 30C ErP, Inovia 35C ErP17962.2197.4 · PDF p. 13
  • Inovia 25S ErPbiasi-inovia-system-2020 · PDF p. 11
  • RinNova Adaptive 25C, RinNova Adaptive 30C, RinNova Adaptive 35Cbiasi-rinnova-combi · PDF p. 10
  • RinNova Adaptive 30S17962.3483.0 · PDF p. 13
E2
Fault meaningModels and manual pages
Heating flow thermistor circuit fault.
Worcester Bosch (5)
  • Greenstar CDi Classic ErP combi 29, 34, 38, 42 CDi6720815725 · 2015/11 · PDF p. 54
  • Greenstar CDi Classic ErP regular 30, 40 CDi6720815723 · 2015/05 · PDF p. 45
  • Greenstar CDi Classic ErP system 30, 35 CDi6720815724 · 2015/11 · PDF p. 52
  • Greenstar FS 30CDi and 42CDi Regular ErP6720818079 · 2016/04 · PDF p. 41
  • Greenstar Highflow 440CDi and 550CDi ErP6720818077 · 2016/04 · PDF p. 47
E2 222
Fault meaningModels and manual pages
Flow temperature sensor circuit reads short.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 70
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 70
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 72
Heating flow temperature sensor circuit reads short.
Worcester Bosch (2)
  • Greenstar 25i and 30i ErP combi6720806944 · 2015/07 · PDF p. 64
  • Greenstar 9i, 12i, 15i, 18i, 21i and 24i System ErP6720806945 · 2015/07 · PDF p. 66
E2 223
Fault meaningModels and manual pages
Flow temperature sensor circuit is disconnected.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 70
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 70
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 72
Heating flow temperature sensor circuit is disconnected.
Worcester Bosch (2)
  • Greenstar 25i and 30i ErP combi6720806944 · 2015/07 · PDF p. 64
  • Greenstar 9i, 12i, 15i, 18i, 21i and 24i System ErP6720806945 · 2015/07 · PDF p. 66
E2 350
Fault meaningModels and manual pages
The heating flow sensor circuit reads short.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 64
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 64
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 66
Heating flow temperature sensor circuit reads short.
Worcester Bosch (2)
  • Greenstar 25i and 30i ErP combi6720806944 · 2015/07 · PDF p. 64
  • Greenstar 9i, 12i, 15i, 18i, 21i and 24i System ErP6720806945 · 2015/07 · PDF p. 66
E2 351
Fault meaningModels and manual pages
The heating flow sensor circuit is open.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 64
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 64
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 66
Heating flow temperature sensor circuit is disconnected.
Worcester Bosch (2)
  • Greenstar 25i and 30i ErP combi6720806944 · 2015/07 · PDF p. 64
  • Greenstar 9i, 12i, 15i, 18i, 21i and 24i System ErP6720806945 · 2015/07 · PDF p. 66
E06
Fault meaningModels and manual pages
Fault on the central-heating flow NTC circuit.
Biasi (7)
  • Basica Cond 24C, Basica Cond 28C, Basica Cond 32Cbiasi-basica-combi · PDF p. 10
  • Basica Cond 28Sbiasi-basica-system · PDF p. 10
  • Dina 25C, Dina 30C, Dina 35Cbiasi-dina-combi · PDF p. 9
  • Inovia 25C ErP, Inovia 30C ErP, Inovia 35C ErP17962.2197.4 · PDF p. 13
  • Inovia 25S ErPbiasi-inovia-system-2020 · PDF p. 11
  • RinNova Adaptive 25C, RinNova Adaptive 30C, RinNova Adaptive 35Cbiasi-rinnova-combi · PDF p. 10
  • RinNova Adaptive 30S17962.3483.0 · PDF p. 13
E07
Fault meaningModels and manual pages
Fault on the hot-water NTC circuit.
Biasi (4)
  • Basica Cond 24C, Basica Cond 28C, Basica Cond 32Cbiasi-basica-combi · PDF p. 10
  • Basica Cond 28Sbiasi-basica-system · PDF p. 10
  • Dina 25C, Dina 30C, Dina 35Cbiasi-dina-combi · PDF p. 9
  • Inovia 25C ErP, Inovia 30C ErP, Inovia 35C ErP17962.2197.4 · PDF p. 13
Fault on the hot-water or cylinder temperature probe, according to the installation.
Biasi (2)
  • RinNova Adaptive 25C, RinNova Adaptive 30C, RinNova Adaptive 35Cbiasi-rinnova-combi · PDF p. 10
  • RinNova Adaptive 30S17962.3483.0 · PDF p. 13
E08
Fault meaningModels and manual pages
Fault on the outdoor temperature probe circuit.
Biasi (6)
  • Basica Cond 24C, Basica Cond 28C, Basica Cond 32Cbiasi-basica-combi · PDF p. 10
  • Basica Cond 28Sbiasi-basica-system · PDF p. 10
  • Dina 25C, Dina 30C, Dina 35Cbiasi-dina-combi · PDF p. 9
  • Inovia 25C ErP, Inovia 30C ErP, Inovia 35C ErP17962.2197.4 · PDF p. 13
  • RinNova Adaptive 25C, RinNova Adaptive 30C, RinNova Adaptive 35Cbiasi-rinnova-combi · PDF p. 11
  • RinNova Adaptive 30S17962.3483.0 · PDF p. 13
The outdoor temperature probe reports a fault with weather compensation configured.
Biasi (1)
  • Inovia 25S ErPbiasi-inovia-system-2020 · PDF p. 11
E09
Fault meaningModels and manual pages
The flue NTC circuit is interrupted.
Biasi (3)
  • Basica Cond 24C, Basica Cond 28C, Basica Cond 32Cbiasi-basica-combi · PDF p. 10
  • Basica Cond 28Sbiasi-basica-system · PDF p. 10
  • Dina 25C, Dina 30C, Dina 35Cbiasi-dina-combi · PDF p. 9
Fault on the flue NTC circuit.
Biasi (2)
  • Inovia 25C ErP, Inovia 30C ErP, Inovia 35C ErP17962.2197.4 · PDF p. 13
  • Inovia 25S ErPbiasi-inovia-system-2020 · PDF p. 11
E9
Fault meaningModels and manual pages
The heating high-limit thermostat circuit has tripped.
Worcester Bosch (5)
  • Greenstar CDi Classic ErP combi 29, 34, 38, 42 CDi6720815725 · 2015/11 · PDF p. 54
  • Greenstar CDi Classic ErP regular 30, 40 CDi6720815723 · 2015/05 · PDF p. 45
  • Greenstar CDi Classic ErP system 30, 35 CDi6720815724 · 2015/11 · PDF p. 52
  • Greenstar FS 30CDi and 42CDi Regular ErP6720818079 · 2016/04 · PDF p. 41
  • Greenstar Highflow 440CDi and 550CDi ErP6720818077 · 2016/04 · PDF p. 47
E9 220
Fault meaningModels and manual pages
Heat exchanger safety temperature sensor circuit reads short.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 70
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 70
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 72
E9 221
Fault meaningModels and manual pages
Heat exchanger safety temperature sensor circuit is open.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 70
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 70
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 72
E9 224
Fault meaningModels and manual pages
The maximum-temperature safety thermostat circuit has operated.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 70
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 70
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 72
The flue or high-limit thermostat safety circuit has operated.
Worcester Bosch (2)
  • Greenstar 25i and 30i ErP combi6720806944 · 2015/07 · PDF p. 67
  • Greenstar 9i, 12i, 15i, 18i, 21i and 24i System ErP6720806945 · 2015/07 · PDF p. 69
E10
Fault meaningModels and manual pages
The flue temperature protection has operated.
Biasi (5)
  • Basica Cond 24C, Basica Cond 28C, Basica Cond 32Cbiasi-basica-combi · PDF p. 10
  • Basica Cond 28Sbiasi-basica-system · PDF p. 10
  • Dina 25C, Dina 30C, Dina 35Cbiasi-dina-combi · PDF p. 10
  • Inovia 25C ErP, Inovia 30C ErP, Inovia 35C ErP17962.2197.4 · PDF p. 13
  • Inovia 25S ErPbiasi-inovia-system-2020 · PDF p. 11
Flue probe or thermal-fuse protection has tripped.
Biasi (2)
  • RinNova Adaptive 25C, RinNova Adaptive 30C, RinNova Adaptive 35Cbiasi-rinnova-combi · PDF p. 11
  • RinNova Adaptive 30S17962.3483.0 · PDF p. 13
E12
Fault meaningModels and manual pages
Fault on the central-heating return NTC circuit.
Biasi (7)
  • Basica Cond 24C, Basica Cond 28C, Basica Cond 32Cbiasi-basica-combi · PDF p. 10
  • Basica Cond 28Sbiasi-basica-system · PDF p. 10
  • Dina 25C, Dina 30C, Dina 35Cbiasi-dina-combi · PDF p. 10
  • Inovia 25C ErP, Inovia 30C ErP, Inovia 35C ErP17962.2197.4 · PDF p. 13
  • Inovia 25S ErPbiasi-inovia-system-2020 · PDF p. 11
  • RinNova Adaptive 25C, RinNova Adaptive 30C, RinNova Adaptive 35Cbiasi-rinnova-combi · PDF p. 11
  • RinNova Adaptive 30S17962.3483.0 · PDF p. 13
E19
Fault meaningModels and manual pages
Fault on the hot-water inlet temperature probe, where fitted.
Biasi (2)
  • Inovia 25C ErP, Inovia 30C ErP, Inovia 35C ErP17962.2197.4 · PDF p. 13
  • Inovia 25S ErPbiasi-inovia-system-2020 · PDF p. 11
E020
Fault meaningModels and manual pages
The high-limit thermostat circuit has triggered a fault.
Vokèra (12)
  • Pinnacle 20S, Pinnacle 25S20208437 · 10/26 Ed.5 · PDF p. 7
  • Pinnacle 25C, Pinnacle 30C, Pinnacle 35C20208435 · 10/26 Ed.5 · PDF p. 7
  • Synergy 20S, Synergy 25S, Synergy 32Svokera-synergy-s-20208494-5 · PDF p. 5
  • Synergy 25C, Synergy 30C, Synergy 35Cvokera-synergy-c-20208493-8 · PDF p. 5
  • Unica MAX 20S, Unica MAX 30SCod. 20188401 - 11/21 - Ed. 2 · Cod. 20188401 - 11/21 - Ed. 2 · PDF p. 39
  • Unica MAX 30C20188258 · PDF p. 39
  • Unica MAX 35C, Unica MAX 40CCod. 20188258 - 10/21 - Ed. 2 · Cod. 20188258 - 10/21 - Ed. 2 · PDF p. 39
  • Vision Plus 20S, Vision Plus 25S, Vision Plus 30SCod. 20174791 - 07/20 - Ed. 2 · Cod. 20174791 - 07/20 - Ed. 2 · PDF p. 8
  • Vision Plus 25C, Vision Plus 30CCod. 20173523 - 04/20 - Ed. 0 · Cod. 20173523 - 04/20 - Ed. 0 · PDF p. 8
  • Vision Plus 35C, Vision Plus 40CCod. 20174438 - 07 /20 - Ed. 2 · Cod. 20174438 - 07 /20 - Ed. 2 · PDF p. 8
  • evolve 18S, evolve 24S, evolve 30S, evolve 35Svokera-evolve-s-20127584-6 · PDF p. 44
  • evolve 24C, evolve 28C, evolve 32C, evolve 36C, evolve 42Cvokera-evolve-c-20131172-6 · PDF p. 48
E20
Fault meaningModels and manual pages
The central heating flow thermistor circuit reports a fault.
Baxi (20)
  • 100 Combi 124/1287659607-02 · 04/17 · PDF p. 46
  • 600 Combi 624/630/636, including LPG (first generation)7717521-03 · PDF p. 64
  • 600 System 615/618/624 and 624 LPG (first generation)7686961-01 · PDF p. 56
  • 800 Combi 825/830/836 (first generation)7728205-01 · PDF p. 64
  • 800 System 818/824 (first generation)7729931-01 · PDF p. 56
  • Assure Combi 25/30/36, including LPG7750729-01 · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7750878-01 · PDF p. 56
  • Duo-tec Combi ErP 24/28/33/40 and 28 LPG7219665-02 · 10/15 · PDF p. 46
  • Duo-tec Compact Combi 25/30/367844480-01 · PDF p. 66
  • EcoBlue Advance Combi 24/28/33/407219715-03 · 04/17 · PDF p. 64
  • EcoBlue Plus Combi 24/28/337219706-03 · 09/16 · PDF p. 65
  • EcoBlue System ErP 12/15/18/24/28/327219708-03 · 03/17 · PDF p. 64
  • Main Eco Compact Combi 25/307908748-v01;7908748-001-01 · 30/10/2025 · PDF p. 58
  • Main Eco Compact System 15/187716600-02 · PDF p. 57
  • Megaflo Compact System 15/18/247846467-01 · PDF p. 58
  • Megaflo System ErP 15/18/24/28/327647625-04 · 05/2017 · PDF p. 43
  • Platinum Combi ErP 24/28/33/407647627-02 · 9/16 · PDF p. 48
  • Platinum Compact Combi 25/30/367846425-01 · PDF p. 66
  • Platinum+ 32 System7753842-01 · 2/20 · PDF p. 43
  • Platinum+ 40 Combi7734477-01 · 7/19 · PDF p. 48
Potterton (10)
  • Assure Combi 25/30/36 and 25/30 LPG7717311-01 (printed back cover; URL contains older number 7678846) · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7717352-01 (printed back cover) · PDF p. 56
  • Gold Combi ErP 24/28/33 and 28 LPG7654263-03 · 05/17 · PDF p. 48
  • Gold System ErP 18/24/287654288-01 · 02/16 · PDF p. 43
  • Promax 24 Store ErP (90/115/150 litre)7221756-01 · 04/15 · PDF p. 47
  • Promax Combi ErP 24/28/337654260-03 · 03/17 · PDF p. 47
  • Promax System ErP 12/15/18/24/327654291-04 · 03/17 · PDF p. 45
  • Promax Ultra Combi ErP 24/28/33/407654258-07 · 07/17 · PDF p. 47
  • Titanium Combi ErP 24/28/33/407654277-02 · 11/16 · PDF p. 49
  • Ultra System 12/15/18/24/287673139-01 · 03/17 · PDF p. 43
E26
Fault meaningModels and manual pages
The two heating NTC readings disagree beyond the permitted range.
Biasi (2)
  • RinNova Adaptive 25C, RinNova Adaptive 30C, RinNova Adaptive 35Cbiasi-rinnova-combi · PDF p. 11
  • RinNova Adaptive 30S17962.3483.0 · PDF p. 13
E28
Fault meaningModels and manual pages
The flue temperature sensor circuit reports a fault.
Baxi (16)
  • Main Eco Compact Combi 25/307908748-v01;7908748-001-01 · 30/10/2025 · PDF p. 58Watch the E28 harness fault test · 06:09
  • 100 Combi 124/1287659607-02 · 04/17 · PDF p. 46
  • 600 Combi 624/630/636, including LPG (first generation)7717521-03 · PDF p. 64
  • 600 System 615/618/624 and 624 LPG (first generation)7686961-01 · PDF p. 56
  • 800 Combi 825/830/836 (first generation)7728205-01 · PDF p. 64
  • 800 System 818/824 (first generation)7729931-01 · PDF p. 56
  • Assure Combi 25/30/36, including LPG7750729-01 · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7750878-01 · PDF p. 56
  • Duo-tec Combi ErP 24/28/33/40 and 28 LPG7219665-02 · 10/15 · PDF p. 46
  • Duo-tec Compact Combi 25/30/367844480-01 · PDF p. 66
  • EcoBlue Advance Combi 24/28/33/407219715-03 · 04/17 · PDF p. 64
  • EcoBlue Plus Combi 24/28/337219706-03 · 09/16 · PDF p. 65
  • EcoBlue System ErP 12/15/18/24/28/327219708-03 · 03/17 · PDF p. 64
  • Main Eco Compact System 15/187716600-02 · PDF p. 57
  • Megaflo Compact System 15/18/247846467-01 · PDF p. 58
  • Platinum Compact Combi 25/30/367846425-01 · PDF p. 66
Potterton (4)
  • Assure Combi 25/30/36 and 25/30 LPG7717311-01 (printed back cover; URL contains older number 7678846) · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7717352-01 (printed back cover) · PDF p. 56
  • Promax Ultra Combi ErP 24/28/33/407654258-07 · 07/17 · PDF p. 47
  • Ultra System 12/15/18/24/287673139-01 · 03/17 · PDF p. 43
The fault can involve the flue thermistor, air pressure switch, wiring, blocked flue or condensate path.
Baxi (4)
  • Megaflo System ErP 15/18/24/28/327647625-04 · 05/2017 · PDF p. 43
  • Platinum Combi ErP 24/28/33/407647627-02 · 9/16 · PDF p. 48
  • Platinum+ 32 System7753842-01 · 2/20 · PDF p. 43
  • Platinum+ 40 Combi7734477-01 · 7/19 · PDF p. 48
Potterton (5)
  • Gold Combi ErP 24/28/33 and 28 LPG7654263-03 · 05/17 · PDF p. 48
  • Gold System ErP 18/24/287654288-01 · 02/16 · PDF p. 43
  • Promax Combi ErP 24/28/337654260-03 · 03/17 · PDF p. 47
  • Promax System ErP 12/15/18/24/327654291-04 · 03/17 · PDF p. 45
  • Titanium Combi ErP 24/28/33/407654277-02 · 11/16 · PDF p. 49
Fault on the cylinder temperature probe, where fitted.
Biasi (2)
  • Basica Cond 24C, Basica Cond 28C, Basica Cond 32Cbiasi-basica-combi · PDF p. 10
  • Basica Cond 28Sbiasi-basica-system · PDF p. 10
The model-specific error table identifies the hot-water thermistor circuit.
Potterton (1)
  • Promax 24 Store ErP (90/115/150 litre)7221756-01 · 04/15 · PDF p. 47
E40
Fault meaningModels and manual pages
The return-water thermistor circuit reports a fault.
Baxi (15)
  • Main Eco Compact Combi 25/307908748-v01;7908748-001-01 · 30/10/2025 · PDF p. 58Watch the return sensor fault test · 08:07Watch the PCB fault test with a healthy sensor and harness · 10:26
  • 100 Combi 124/1287659607-02 · 04/17 · PDF p. 46
  • 600 Combi 624/630/636, including LPG (first generation)7717521-03 · PDF p. 64
  • 600 System 615/618/624 and 624 LPG (first generation)7686961-01 · PDF p. 56
  • 800 Combi 825/830/836 (first generation)7728205-01 · PDF p. 64
  • 800 System 818/824 (first generation)7729931-01 · PDF p. 56
  • Assure Combi 25/30/36, including LPG7750729-01 · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7750878-01 · PDF p. 56
  • Duo-tec Compact Combi 25/30/367844480-01 · PDF p. 66
  • EcoBlue Advance Combi 24/28/33/407219715-03 · 04/17 · PDF p. 64
  • EcoBlue Plus Combi 24/28/337219706-03 · 09/16 · PDF p. 65
  • EcoBlue System ErP 12/15/18/24/28/327219708-03 · 03/17 · PDF p. 64
  • Main Eco Compact System 15/187716600-02 · PDF p. 57
  • Megaflo Compact System 15/18/247846467-01 · PDF p. 58
  • Platinum Compact Combi 25/30/367846425-01 · PDF p. 66
Potterton (4)
  • Assure Combi 25/30/36 and 25/30 LPG7717311-01 (printed back cover; URL contains older number 7678846) · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7717352-01 (printed back cover) · PDF p. 56
  • Promax Ultra Combi ErP 24/28/33/407654258-07 · 07/17 · PDF p. 47
  • Ultra System 12/15/18/24/287673139-01 · 03/17 · PDF p. 43
E50
Fault meaningModels and manual pages
The domestic hot-water thermistor circuit reports a fault.
Baxi (3)
  • Duo-tec Combi ErP 24/28/33/40 and 28 LPG7219665-02 · 10/15 · PDF p. 46
  • Platinum Combi ErP 24/28/33/407647627-02 · 9/16 · PDF p. 48
  • Platinum+ 40 Combi7734477-01 · 7/19 · PDF p. 48
Potterton (2)
  • Gold Combi ErP 24/28/33 and 28 LPG7654263-03 · 05/17 · PDF p. 48
  • Titanium Combi ErP 24/28/33/407654277-02 · 11/16 · PDF p. 49
The model-specific error table identifies the flue thermistor circuit.
Potterton (1)
  • Promax 24 Store ErP (90/115/150 litre)7221756-01 · 04/15 · PDF p. 47
E060
Fault meaningModels and manual pages
The domestic hot-water temperature probe circuit reports a fault.
Vokèra (7)
  • Pinnacle 25C, Pinnacle 30C, Pinnacle 35C20208435 · 10/26 Ed.5 · PDF p. 8
  • Synergy 25C, Synergy 30C, Synergy 35Cvokera-synergy-c-20208493-8 · PDF p. 5
  • Unica MAX 30C20188258 · PDF p. 39
  • Unica MAX 35C, Unica MAX 40CCod. 20188258 - 10/21 - Ed. 2 · Cod. 20188258 - 10/21 - Ed. 2 · PDF p. 39
  • Vision Plus 25C, Vision Plus 30CCod. 20173523 - 04/20 - Ed. 0 · Cod. 20173523 - 04/20 - Ed. 0 · PDF p. 8
  • Vision Plus 35C, Vision Plus 40CCod. 20174438 - 07 /20 - Ed. 2 · Cod. 20174438 - 07 /20 - Ed. 2 · PDF p. 8
  • evolve 24C, evolve 28C, evolve 32C, evolve 36C, evolve 42Cvokera-evolve-c-20131172-6 · PDF p. 48
E070
Fault meaningModels and manual pages
Flow-side alarm. The manual lists a probe fault, excessive flow temperature or a flow/return temperature difference.
Vokèra (8)
  • Unica MAX 20S, Unica MAX 30SCod. 20188401 - 11/21 - Ed. 2 · Cod. 20188401 - 11/21 - Ed. 2 · PDF p. 39
  • Unica MAX 30C20188258 · PDF p. 39
  • Unica MAX 35C, Unica MAX 40CCod. 20188258 - 10/21 - Ed. 2 · Cod. 20188258 - 10/21 - Ed. 2 · PDF p. 39
  • Vision Plus 20S, Vision Plus 25S, Vision Plus 30SCod. 20174791 - 07/20 - Ed. 2 · Cod. 20174791 - 07/20 - Ed. 2 · PDF p. 8
  • Vision Plus 25C, Vision Plus 30CCod. 20173523 - 04/20 - Ed. 0 · Cod. 20173523 - 04/20 - Ed. 0 · PDF p. 8
  • Vision Plus 35C, Vision Plus 40CCod. 20174438 - 07 /20 - Ed. 2 · Cod. 20174438 - 07 /20 - Ed. 2 · PDF p. 8
  • evolve 18S, evolve 24S, evolve 30S, evolve 35Svokera-evolve-s-20127584-6 · PDF p. 44
  • evolve 24C, evolve 28C, evolve 32C, evolve 36C, evolve 42Cvokera-evolve-c-20131172-6 · PDF p. 48
The central-heating flow probe circuit reports a fault.
Vokèra (4)
  • Pinnacle 20S, Pinnacle 25S20208437 · 10/26 Ed.5 · PDF p. 7
  • Pinnacle 25C, Pinnacle 30C, Pinnacle 35C20208435 · 10/26 Ed.5 · PDF p. 8
  • Synergy 20S, Synergy 25S, Synergy 32Svokera-synergy-s-20208494-5 · PDF p. 5
  • Synergy 25C, Synergy 30C, Synergy 35Cvokera-synergy-c-20208493-8 · PDF p. 5
E077
Fault meaningModels and manual pages
The boiler reports a fault at the main-zone water thermostat.
Vokèra (7)
  • Synergy 20S, Synergy 25S, Synergy 32Svokera-synergy-s-20208494-5 · PDF p. 5
  • Synergy 25C, Synergy 30C, Synergy 35Cvokera-synergy-c-20208493-8 · PDF p. 5
  • Unica MAX 20S, Unica MAX 30SCod. 20188401 - 11/21 - Ed. 2 · Cod. 20188401 - 11/21 - Ed. 2 · PDF p. 39
  • Unica MAX 30C20188258 · PDF p. 39
  • Unica MAX 35C, Unica MAX 40CCod. 20188258 - 10/21 - Ed. 2 · Cod. 20188258 - 10/21 - Ed. 2 · PDF p. 39
  • evolve 18S, evolve 24S, evolve 30S, evolve 35Svokera-evolve-s-20127584-6 · PDF p. 44
  • evolve 24C, evolve 28C, evolve 32C, evolve 36C, evolve 42Cvokera-evolve-c-20131172-6 · PDF p. 48
The main-zone or enabled zone 1 water thermostat has signalled.
Vokèra (3)
  • Vision Plus 20S, Vision Plus 25S, Vision Plus 30SCod. 20174791 - 07/20 - Ed. 2 · Cod. 20174791 - 07/20 - Ed. 2 · PDF p. 8
  • Vision Plus 25C, Vision Plus 30CCod. 20173523 - 04/20 - Ed. 0 · Cod. 20173523 - 04/20 - Ed. 0 · PDF p. 8
  • Vision Plus 35C, Vision Plus 40CCod. 20174438 - 07 /20 - Ed. 2 · Cod. 20174438 - 07 /20 - Ed. 2 · PDF p. 8
The boiler has lost communication with the low-temperature thermostat.
Vokèra (2)
  • Pinnacle 20S, Pinnacle 25S20208437 · 10/26 Ed.5 · PDF p. 7
  • Pinnacle 25C, Pinnacle 30C, Pinnacle 35C20208435 · 10/26 Ed.5 · PDF p. 8
E080
Fault meaningModels and manual pages
Return-side alarm. The manual lists a probe fault, excessive return temperature or a flow/return temperature difference.
Vokèra (8)
  • Unica MAX 20S, Unica MAX 30SCod. 20188401 - 11/21 - Ed. 2 · Cod. 20188401 - 11/21 - Ed. 2 · PDF p. 39
  • Unica MAX 30C20188258 · PDF p. 39
  • Unica MAX 35C, Unica MAX 40CCod. 20188258 - 10/21 - Ed. 2 · Cod. 20188258 - 10/21 - Ed. 2 · PDF p. 39
  • Vision Plus 20S, Vision Plus 25S, Vision Plus 30SCod. 20174791 - 07/20 - Ed. 2 · Cod. 20174791 - 07/20 - Ed. 2 · PDF p. 8
  • Vision Plus 25C, Vision Plus 30CCod. 20173523 - 04/20 - Ed. 0 · Cod. 20173523 - 04/20 - Ed. 0 · PDF p. 8
  • Vision Plus 35C, Vision Plus 40CCod. 20174438 - 07 /20 - Ed. 2 · Cod. 20174438 - 07 /20 - Ed. 2 · PDF p. 8
  • evolve 18S, evolve 24S, evolve 30S, evolve 35Svokera-evolve-s-20127584-6 · PDF p. 44
  • evolve 24C, evolve 28C, evolve 32C, evolve 36C, evolve 42Cvokera-evolve-c-20131172-6 · PDF p. 48
The heating return probe circuit reports a fault.
Vokèra (4)
  • Pinnacle 20S, Pinnacle 25S20208437 · 10/26 Ed.5 · PDF p. 7
  • Pinnacle 25C, Pinnacle 30C, Pinnacle 35C20208435 · 10/26 Ed.5 · PDF p. 8
  • Synergy 20S, Synergy 25S, Synergy 32Svokera-synergy-s-20208494-5 · PDF p. 5
  • Synergy 25C, Synergy 30C, Synergy 35Cvokera-synergy-c-20208493-8 · PDF p. 5
E084
Fault meaningModels and manual pages
Fault at the zone 1 delivery temperature probe.
Vokèra (3)
  • Vision Plus 20S, Vision Plus 25S, Vision Plus 30SCod. 20174791 - 07/20 - Ed. 2 · Cod. 20174791 - 07/20 - Ed. 2 · PDF p. 8
  • Vision Plus 25C, Vision Plus 30CCod. 20173523 - 04/20 - Ed. 0 · Cod. 20173523 - 04/20 - Ed. 0 · PDF p. 8
  • Vision Plus 35C, Vision Plus 40CCod. 20174438 - 07 /20 - Ed. 2 · Cod. 20174438 - 07 /20 - Ed. 2 · PDF p. 8
E086
Fault meaningModels and manual pages
Fault at the main-zone delivery temperature probe.
Vokèra (3)
  • Vision Plus 20S, Vision Plus 25S, Vision Plus 30SCod. 20174791 - 07/20 - Ed. 2 · Cod. 20174791 - 07/20 - Ed. 2 · PDF p. 8
  • Vision Plus 25C, Vision Plus 30CCod. 20173523 - 04/20 - Ed. 0 · Cod. 20173523 - 04/20 - Ed. 0 · PDF p. 8
  • Vision Plus 35C, Vision Plus 40CCod. 20174438 - 07 /20 - Ed. 2 · Cod. 20174438 - 07 /20 - Ed. 2 · PDF p. 8
E090
Fault meaningModels and manual pages
The flue probe can be faulty or can have detected excessive flue temperature.
Vokèra (8)
  • Unica MAX 20S, Unica MAX 30SCod. 20188401 - 11/21 - Ed. 2 · Cod. 20188401 - 11/21 - Ed. 2 · PDF p. 39
  • Unica MAX 30C20188258 · PDF p. 39
  • Unica MAX 35C, Unica MAX 40CCod. 20188258 - 10/21 - Ed. 2 · Cod. 20188258 - 10/21 - Ed. 2 · PDF p. 39
  • Vision Plus 20S, Vision Plus 25S, Vision Plus 30SCod. 20174791 - 07/20 - Ed. 2 · Cod. 20174791 - 07/20 - Ed. 2 · PDF p. 8
  • Vision Plus 25C, Vision Plus 30CCod. 20173523 - 04/20 - Ed. 0 · Cod. 20173523 - 04/20 - Ed. 0 · PDF p. 8
  • Vision Plus 35C, Vision Plus 40CCod. 20174438 - 07 /20 - Ed. 2 · Cod. 20174438 - 07 /20 - Ed. 2 · PDF p. 8
  • evolve 18S, evolve 24S, evolve 30S, evolve 35Svokera-evolve-s-20127584-6 · PDF p. 44
  • evolve 24C, evolve 28C, evolve 32C, evolve 36C, evolve 42Cvokera-evolve-c-20131172-6 · PDF p. 48
The flue temperature probe circuit reports a fault.
Vokèra (4)
  • Pinnacle 20S, Pinnacle 25S20208437 · 10/26 Ed.5 · PDF p. 7
  • Pinnacle 25C, Pinnacle 30C, Pinnacle 35C20208435 · 10/26 Ed.5 · PDF p. 8
  • Synergy 20S, Synergy 25S, Synergy 32Svokera-synergy-s-20208494-5 · PDF p. 5
  • Synergy 25C, Synergy 30C, Synergy 35Cvokera-synergy-c-20208493-8 · PDF p. 5
E110
Fault meaningModels and manual pages
The safety thermostat has tripped on the primary circuit.
Baxi (17)
  • 100 Combi 124/1287659607-02 · 04/17 · PDF p. 46
  • 600 Combi 624/630/636, including LPG (first generation)7717521-03 · PDF p. 64
  • 600 System 615/618/624 and 624 LPG (first generation)7686961-01 · PDF p. 56
  • 800 Combi 825/830/836 (first generation)7728205-01 · PDF p. 64
  • 800 System 818/824 (first generation)7729931-01 · PDF p. 56
  • Assure Combi 25/30/36, including LPG7750729-01 · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7750878-01 · PDF p. 56
  • Duo-tec Combi ErP 24/28/33/40 and 28 LPG7219665-02 · 10/15 · PDF p. 46
  • Duo-tec Compact Combi 25/30/367844480-01 · PDF p. 66
  • Main Eco Compact Combi 25/307908748-v01;7908748-001-01 · 30/10/2025 · PDF p. 58
  • Main Eco Compact System 15/187716600-02 · PDF p. 57
  • Megaflo Compact System 15/18/247846467-01 · PDF p. 58
  • Megaflo System ErP 15/18/24/28/327647625-04 · 05/2017 · PDF p. 43
  • Platinum Combi ErP 24/28/33/407647627-02 · 9/16 · PDF p. 48
  • Platinum Compact Combi 25/30/367846425-01 · PDF p. 66
  • Platinum+ 32 System7753842-01 · 2/20 · PDF p. 43
  • Platinum+ 40 Combi7734477-01 · 7/19 · PDF p. 48
Potterton (9)
  • Assure Combi 25/30/36 and 25/30 LPG7717311-01 (printed back cover; URL contains older number 7678846) · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7717352-01 (printed back cover) · PDF p. 56
  • Gold Combi ErP 24/28/33 and 28 LPG7654263-03 · 05/17 · PDF p. 48
  • Gold System ErP 18/24/287654288-01 · 02/16 · PDF p. 43
  • Promax Combi ErP 24/28/337654260-03 · 03/17 · PDF p. 47
  • Promax System ErP 12/15/18/24/327654291-04 · 03/17 · PDF p. 45
  • Promax Ultra Combi ErP 24/28/33/407654258-07 · 07/17 · PDF p. 47
  • Titanium Combi ErP 24/28/33/407654277-02 · 11/16 · PDF p. 49
  • Ultra System 12/15/18/24/287673139-01 · 03/17 · PDF p. 43
Safety thermostat trip. The manual associates this indication with a pump fault.
Baxi (3)
  • EcoBlue Advance Combi 24/28/33/407219715-03 · 04/17 · PDF p. 64
  • EcoBlue Plus Combi 24/28/337219706-03 · 09/16 · PDF p. 65
  • EcoBlue System ErP 12/15/18/24/28/327219708-03 · 03/17 · PDF p. 64
Potterton (1)
  • Promax 24 Store ErP (90/115/150 litre)7221756-01 · 04/15 · PDF p. 47
E111
Fault meaningModels and manual pages
The safety thermostat has tripped on excessive temperature.
Baxi (3)
  • EcoBlue Advance Combi 24/28/33/407219715-03 · 04/17 · PDF p. 64
  • EcoBlue Plus Combi 24/28/337219706-03 · 09/16 · PDF p. 65
  • EcoBlue System ErP 12/15/18/24/28/327219708-03 · 03/17 · PDF p. 64
E130
Fault meaningModels and manual pages
Flue temperature protection has operated.
Baxi (20)
  • 100 Combi 124/1287659607-02 · 04/17 · PDF p. 46
  • 600 Combi 624/630/636, including LPG (first generation)7717521-03 · PDF p. 64
  • 600 System 615/618/624 and 624 LPG (first generation)7686961-01 · PDF p. 56
  • 800 Combi 825/830/836 (first generation)7728205-01 · PDF p. 64
  • 800 System 818/824 (first generation)7729931-01 · PDF p. 56
  • Assure Combi 25/30/36, including LPG7750729-01 · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7750878-01 · PDF p. 56
  • Duo-tec Combi ErP 24/28/33/40 and 28 LPG7219665-02 · 10/15 · PDF p. 46
  • Duo-tec Compact Combi 25/30/367844480-01 · PDF p. 66
  • EcoBlue Advance Combi 24/28/33/407219715-03 · 04/17 · PDF p. 64
  • EcoBlue Plus Combi 24/28/337219706-03 · 09/16 · PDF p. 65
  • EcoBlue System ErP 12/15/18/24/28/327219708-03 · 03/17 · PDF p. 64
  • Main Eco Compact Combi 25/307908748-v01;7908748-001-01 · 30/10/2025 · PDF p. 58
  • Main Eco Compact System 15/187716600-02 · PDF p. 57
  • Megaflo Compact System 15/18/247846467-01 · PDF p. 58
  • Megaflo System ErP 15/18/24/28/327647625-04 · 05/2017 · PDF p. 43
  • Platinum Combi ErP 24/28/33/407647627-02 · 9/16 · PDF p. 48
  • Platinum Compact Combi 25/30/367846425-01 · PDF p. 66
  • Platinum+ 32 System7753842-01 · 2/20 · PDF p. 43
  • Platinum+ 40 Combi7734477-01 · 7/19 · PDF p. 48
Potterton (10)
  • Assure Combi 25/30/36 and 25/30 LPG7717311-01 (printed back cover; URL contains older number 7678846) · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7717352-01 (printed back cover) · PDF p. 56
  • Gold Combi ErP 24/28/33 and 28 LPG7654263-03 · 05/17 · PDF p. 48
  • Gold System ErP 18/24/287654288-01 · 02/16 · PDF p. 43
  • Promax 24 Store ErP (90/115/150 litre)7221756-01 · 04/15 · PDF p. 47
  • Promax Combi ErP 24/28/337654260-03 · 03/17 · PDF p. 47
  • Promax System ErP 12/15/18/24/327654291-04 · 03/17 · PDF p. 45
  • Promax Ultra Combi ErP 24/28/33/407654258-07 · 07/17 · PDF p. 47
  • Titanium Combi ErP 24/28/33/407654277-02 · 11/16 · PDF p. 49
  • Ultra System 12/15/18/24/287673139-01 · 03/17 · PDF p. 43
E154
Fault meaningModels and manual pages
The flow/return sensor temperature comparison has failed.
Baxi (12)
  • 100 Combi 124/1287659607-02 · 04/17 · PDF p. 46
  • 600 Combi 624/630/636, including LPG (first generation)7717521-03 · PDF p. 64
  • 600 System 615/618/624 and 624 LPG (first generation)7686961-01 · PDF p. 56
  • 800 Combi 825/830/836 (first generation)7728205-01 · PDF p. 64
  • 800 System 818/824 (first generation)7729931-01 · PDF p. 56
  • Assure Combi 25/30/36, including LPG7750729-01 · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7750878-01 · PDF p. 56
  • Duo-tec Compact Combi 25/30/367844480-01 · PDF p. 66
  • Main Eco Compact Combi 25/307908748-v01;7908748-001-01 · 30/10/2025 · PDF p. 58
  • Main Eco Compact System 15/187716600-02 · PDF p. 57
  • Megaflo Compact System 15/18/247846467-01 · PDF p. 58
  • Platinum Compact Combi 25/30/367846425-01 · PDF p. 66
Potterton (4)
  • Assure Combi 25/30/36 and 25/30 LPG7717311-01 (printed back cover; URL contains older number 7678846) · PDF p. 64
  • Assure System 12/15/18/24 and 18/24 LPG7717352-01 (printed back cover) · PDF p. 56
  • Promax Ultra Combi ErP 24/28/33/407654258-07 · 07/17 · PDF p. 47
  • Ultra System 12/15/18/24/287673139-01 · 03/17 · PDF p. 43
E321
Fault meaningModels and manual pages
The domestic hot-water thermistor circuit reports a fault.
Baxi (9)
  • 100 Combi 124/1287659607-02 · 04/17 · PDF p. 46
  • 600 Combi 624/630/636, including LPG (first generation)7717521-03 · PDF p. 64
  • 800 Combi 825/830/836 (first generation)7728205-01 · PDF p. 64
  • Assure Combi 25/30/36, including LPG7750729-01 · PDF p. 64
  • Duo-tec Compact Combi 25/30/367844480-01 · PDF p. 66
  • EcoBlue Advance Combi 24/28/33/407219715-03 · 04/17 · PDF p. 64
  • EcoBlue Plus Combi 24/28/337219706-03 · 09/16 · PDF p. 65
  • Main Eco Compact Combi 25/307908748-v01;7908748-001-01 · 30/10/2025 · PDF p. 58
  • Platinum Compact Combi 25/30/367846425-01 · PDF p. 66
Potterton (2)
  • Assure Combi 25/30/36 and 25/30 LPG7717311-01 (printed back cover; URL contains older number 7678846) · PDF p. 64
  • Promax Ultra Combi ErP 24/28/33/407654258-07 · 07/17 · PDF p. 47
E 01
Fault meaningModels and manual pages
The flow temperature probe circuit is open.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
E 02
Fault meaningModels and manual pages
The return temperature probe circuit is open.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
E 08
Fault meaningModels and manual pages
The hot-water cylinder sensor circuit is open.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
E 11
Fault meaningModels and manual pages
The flow temperature probe circuit is shorted.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
E 12
Fault meaningModels and manual pages
The return temperature probe circuit is shorted.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
E 18
Fault meaningModels and manual pages
The cylinder temperature probe circuit is shorted.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
E 35
Fault meaningModels and manual pages
Flue temperature exceeds 75°C or the flue probe is shorted.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
E 36
Fault meaningModels and manual pages
The flue thermostat contact is open.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
E.00.04
Fault meaningModels and manual pages
The return temperature sensor input is open.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 74
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 52
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 74
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 50
E.00.05
Fault meaningModels and manual pages
The return temperature sensor input is short-circuited.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 74
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 52
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 74
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 50
E.00.16
Fault meaningModels and manual pages
The configured hot-water cylinder sensor signal is missing.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 74
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 52
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 74
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 50
E.00.17
Fault meaningModels and manual pages
The hot-water cylinder sensor circuit is short-circuited, where fitted.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 74
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 52
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 74
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 50
E.00.20
Fault meaningModels and manual pages
The flue sensor is disconnected or reads below its measuring range.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 74
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 52
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 74
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 50
E.00.21
Fault meaningModels and manual pages
The flue sensor is short-circuited or reads above its measuring range.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 74
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 52
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 74
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 50
E.04.01
Fault meaningModels and manual pages
The heating flow thermistor input is short-circuited.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 75
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 53
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 75
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 51
E.04.02
Fault meaningModels and manual pages
The heating flow thermistor input is open.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 75
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 53
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 75
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 51
E.04.03
Fault meaningModels and manual pages
Flow temperature is above its limit or the flow sensor is short-circuited.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 75
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 53
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 75
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 51
E.04.18
Fault meaningModels and manual pages
The flow reading is below minimum or its sensor is disconnected.
Baxi (4)
  • 224/228 Combi 2 and 224 Combi 2 LPG7791868-02 · 03/12/2021 · PDF p. 75
  • 400 Combi 2.1 (424/430/436), 600 Combi 2 (624/630/636), 800 Combi 2 (824/830/836), Assure 500 Combi 2 (524/530/536)7875578-02 · 07/24 · PDF p. 53
  • 424/430 Combi 2, including LPG7791870-03 · 15/03/2022 · PDF p. 75
  • 600 System 2 (615/618/624), 800 System 2 (818/824/830), Assure 500 System 2 (515/518/524)7875579-01 · 06/24 · PDF p. 51
E:00.04
Fault meaningModels and manual pages
The return temperature sensor input is open.
Baxi (2)
  • Combi 224/228/424/428 (manual 7661586-2)7661586-2 · 12/07/2016 (12072016) · PDF p. 65
  • Combi 224/228/424/428 and 428 LPG (manual 7696317-1)7696317-1 · 21/03/2018 · PDF p. 66
E:00.05
Fault meaningModels and manual pages
The return temperature sensor input is short-circuited.
Baxi (2)
  • Combi 224/228/424/428 (manual 7661586-2)7661586-2 · 12/07/2016 (12072016) · PDF p. 66
  • Combi 224/228/424/428 and 428 LPG (manual 7696317-1)7696317-1 · 21/03/2018 · PDF p. 66
E:04.01
Fault meaningModels and manual pages
The heating flow thermistor input is short-circuited.
Baxi (2)
  • Combi 224/228/424/428 (manual 7661586-2)7661586-2 · 12/07/2016 (12072016) · PDF p. 67
  • Combi 224/228/424/428 and 428 LPG (manual 7696317-1)7696317-1 · 21/03/2018 · PDF p. 68
E:04.02
Fault meaningModels and manual pages
The heating flow thermistor input is open.
Baxi (2)
  • Combi 224/228/424/428 (manual 7661586-2)7661586-2 · 12/07/2016 (12072016) · PDF p. 67
  • Combi 224/228/424/428 and 428 LPG (manual 7696317-1)7696317-1 · 21/03/2018 · PDF p. 68
E:04.04
Fault meaningModels and manual pages
The flue temperature sensor input is short-circuited.
Baxi (2)
  • Combi 224/228/424/428 (manual 7661586-2)7661586-2 · 12/07/2016 (12072016) · PDF p. 67
  • Combi 224/228/424/428 and 428 LPG (manual 7696317-1)7696317-1 · 21/03/2018 · PDF p. 68
E:04.05
Fault meaningModels and manual pages
The flue temperature sensor input is open.
Baxi (2)
  • Combi 224/228/424/428 (manual 7661586-2)7661586-2 · 12/07/2016 (12072016) · PDF p. 67
  • Combi 224/228/424/428 and 428 LPG (manual 7696317-1)7696317-1 · 21/03/2018 · PDF p. 68
E:04.08
Fault meaningModels and manual pages
The water temperature reached the safety cut-out limit.
Baxi (2)
  • Combi 224/228/424/428 (manual 7661586-2)7661586-2 · 12/07/2016 (12072016) · PDF p. 68
  • Combi 224/228/424/428 and 428 LPG (manual 7696317-1)7696317-1 · 21/03/2018 · PDF p. 68
Er 02
Fault meaningModels and manual pages
The safety thermostat has operated and the boiler has locked out.
Biasi (5)
  • Advance 25Cbiasi-advance25-combi-2020 · PDF p. 9
  • Advance 25S, Advance 30Sbiasi-advance-system-2020 · PDF p. 9
  • Advance 30C, Advance 35Cbiasi-advance3035-combi-2020 · PDF p. 9
  • Advance Plus 25C ErP, Advance Plus 30C ErP, Advance Plus 35C ErPbiasi-advance-plus-combi-2019 · PDF p. 9
  • Advance Plus 25S ErP, Advance Plus 30S ErPbiasi-advance-plus-system-2019 · PDF p. 9
Er 06
Fault meaningModels and manual pages
Fault on the central-heating flow NTC circuit.
Biasi (5)
  • Advance 25Cbiasi-advance25-combi-2020 · PDF p. 10
  • Advance 25S, Advance 30Sbiasi-advance-system-2020 · PDF p. 10
  • Advance 30C, Advance 35Cbiasi-advance3035-combi-2020 · PDF p. 10
  • Advance Plus 25C ErP, Advance Plus 30C ErP, Advance Plus 35C ErPbiasi-advance-plus-combi-2019 · PDF p. 10
  • Advance Plus 25S ErP, Advance Plus 30S ErPbiasi-advance-plus-system-2019 · PDF p. 10
Er 07
Fault meaningModels and manual pages
Fault on the hot-water NTC circuit.
Biasi (3)
  • Advance 25Cbiasi-advance25-combi-2020 · PDF p. 10
  • Advance 30C, Advance 35Cbiasi-advance3035-combi-2020 · PDF p. 10
  • Advance Plus 25C ErP, Advance Plus 30C ErP, Advance Plus 35C ErPbiasi-advance-plus-combi-2019 · PDF p. 10
Er 08
Fault meaningModels and manual pages
Fault on the outdoor temperature probe circuit.
Biasi (5)
  • Advance 25Cbiasi-advance25-combi-2020 · PDF p. 10
  • Advance 25S, Advance 30Sbiasi-advance-system-2020 · PDF p. 10
  • Advance 30C, Advance 35Cbiasi-advance3035-combi-2020 · PDF p. 10
  • Advance Plus 25C ErP, Advance Plus 30C ErP, Advance Plus 35C ErPbiasi-advance-plus-combi-2019 · PDF p. 10
  • Advance Plus 25S ErP, Advance Plus 30S ErPbiasi-advance-plus-system-2019 · PDF p. 10
Er 09
Fault meaningModels and manual pages
Fault on the flue NTC circuit.
Biasi (5)
  • Advance 25Cbiasi-advance25-combi-2020 · PDF p. 10
  • Advance 25S, Advance 30Sbiasi-advance-system-2020 · PDF p. 10
  • Advance 30C, Advance 35Cbiasi-advance3035-combi-2020 · PDF p. 10
  • Advance Plus 25C ErP, Advance Plus 30C ErP, Advance Plus 35C ErPbiasi-advance-plus-combi-2019 · PDF p. 10
  • Advance Plus 25S ErP, Advance Plus 30S ErPbiasi-advance-plus-system-2019 · PDF p. 10
Er 10
Fault meaningModels and manual pages
The flue temperature protection has operated.
Biasi (5)
  • Advance 25Cbiasi-advance25-combi-2020 · PDF p. 10
  • Advance 25S, Advance 30Sbiasi-advance-system-2020 · PDF p. 10
  • Advance 30C, Advance 35Cbiasi-advance3035-combi-2020 · PDF p. 10
  • Advance Plus 25C ErP, Advance Plus 30C ErP, Advance Plus 35C ErPbiasi-advance-plus-combi-2019 · PDF p. 10
  • Advance Plus 25S ErP, Advance Plus 30S ErPbiasi-advance-plus-system-2019 · PDF p. 10
Er 12
Fault meaningModels and manual pages
Fault on the central-heating return NTC circuit.
Biasi (5)
  • Advance 25Cbiasi-advance25-combi-2020 · PDF p. 10
  • Advance 25S, Advance 30Sbiasi-advance-system-2020 · PDF p. 10
  • Advance 30C, Advance 35Cbiasi-advance3035-combi-2020 · PDF p. 10
  • Advance Plus 25C ErP, Advance Plus 30C ErP, Advance Plus 35C ErPbiasi-advance-plus-combi-2019 · PDF p. 10
  • Advance Plus 25S ErP, Advance Plus 30S ErPbiasi-advance-plus-system-2019 · PDF p. 10
Er 19
Fault meaningModels and manual pages
Fault on the hot-water inlet temperature probe, where fitted.
Biasi (3)
  • Advance 25Cbiasi-advance25-combi-2020 · PDF p. 10
  • Advance 30C, Advance 35Cbiasi-advance3035-combi-2020 · PDF p. 10
  • Advance Plus 25C ErP, Advance Plus 30C ErP, Advance Plus 35C ErPbiasi-advance-plus-combi-2019 · PDF p. 10
F000
Fault meaningModels and manual pages
Heat exchanger temperature sensor S0 reports a fault.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 71
  • Xtreme 24, 30, 3684007408 · PDF p. 71
F0 278
Fault meaningModels and manual pages
A safety sensor failed the power-up check.
Worcester Bosch (3)
  • Greenstar 25Si and 30Si Compact ErP6720813278 · 2015/07 · PDF p. 71
  • Greenstar 27i and 30i System Compact ErP6720813280 · 2015/07 · PDF p. 71
  • Greenstar CDi Compact ErP combi 28, 32, 36 CDi6720813276 · 2015/07 · PDF p. 73
F0b
Fault meaningModels and manual pages
The heating circuit dual flow temperature sensor is short-circuited.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 56
F0C
Fault meaningModels and manual pages
Domestic hot-water thermistor circuit fault.
Ideal (3)
  • Independent Combi2 C24, C30, C35236469 A02 · 04/2023 · PDF p. 52
  • Logic Combi2 C24, C30, C35237664 A08 · 08/2026 · PDF p. 55
  • i-mini2 Combi C24, C30, C35UIN 236471 A02 · 04/2023 · PDF p. 52
F0t
Fault meaningModels and manual pages
Fault in the room thermostat or its connection, where fitted.
Ideal (6)
  • Independent Combi2 C24, C30, C35236469 A02 · 04/2023 · PDF p. 52
  • Independent System2 S15, S18, S24, S30236470 A02 · 04/2023 · PDF p. 48
  • Logic Combi2 C24, C30, C35237664 A08 · 08/2026 · PDF p. 55
  • Logic Heat2 H12, H15, H18, H24, H30UIN 228298 A07 · 10/2024 · PDF p. 51
  • Logic System2 S15, S18, S24, S30UIN 237665 A06 · 07/2025 · PDF p. 50
  • i-mini2 Combi C24, C30, C35UIN 236471 A02 · 04/2023 · PDF p. 52
F2
Fault meaningModels and manual pages
The boiler temperature limiter has tripped.
Viessmann (4)
  • Vitodens 050-W BPJD5675991 GB · 2/2015 · PDF p. 49
  • Vitodens 100-W B1HC/B1KC5697787 GB · 4/2019 · PDF p. 50
  • Vitodens 100-W Compact open vent, WB1B (7.9–35 kW manual)5368662 GB · 1/2012 · PDF p. 34
  • Vitodens 111-W B1LD5697789 GB · 3/2019 · PDF p. 42
F02
Fault meaningModels and manual pages
Short circuit at the combined heating flow temperature sensor and high-limit cut-out.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 53
F4
Fault meaningModels and manual pages
Heating flow thermistor circuit fault.
Ideal (18)
  • Atlantic Combi 24, 30, 35UIN 223483 A03 · July 2020 · PDF p. 55
  • Classic Combi 24, 30, 35UIN 212135 A06 · July 2018 · PDF p. 55
  • Classic2 Combi 24, 30, 35UIN 220219 A07 · June 2022 · PDF p. 55
  • Esprit Eco Combi 24, 30UIN 207493 A04 · January 2014 · PDF p. 53
  • Esprit Eco2 Combi 24, 30, 35UIN 220218 A07 · June 2022 · PDF p. 55
  • Exclusive Combi 24, 30, 35UIN 217746 A03 · July 2018 · PDF p. 56
  • Exclusive2 Combi 24, 30, 35UIN 220221 A07 · June 2022 · PDF p. 55
  • Independent Combi C24, C30, C35UIN205367 A08 · May2014 · PDF p. 54
  • Independent+ Combi 24, 30, 35 (UIN 222354)ideal-combi-legacy-independentplus-phc · PDF p. 56
  • Independent+ Combi C24, C30, C35 (UIN 207607)UIN 207607 A04 · February 2014 · PDF p. 54
  • Instinct Combi 24, 30, 35UIN 212456 A03 · April 2017 · PDF p. 55
  • Instinct2 Combi 24, 30, 35UIN 220222 A07 · June 2022 · PDF p. 55
  • Logic Code Combi ESP1 26, 33, 38UIN 222364 A06 · 08/2026 · PDF p. 56
  • Logic Combi 24, 30, 35 (UIN 204626)ideal-combi-legacy-logic-candidate · PDF p. 53
  • Logic Combi C24, C30, C35 (UIN 222351)UIN 222351 A01 · April 2019 · PDF p. 55
  • Logic Combi ESP1 24, 30, 35UIN 222353 A07 · 08/2026 · PDF p. 55
  • i-mini Combi C24, C30UIN 222352 · April 2019 · PDF p. 55
  • i2 Combi 24, 30, 35UIN 220220 A05 · July 2020 · PDF p. 55
The control/no-flow thermistor circuit has reported a fault.
Ideal (8)
  • Independent System S15, S18, S24, S30UIN 215351 A08 · February 2019 · PDF p. 54
  • Logic Heat H12, H15, H18, H24, H30215354 A06 · 10/2017 · PDF p. 54
  • Logic MAX Heat H12, H15, H18, H24, H30219010 A04 · 2/2019 · PDF p. 55
  • Logic MAX System S15, S18, S24, S30UIN 219009 A04 · February 2019 · PDF p. 54
  • Logic System 15, 18, 24, 30 (UIN 205552)ideal-system-legacy-logic-mirror · PDF p. 51
  • Logic System S15, S18, S24, S30 (S series)UIN 215349 A05 · February 2018 · PDF p. 54
  • Logic+ Heat H12, H15, H18, H24, H30215355 A10 · 2/2019 · PDF p. 54
  • Logic+ System S15, S18, S24, S30UIN 215353 A01 · July 2016 · PDF p. 54
F04
Fault meaningModels and manual pages
Heating flow thermistor circuit fault.
Ideal (6)
  • Independent Combi2 C24, C30, C35236469 A02 · 04/2023 · PDF p. 52
  • Independent System2 S15, S18, S24, S30236470 A02 · 04/2023 · PDF p. 48
  • Logic Combi2 C24, C30, C35237664 A08 · 08/2026 · PDF p. 55
  • Logic Heat2 H12, H15, H18, H24, H30UIN 228298 A07 · 10/2024 · PDF p. 51
  • Logic System2 S15, S18, S24, S30UIN 237665 A06 · 07/2025 · PDF p. 50
  • i-mini2 Combi C24, C30, C35UIN 236471 A02 · 04/2023 · PDF p. 52
F5
Fault meaningModels and manual pages
Heating return thermistor circuit fault.
Ideal (26)
  • Atlantic Combi 24, 30, 35UIN 223483 A03 · July 2020 · PDF p. 55
  • Classic Combi 24, 30, 35UIN 212135 A06 · July 2018 · PDF p. 55
  • Classic2 Combi 24, 30, 35UIN 220219 A07 · June 2022 · PDF p. 55
  • Esprit Eco Combi 24, 30UIN 207493 A04 · January 2014 · PDF p. 53
  • Esprit Eco2 Combi 24, 30, 35UIN 220218 A07 · June 2022 · PDF p. 55
  • Exclusive Combi 24, 30, 35UIN 217746 A03 · July 2018 · PDF p. 56
  • Exclusive2 Combi 24, 30, 35UIN 220221 A07 · June 2022 · PDF p. 55
  • Independent Combi C24, C30, C35UIN205367 A08 · May2014 · PDF p. 53
  • Independent System S15, S18, S24, S30UIN 215351 A08 · February 2019 · PDF p. 54
  • Independent+ Combi 24, 30, 35 (UIN 222354)ideal-combi-legacy-independentplus-phc · PDF p. 56
  • Independent+ Combi C24, C30, C35 (UIN 207607)UIN 207607 A04 · February 2014 · PDF p. 53
  • Instinct Combi 24, 30, 35UIN 212456 A03 · April 2017 · PDF p. 55
  • Instinct2 Combi 24, 30, 35UIN 220222 A07 · June 2022 · PDF p. 55
  • Logic Code Combi ESP1 26, 33, 38UIN 222364 A06 · 08/2026 · PDF p. 56
  • Logic Combi 24, 30, 35 (UIN 204626)ideal-combi-legacy-logic-candidate · PDF p. 53
  • Logic Combi C24, C30, C35 (UIN 222351)UIN 222351 A01 · April 2019 · PDF p. 55
  • Logic Combi ESP1 24, 30, 35UIN 222353 A07 · 08/2026 · PDF p. 55
  • Logic Heat H12, H15, H18, H24, H30215354 A06 · 10/2017 · PDF p. 54
  • Logic MAX Heat H12, H15, H18, H24, H30219010 A04 · 2/2019 · PDF p. 55
  • Logic MAX System S15, S18, S24, S30UIN 219009 A04 · February 2019 · PDF p. 54
  • Logic System 15, 18, 24, 30 (UIN 205552)ideal-system-legacy-logic-mirror · PDF p. 51
  • Logic System S15, S18, S24, S30 (S series)UIN 215349 A05 · February 2018 · PDF p. 54
  • Logic+ Heat H12, H15, H18, H24, H30215355 A10 · 2/2019 · PDF p. 54
  • Logic+ System S15, S18, S24, S30UIN 215353 A01 · July 2016 · PDF p. 54
  • i-mini Combi C24, C30UIN 222352 · April 2019 · PDF p. 55
  • i2 Combi 24, 30, 35UIN 220220 A05 · July 2020 · PDF p. 55
F05
Fault meaningModels and manual pages
Heating return thermistor circuit fault.
Ideal (6)
  • Independent Combi2 C24, C30, C35236469 A02 · 04/2023 · PDF p. 52
  • Independent System2 S15, S18, S24, S30236470 A02 · 04/2023 · PDF p. 48
  • Logic Combi2 C24, C30, C35237664 A08 · 08/2026 · PDF p. 55
  • Logic Heat2 H12, H15, H18, H24, H30UIN 228298 A07 · 10/2024 · PDF p. 51
  • Logic System2 S15, S18, S24, S30UIN 237665 A06 · 07/2025 · PDF p. 50
  • i-mini2 Combi C24, C30, C35UIN 236471 A02 · 04/2023 · PDF p. 52
F6
Fault meaningModels and manual pages
Signal fault at the outside temperature sensor, where fitted.
Ideal (23)
  • Atlantic Combi 24, 30, 35UIN 223483 A03 · July 2020 · PDF p. 55
  • Classic2 Combi 24, 30, 35UIN 220219 A07 · June 2022 · PDF p. 55
  • Esprit Eco Combi 24, 30UIN 207493 A04 · January 2014 · PDF p. 72
  • Esprit Eco2 Combi 24, 30, 35UIN 220218 A07 · June 2022 · PDF p. 55
  • Exclusive2 Combi 24, 30, 35UIN 220221 A07 · June 2022 · PDF p. 55
  • Independent Combi C24, C30, C35UIN205367 A08 · May2014 · PDF p. 53
  • Independent System S15, S18, S24, S30UIN 215351 A08 · February 2019 · PDF p. 54
  • Independent+ Combi 24, 30, 35 (UIN 222354)ideal-combi-legacy-independentplus-phc · PDF p. 56
  • Independent+ Combi C24, C30, C35 (UIN 207607)UIN 207607 A04 · February 2014 · PDF p. 53
  • Instinct2 Combi 24, 30, 35UIN 220222 A07 · June 2022 · PDF p. 55
  • Logic Code Combi ESP1 26, 33, 38UIN 222364 A06 · 08/2026 · PDF p. 56
  • Logic Combi 24, 30, 35 (UIN 204626)ideal-combi-legacy-logic-candidate · PDF p. 54
  • Logic Combi C24, C30, C35 (UIN 222351)UIN 222351 A01 · April 2019 · PDF p. 55
  • Logic Combi ESP1 24, 30, 35UIN 222353 A07 · 08/2026 · PDF p. 55
  • Logic Heat H12, H15, H18, H24, H30215354 A06 · 10/2017 · PDF p. 54
  • Logic MAX Heat H12, H15, H18, H24, H30219010 A04 · 2/2019 · PDF p. 55
  • Logic MAX System S15, S18, S24, S30UIN 219009 A04 · February 2019 · PDF p. 54
  • Logic System 15, 18, 24, 30 (UIN 205552)ideal-system-legacy-logic-mirror · PDF p. 51
  • Logic System S15, S18, S24, S30 (S series)UIN 215349 A05 · February 2018 · PDF p. 54
  • Logic+ Heat H12, H15, H18, H24, H30215355 A10 · 2/2019 · PDF p. 54
  • Logic+ System S15, S18, S24, S30UIN 215353 A01 · July 2016 · PDF p. 54
  • i-mini Combi C24, C30UIN 222352 · April 2019 · PDF p. 55
  • i2 Combi 24, 30, 35UIN 220220 A05 · July 2020 · PDF p. 55
F06
Fault meaningModels and manual pages
Signal fault at the outside temperature sensor, where fitted.
Ideal (6)
  • Independent Combi2 C24, C30, C35236469 A02 · 04/2023 · PDF p. 52
  • Independent System2 S15, S18, S24, S30236470 A02 · 04/2023 · PDF p. 48
  • Logic Combi2 C24, C30, C35237664 A08 · 08/2026 · PDF p. 55
  • Logic Heat2 H12, H15, H18, H24, H30UIN 228298 A07 · 10/2024 · PDF p. 51
  • Logic System2 S15, S18, S24, S30UIN 237665 A06 · 07/2025 · PDF p. 50
  • i-mini2 Combi C24, C30, C35UIN 236471 A02 · 04/2023 · PDF p. 52
F010
Fault meaningModels and manual pages
The heat exchanger temperature sensor S0 circuit reports a fault.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 72
  • Xtreme 24, 30, 3684007408 · PDF p. 72
F10
Fault meaningModels and manual pages
The outdoor temperature sensor is short-circuited.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 54
F011
Fault meaningModels and manual pages
The heat exchanger temperature sensor S0 circuit reports a fault.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 72
  • Xtreme 24, 30, 3684007408 · PDF p. 72
F012
Fault meaningModels and manual pages
The flue gas sensor S5 circuit reports a fault.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 72
  • Xtreme 24, 30, 3684007408 · PDF p. 72
F014
Fault meaningModels and manual pages
The heat exchanger temperature sensor S0 is incorrectly seated.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 72
  • Xtreme 24, 30, 3684007408 · PDF p. 72
F015
Fault meaningModels and manual pages
Heating flow sensor S1 is incorrectly seated.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 72
  • Xtreme 24, 30, 3684007408 · PDF p. 72
F016
Fault meaningModels and manual pages
Domestic hot water sensor S3 is incorrectly seated.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 72
  • Xtreme 24, 30, 3684007408 · PDF p. 72
F18
Fault meaningModels and manual pages
The outdoor temperature sensor input is open.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 54
F027
Fault meaningModels and manual pages
The optional outdoor weather-compensation sensor S6 circuit reads short.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 72
  • Xtreme 24, 30, 3684007408 · PDF p. 72
F30
Fault meaningModels and manual pages
In this BPKB manual, the fault table identifies a short circuit at the outdoor sensor.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 55
F031
Fault meaningModels and manual pages
Central heating flow temperature sensor S1 reports a fault.
Intergas (2)
  • Xclusive 24, 30, 3684010403 · PDF p. 72
  • Xtreme 24, 30, 3684007408 · PDF p. 72
F31
Fault meaningModels and manual pages
The room temperature sensor is short-circuited.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 55
F38
Fault meaningModels and manual pages
In this BPKB manual, the fault table identifies an open circuit at the outdoor sensor.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 55
F39
Fault meaningModels and manual pages
The room temperature sensor input is open.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 55
F51
Fault meaningModels and manual pages
The domestic hot-water temperature sensor is short-circuited.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 56
F58
Fault meaningModels and manual pages
The domestic hot-water temperature sensor input is open.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 56
F.00
Fault meaningModels and manual pages
The boiler has lost the signal from the heating flow temperature sensor. The sensor, its plug and wiring are on this circuit.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 36
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 46
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 45
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 38
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 42
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 35
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 40
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 50
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 51
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 47
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 38
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 43
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 45
Vaillant (15)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 42
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 46
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 40
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 43
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 54
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 44
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 46
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 44
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 51
F.000
Fault meaningModels and manual pages
The boiler has lost the signal from the heating flow temperature sensor. The sensor, its plug and wiring are on this circuit.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 73
F.01
Fault meaningModels and manual pages
The boiler has lost the signal from the heating return temperature sensor. The sensor, plug, wiring or PCB connection can interrupt it.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 36
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 46
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 45
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 38
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 42
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 35
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 40
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 50
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 51
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 47
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 38
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 43
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 45
Vaillant (15)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 42
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 46
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 40
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 43
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 54
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 44
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 46
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 44
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 51
F.001
Fault meaningModels and manual pages
The boiler has lost the signal from the heating return temperature sensor. The sensor, plug, wiring or PCB connection can interrupt it.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 73
F.02
Fault meaningModels and manual pages
The domestic hot-water outlet temperature signal is interrupted. Applies to the hot-water sensor configuration specified in this manual. The manual specifies this indication together with F.91.
Vaillant (4)
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 54
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
F.002
Fault meaningModels and manual pages
The temperature signal from the domestic hot-water connection has been interrupted, where this sensor is fitted.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 73
F.03
Fault meaningModels and manual pages
The boiler has lost the cylinder temperature signal on installations equipped with this sensor. The manual specifies this indication together with F.91.
Vaillant (4)
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 54
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
F.003
Fault meaningModels and manual pages
The boiler has lost the cylinder temperature signal on installations equipped with this sensor.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 73
F.7
Fault meaningModels and manual pages
Open circuit at the hot-water cylinder temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 80
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 90
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 78
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 88
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 81
F.8
Fault meaningModels and manual pages
Short circuit at the hot-water cylinder temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 80
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 90
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 78
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 88
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 81
F.9
Fault meaningModels and manual pages
Open circuit at the domestic hot-water outlet temperature sensor.
Viessmann (1)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 80
F.10
Fault meaningModels and manual pages
The heating flow temperature sensor circuit is shorted.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 36
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 46
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 45
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 38
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 42
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 35
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 40
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 50
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 51
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 47
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 38
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 43
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 45
Vaillant (15)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 42
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 46
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 40
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 43
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 54
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 44
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 46
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 44
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 51
Short circuit at the domestic hot-water outlet temperature sensor.
Viessmann (1)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 80
F.010
Fault meaningModels and manual pages
The heating flow temperature sensor circuit is shorted.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 73
F.11
Fault meaningModels and manual pages
The heating return temperature sensor circuit is shorted.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 36
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 46
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 45
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 38
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 42
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 35
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 40
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 50
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 51
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 47
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 38
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 43
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 45
Vaillant (15)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 42
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 46
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 40
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 43
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 54
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 44
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 46
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 44
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 51
Open circuit at the solar collector temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 80
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 90
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 78
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 88
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 81
F.011
Fault meaningModels and manual pages
The heating return temperature sensor circuit is shorted.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 74
F.12
Fault meaningModels and manual pages
Short circuit at the solar collector temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 80
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 90
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 78
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 88
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 81
The hot-water outlet temperature sensor circuit is shorted on installations equipped with this sensor. The manual specifies this indication together with F.91.
Vaillant (4)
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 54
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
F.012
Fault meaningModels and manual pages
The temperature sensor circuit at the domestic hot-water connection has shorted, where fitted.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 74
F.12 and F.91
Fault meaningModels and manual pages
Both codes appear together for a shorted cylinder temperature sensor circuit, where this sensor is fitted.
Glow-worm (6)
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 38
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 35
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 40
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 51
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 52
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 38
Vaillant (5)
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 46
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 43
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
F.13
Fault meaningModels and manual pages
The cylinder temperature sensor circuit has shorted, where this sensor is fitted.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 36
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 46
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 45
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 38
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 42
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 35
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 40
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 51
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 52
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 47
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 38
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 43
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 45
Vaillant (5)
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 46
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 43
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
Open circuit at the outdoor temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 80
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 90
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 78
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 88
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 81
The cylinder or warm-start sensor circuit is shorted, depending on equipment. For the actoSTOR cylinder, the manual specifies F.13 with F.91.
Vaillant (4)
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 54
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
A short is reported on the hot-water temperature sensor circuit (cylinder or warm-start sensor, depending on equipment).
Vaillant (3)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 42
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 40
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 44
F.013
Fault meaningModels and manual pages
The cylinder temperature sensor circuit is shorted, where a cylinder sensor is fitted.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 74
F.14
Fault meaningModels and manual pages
Short circuit at the outdoor temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 78
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 81
F.15
Fault meaningModels and manual pages
Open circuit at the solar hot-water cylinder temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 79
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 82
F.16
Fault meaningModels and manual pages
Short circuit at the solar hot-water cylinder temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 79
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 82
F.19
Fault meaningModels and manual pages
The lower cylinder temperature sensor circuit is open, where fitted.
Viessmann (2)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
F.20
Fault meaningModels and manual pages
The temperature limiter has stopped the burner. The listed causes include problems with temperature sensing.
Glow-worm (2)
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 46
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 48
Vaillant (6)
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 52
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 55
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 60
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 56
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 46
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 44
F.020
Fault meaningModels and manual pages
Overheat protection has closed the gas valve because the flow or return temperature reading exceeded the limit.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 80
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 74
F.29
Fault meaningModels and manual pages
Open circuit at the low-loss header temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 79
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 82
F.30
Fault meaningModels and manual pages
Short circuit at the low-loss header temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 79
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 82
F.46
Fault meaningModels and manual pages
A short is reported on the cold-water inlet temperature sensor circuit.
Glow-worm (2)
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 48
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 49
A short is reported on the cold-water inlet temperature sensor circuit. This applies to the optional solar inlet sensor.
Vaillant (1)
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 51
F.047
Fault meaningModels and manual pages
The hot-water outlet temperature signal from the internal cylinder is implausible, where this cylinder is fitted.
Vaillant (1)
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 78
F.49
Fault meaningModels and manual pages
Open circuit at the flue gas temperature sensor.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 79
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 82
F.50
Fault meaningModels and manual pages
Short circuit at the flue gas temperature sensor.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 79
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 82
F.57
Fault meaningModels and manual pages
Open circuit at the external room temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 91
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 79
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 89
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 82
F.58
Fault meaningModels and manual pages
Short circuit at the external room temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 92
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 79
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 90
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 82
F.62
Fault meaningModels and manual pages
The high-limit safety cut-out has tripped.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 92
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 80
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 90
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 83
F.63
Fault meaningModels and manual pages
The flue gas temperature limiter has tripped.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 81
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 92
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 80
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 90
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 83
F.64
Fault meaningModels and manual pages
The control electronics report a sensor or electronics fault. The temperature-sensing circuit and PCB are possible causes.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 37
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 48
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 46
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 39
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 43
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 36
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 41
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 51
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 52
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 50
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 39
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 44
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 46
Vaillant (15)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 42
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 46
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 40
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 44
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 43
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 53
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 56
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 44
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 61
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 57
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 47
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 45
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 51
F.71
Fault meaningModels and manual pages
The flow temperature signal stays at a constant value. Poor pipe contact or a defective sensor can cause this.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 37
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 49
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 46
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 39
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 43
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 36
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 41
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 51
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 52
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 50
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 39
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 44
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 46
Vaillant (11)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 42
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 47
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 40
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 44
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 53
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 56
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 44
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 51
The heating flow temperature signal is implausible. Poor contact with the pipe can affect this reading.
Vaillant (4)
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 62
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 58
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 47
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 45
F.071
Fault meaningModels and manual pages
The heating flow temperature signal is implausible. Poor contact with the pipe can affect this reading.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 86
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 79
F.72
Fault meaningModels and manual pages
The fault table lists an excessive difference between the flow and return NTC readings among the possible causes.
Glow-worm (11)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 37
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 46
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 39
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 43
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 36
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 41
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 51
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 52
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 39
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 44
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 46
Vaillant (6)
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 47
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 44
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 52
The flow and return sensor readings disagree. The manual identifies both temperature sensors in this check.
Vaillant (9)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 42
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 40
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 54
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 56
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 44
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 62
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 58
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 47
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 45
The return temperature reading is faulty. The manual lists both the flow and return temperature sensors as possible causes.
Glow-worm (2)
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 49
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 50
F.072
Fault meaningModels and manual pages
The difference between flow and return temperature readings is implausible.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 86
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 79
F.78
Fault meaningModels and manual pages
The domestic hot-water outlet temperature input is interrupted with external controls connected.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 37
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 49
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 46
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 39
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 43
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 36
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 41
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 52
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 53
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 51
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 39
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 44
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 46
Vaillant (11)
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 47
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 44
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 54
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 56
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 43
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 62
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 58
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 47
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 45
F.80
Fault meaningModels and manual pages
The actoSTOR cylinder inlet temperature signal is missing or faulty. Applies to installations equipped with this cylinder. The manual specifies this indication together with F.91.
Vaillant (4)
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 54
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 56
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 62
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 58
F.080
Fault meaningModels and manual pages
The internal cylinder cold-water inlet sensor is faulty or disconnected. Its plug and wiring are part of the signal path.
Vaillant (1)
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 80
F.83
Fault meaningModels and manual pages
The flow or return sensor registers too little temperature change when the burner starts. Water quantity and sensor contact affect this check.
Vaillant (5)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 43
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 41
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 54
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 57
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 45
The difference between the flow and return sensor temperatures is too small. Sensor contact and water volume affect this check.
Vaillant (4)
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 62
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 58
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 48
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 46
The boiler reports a fault in the way the NTC temperatures change. Water pressure and sensor contact with the pipes are among the listed causes.
Glow-worm (2)
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 49
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 51
F.84
Fault meaningModels and manual pages
The temperature difference between flow and return is implausible.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 37
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 49
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 46
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 39
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 43
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 36
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 41
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 52
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 53
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 51
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 39
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 44
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 46
Vaillant (13)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 43
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 47
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 44
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 54
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 57
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 44
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 62
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 58
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 48
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 46
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 52
F.084
Fault meaningModels and manual pages
The temperature difference between flow and return is implausible.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 87
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 80
F.85
Fault meaningModels and manual pages
The positions or pipe contact of the flow and return temperature sensors are inconsistent with the expected readings.
Glow-worm (13)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 37
  • Compact 24c-AS/1 (NG and LPG), Compact 28c-AS/1 (NG and LPG)0020313973_08 · 05.12.2024 · PDF p. 50
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 46
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 39
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 43
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 36
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 41
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 52
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 53
  • MicraCom 24c-AS/1, MicraCom 28c-AS/10020289288_05 · 05.12.2024 · PDF p. 51
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 39
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 44
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 46
Vaillant (15)
  • ecoFIT pure 412, ecoFIT pure 415, ecoFIT pure 418, ecoFIT pure 425, ecoFIT pure 430, ecoFIT pure 4350020230535_09 · 30.03.2021 · PDF p. 43
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 47
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 415, ecoFIT sustain 418, ecoFIT sustain 4300020277262_04 · 30.03.2021 · PDF p. 41
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 44
  • ecoTEC exclusive 6270020193966_04 · 29.07.2020 · PDF p. 54
  • ecoTEC exclusive 835, ecoTEC exclusive 8430020193968_05 · 22.02.2021 · PDF p. 57
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 44
  • ecoTEC plus 424 LPG0020239015_09 · 30.03.2021 · PDF p. 45
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 62
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 58
  • ecoTEC pro 24 kW, ecoTEC pro 28 kW, ecoTEC pro 28 kW LPG0020244995_05 · 17.02.2021 · PDF p. 48
  • ecoTEC pro 30 kW0020209589_05 · 17.02.2021 · PDF p. 46
  • ecoTEC sustain 24 kW, ecoTEC sustain 28 kW, ecoTEC sustain 34 kW0020253094_06 · 15.02.2021 · PDF p. 52
F.085
Fault meaningModels and manual pages
The positions or pipe contact of the flow and return temperature sensors are inconsistent with the expected readings.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 87
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 81
F.86
Fault meaningModels and manual pages
The underfloor heating safety contact is open, or its sensor circuit is disconnected or faulty, where fitted.
Glow-worm (11)
  • Betacom4 24c, Betacom4 30c0020238424_02 · 15.11.2017 · PDF p. 37
  • Easicom3 24c, Easicom3 28c0020239562_05 · 06.10.2020 · PDF p. 46
  • Easicom3 25r0020238431_04 · 30.03.2021 · PDF p. 39
  • Easicom3 25s0020238426_05 · 20.10.2020 · PDF p. 43
  • Energy2 30c LPG0020283671_01 · 21.09.2018 · PDF p. 36
  • Energy7 12r, Energy7 15r, Energy7 18r, Energy7 25r, Energy7 30r0020300877_02 · 17.12.2020 · PDF p. 41
  • Energy7 12s, Energy7 15s, Energy7 18s, Energy7 25s, Energy7 30s0020300876_01 · 09.11.2020 · PDF p. 52
  • Energy7 25c, Energy7 30c, Energy7 35c0020300875_01 · 09.11.2020 · PDF p. 53
  • Ultimate3 25r0020239568_06 · 18.02.2025 · PDF p. 39
  • Ultimate3 25s0020239564_06 · 18.02.2025 · PDF p. 44
  • Ultimate3 30c, Ultimate3 35c0020239566_06 · 18.02.2025 · PDF p. 46
Vaillant (5)
  • ecoFIT pure 612, ecoFIT pure 615, ecoFIT pure 618, ecoFIT pure 625, ecoFIT pure 6300020230533_07 · 20.10.2020 · PDF p. 47
  • ecoFIT pure 825, ecoFIT pure 830, ecoFIT pure 8350020230531_07 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 615, ecoFIT sustain 618, ecoFIT sustain 6300020277252_03 · 20.10.2020 · PDF p. 45
  • ecoFIT sustain 825, ecoFIT sustain 830, ecoFIT sustain 8350020230529_06 · 20.10.2020 · PDF p. 44
  • ecoTEC plus 412, ecoTEC plus 415, ecoTEC plus 418, ecoTEC plus 424, ecoTEC plus 430, ecoTEC plus 4350020238195_08 · 30.03.2021 · PDF p. 44
F.91
Fault meaningModels and manual pages
A sensor fault is reported by the connected actoSTOR cylinder. Applies where this accessory is fitted.
Vaillant (2)
  • ecoTEC plus 612, ecoTEC plus 615, ecoTEC plus 618, ecoTEC plus 624, ecoTEC plus 630, ecoTEC plus 637, ecoTEC plus 618 LPG, ecoTEC plus 630 LPG, ecoTEC plus 825, ecoTEC plus 832, ecoTEC plus 835, ecoTEC plus 838, ecoTEC plus 832 LPG (VU/VUW ..6/5-5)0020244997_07 · 15.07.2021 · PDF p. 62
  • ecoTEC plus 938 storage combi0020244998_06 · 20.07.2021 · PDF p. 58
F.182
Fault meaningModels and manual pages
Short circuit at the outlet temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 84
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 96
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 83
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 94
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 86
F.183
Fault meaningModels and manual pages
Open circuit at the outlet temperature sensor, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 84
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 96
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 83
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 94
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 86
F.184
Fault meaningModels and manual pages
Short circuit at the combined heating flow sensor and high-limit cut-out circuit.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 84
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 96
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 83
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 94
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 86
F.185
Fault meaningModels and manual pages
Open circuit at the combined heating flow sensor and high-limit cut-out circuit.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 84
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 96
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 83
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 94
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 86
F.345
Fault meaningModels and manual pages
The temperature limiter has tripped.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 84
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 97
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 83
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 95
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 86
F.373
Fault meaningModels and manual pages
Heat transfer during calibration was insufficient and the temperature limiter shut the burner down.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 87
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 101
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 86
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 99
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 90
F.394
Fault meaningModels and manual pages
Open circuit at the second flue temperature sensor, where fitted.
Viessmann (2)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 102
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 100
F.416
Fault meaningModels and manual pages
The flue gas temperature sensor is incorrectly positioned.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 91
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 103
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 88
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 101
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 92
F.446
Fault meaningModels and manual pages
The flow sensor and high-limit channel give inconsistent readings.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 92
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 103
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 89
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 101
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 92
F.530
Fault meaningModels and manual pages
The solar controller is missing one or more sensor readings, where fitted.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 95
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 107
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 92
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 105
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 95
F.538
Fault meaningModels and manual pages
Open circuit at the system return temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 95
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 107
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 105
F.539
Fault meaningModels and manual pages
Short circuit at the system return temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 95
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 107
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 105
F.542
Fault meaningModels and manual pages
Open circuit at the mixed heating circuit 1 flow temperature sensor.
Viessmann (1)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
F.543
Fault meaningModels and manual pages
Short circuit at the mixed heating circuit 1 flow temperature sensor.
Viessmann (1)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
F.544
Fault meaningModels and manual pages
Open circuit at the mixed heating circuit 2 flow temperature sensor.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 107
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 93
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 105
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 96
F.545
Fault meaningModels and manual pages
Short circuit at the mixed heating circuit 2 flow temperature sensor.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 107
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 93
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 105
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 96
F.546
Fault meaningModels and manual pages
Open circuit at the mixed heating circuit 3 flow temperature sensor.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 107
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 93
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 105
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 96
F.547
Fault meaningModels and manual pages
Short circuit at the mixed heating circuit 3 flow temperature sensor.
Viessmann (5)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 107
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 93
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 105
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 96
F.548
Fault meaningModels and manual pages
The manual lists a fault at the flow temperature sensor for mixed heating circuit 4.
Viessmann (4)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 94
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 97
F.549
Fault meaningModels and manual pages
The flow temperature sensor for mixed heating circuit 4 is short-circuited.
Viessmann (4)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TE6130884 GB · 5/2020 · PDF p. 94
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
  • Vitodens 222-W B2LE6130945 GB · 3/2020 · PDF p. 97
F.574
Fault meaningModels and manual pages
The room sensor for heating circuit 1 is unavailable, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.575
Fault meaningModels and manual pages
The room sensor for heating circuit 1 is open-circuit, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.576
Fault meaningModels and manual pages
The room sensor for heating circuit 1 is short-circuited, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.577
Fault meaningModels and manual pages
The room sensor for heating circuit 2 is unavailable, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.578
Fault meaningModels and manual pages
The room sensor for heating circuit 2 is open-circuit, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.579
Fault meaningModels and manual pages
The room sensor for heating circuit 2 is short-circuited, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.580
Fault meaningModels and manual pages
The room sensor for heating circuit 3 is unavailable, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 96
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.581
Fault meaningModels and manual pages
The room sensor for heating circuit 3 is open-circuit, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.582
Fault meaningModels and manual pages
The room sensor for heating circuit 3 is short-circuited, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 108
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 106
F.583
Fault meaningModels and manual pages
The room sensor for heating circuit 4 is unavailable, where fitted.
Viessmann (2)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.584
Fault meaningModels and manual pages
The room sensor for heating circuit 4 is open-circuit, where fitted.
Viessmann (2)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.585
Fault meaningModels and manual pages
The room sensor for heating circuit 4 is short-circuited, where fitted.
Viessmann (2)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.666
Fault meaningModels and manual pages
Open circuit at the TS3 domestic hot-water preheating sensor, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.667
Fault meaningModels and manual pages
Short circuit at the TS3 domestic hot-water preheating sensor, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.668
Fault meaningModels and manual pages
Open circuit at the TS4 hot-water temperature sensor in the solar installation.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.669
Fault meaningModels and manual pages
Short circuit at the TS4 hot-water temperature sensor in the solar installation.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.670
Fault meaningModels and manual pages
Open circuit at the TS3 buffer temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.671
Fault meaningModels and manual pages
Short circuit at the TS3 buffer temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.672
Fault meaningModels and manual pages
Open circuit at the TS3 thermostat-function temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.673
Fault meaningModels and manual pages
Short circuit at the TS3 thermostat-function temperature sensor, where fitted.
Viessmann (3)
  • Vitodens 200-W B2HE/B2KE6131268 GB · 6/2019 · PDF p. 97
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 109
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 107
F.693
Fault meaningModels and manual pages
Open circuit at the flue gas temperature sensor.
Viessmann (2)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 110
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 108
F.694
Fault meaningModels and manual pages
The flue high-limit safety signals disagree.
Viessmann (2)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 110
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 108
F.696
Fault meaningModels and manual pages
Short circuit at the flue gas temperature sensor.
Viessmann (2)
  • Vitodens 200-W B2HF/B2KF (7-inch touchscreen)5593201 GB · 3/2023 · PDF p. 110
  • Vitodens 222-F B2TF (3.5-inch display)viessmann-vitodens222-official-current · PDF p. 108
Fb0
Fault meaningModels and manual pages
The flue temperature sensor circuit is short-circuited.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 56
Fb8
Fault meaningModels and manual pages
The second flue temperature sensor circuit is open.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 56
FF1
Fault meaningModels and manual pages
The flue gas temperature limiter has tripped.
Viessmann (1)
  • Vitodens 025-W BPKB-24/BPKB-28; Vitodens Classic 24/28 with matching BPKB type6227767 GB · 11/2024 · PDF p. 55
H1
Fault meaningModels and manual pages
Heating flow thermistor circuit fault.
Ideal (1)
  • Mexico HE15, HE18, HE24, HE30, HE36 (ErP)201787 A12 · 6/2015 · PDF p. 49
H4
Fault meaningModels and manual pages
Dry-fire thermistor circuit fault.
Ideal (1)
  • Mexico HE15, HE18, HE24, HE30, HE36 (ErP)201787 A12 · 6/2015 · PDF p. 50
H:03.00
Fault meaningModels and manual pages
Communication with the flue thermistor has failed.
Baxi (2)
  • Combi 224/228/424/428 (manual 7661586-2)7661586-2 · 12/07/2016 (12072016) · PDF p. 65
  • Combi 224/228/424/428 and 428 LPG (manual 7696317-1)7696317-1 · 21/03/2018 · PDF p. 66
L4
Fault meaningModels and manual pages
Heating flow thermistor circuit fault.
Ideal (11)
  • Atlantic Combi 24, 30, 35UIN 223483 A03 · July 2020 · PDF p. 55
  • Classic2 Combi 24, 30, 35UIN 220219 A07 · June 2022 · PDF p. 55
  • Esprit Eco2 Combi 24, 30, 35UIN 220218 A07 · June 2022 · PDF p. 55
  • Exclusive2 Combi 24, 30, 35UIN 220221 A07 · June 2022 · PDF p. 55
  • Independent+ Combi 24, 30, 35 (UIN 222354)ideal-combi-legacy-independentplus-phc · PDF p. 56
  • Instinct2 Combi 24, 30, 35UIN 220222 A07 · June 2022 · PDF p. 55
  • Logic Code Combi ESP1 26, 33, 38UIN 222364 A06 · 08/2026 · PDF p. 56
  • Logic Combi C24, C30, C35 (UIN 222351)UIN 222351 A01 · April 2019 · PDF p. 55
  • Logic Combi ESP1 24, 30, 35UIN 222353 A07 · 08/2026 · PDF p. 55
  • i-mini Combi C24, C30UIN 222352 · April 2019 · PDF p. 55
  • i2 Combi 24, 30, 35UIN 220220 A05 · July 2020 · PDF p. 55
The control/no-flow thermistor circuit has reported a fault.
Ideal (7)
  • Independent System S15, S18, S24, S30UIN 215351 A08 · February 2019 · PDF p. 54
  • Logic Heat H12, H15, H18, H24, H30215354 A06 · 10/2017 · PDF p. 54
  • Logic MAX Heat H12, H15, H18, H24, H30219010 A04 · 2/2019 · PDF p. 55
  • Logic MAX System S15, S18, S24, S30UIN 219009 A04 · February 2019 · PDF p. 54
  • Logic System S15, S18, S24, S30 (S series)UIN 215349 A05 · February 2018 · PDF p. 54
  • Logic+ Heat H12, H15, H18, H24, H30215355 A10 · 2/2019 · PDF p. 54
  • Logic+ System S15, S18, S24, S30UIN 215353 A01 · July 2016 · PDF p. 54
L04
Fault meaningModels and manual pages
Heating flow thermistor circuit fault.
Ideal (6)
  • Independent Combi2 C24, C30, C35236469 A02 · 04/2023 · PDF p. 52
  • Independent System2 S15, S18, S24, S30236470 A02 · 04/2023 · PDF p. 48
  • Logic Combi2 C24, C30, C35237664 A08 · 08/2026 · PDF p. 55
  • Logic Heat2 H12, H15, H18, H24, H30UIN 228298 A07 · 10/2024 · PDF p. 51
  • Logic System2 S15, S18, S24, S30UIN 237665 A06 · 07/2025 · PDF p. 50
  • i-mini2 Combi C24, C30, C35UIN 236471 A02 · 04/2023 · PDF p. 52
L5
Fault meaningModels and manual pages
Heating return thermistor circuit fault.
Ideal (18)
  • Atlantic Combi 24, 30, 35UIN 223483 A03 · July 2020 · PDF p. 55
  • Classic2 Combi 24, 30, 35UIN 220219 A07 · June 2022 · PDF p. 55
  • Esprit Eco2 Combi 24, 30, 35UIN 220218 A07 · June 2022 · PDF p. 55
  • Exclusive2 Combi 24, 30, 35UIN 220221 A07 · June 2022 · PDF p. 55
  • Independent System S15, S18, S24, S30UIN 215351 A08 · February 2019 · PDF p. 54
  • Independent+ Combi 24, 30, 35 (UIN 222354)ideal-combi-legacy-independentplus-phc · PDF p. 56
  • Instinct2 Combi 24, 30, 35UIN 220222 A07 · June 2022 · PDF p. 55
  • Logic Code Combi ESP1 26, 33, 38UIN 222364 A06 · 08/2026 · PDF p. 56
  • Logic Combi C24, C30, C35 (UIN 222351)UIN 222351 A01 · April 2019 · PDF p. 55
  • Logic Combi ESP1 24, 30, 35UIN 222353 A07 · 08/2026 · PDF p. 55
  • Logic Heat H12, H15, H18, H24, H30215354 A06 · 10/2017 · PDF p. 54
  • Logic MAX Heat H12, H15, H18, H24, H30219010 A04 · 2/2019 · PDF p. 55
  • Logic MAX System S15, S18, S24, S30UIN 219009 A04 · February 2019 · PDF p. 54
  • Logic System S15, S18, S24, S30 (S series)UIN 215349 A05 · February 2018 · PDF p. 54
  • Logic+ Heat H12, H15, H18, H24, H30215355 A10 · 2/2019 · PDF p. 54
  • Logic+ System S15, S18, S24, S30UIN 215353 A01 · July 2016 · PDF p. 54
  • i-mini Combi C24, C30UIN 222352 · April 2019 · PDF p. 55
  • i2 Combi 24, 30, 35UIN 220220 A05 · July 2020 · PDF p. 55
L05
Fault meaningModels and manual pages
Heating return thermistor circuit fault.
Ideal (6)
  • Independent Combi2 C24, C30, C35236469 A02 · 04/2023 · PDF p. 52
  • Independent System2 S15, S18, S24, S30236470 A02 · 04/2023 · PDF p. 48
  • Logic Combi2 C24, C30, C35237664 A08 · 08/2026 · PDF p. 55
  • Logic Heat2 H12, H15, H18, H24, H30UIN 228298 A07 · 10/2024 · PDF p. 51
  • Logic System2 S15, S18, S24, S30UIN 237665 A06 · 07/2025 · PDF p. 50
  • i-mini2 Combi C24, C30, C35UIN 236471 A02 · 04/2023 · PDF p. 52
L.025
Fault meaningModels and manual pages
Reversible reduced operation. The cold-water inlet temperature sensor circuit is shorted, where fitted.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 96
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 85
N.027
Fault meaningModels and manual pages
Reduced operation requiring attention. The temperature signal at the domestic hot-water connection is implausible, where fitted.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 96
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 86
N.100
Fault meaningModels and manual pages
Reduced operation requiring attention. The signal from the outdoor temperature sensor has been interrupted on a weather-compensated installation.
Vaillant (2)
  • ecoTEC plus 610, ecoTEC plus 615, ecoTEC plus 620, ecoTEC plus 625, ecoTEC plus 630, ecoTEC plus 635, ecoTEC plus 826, ecoTEC plus 832, ecoTEC plus 836, ecoTEC plus 840 (remastered generation)0020308118_06 · 22.08.2024 · PDF p. 98
  • ecoTEC plus 940 storage combi (remastered generation)0020308121_05 · 13.02.2024 · PDF p. 87
U 10
Fault meaningModels and manual pages
The low-temperature heating zone flow probe circuit is interrupted, where fitted.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
U 11
Fault meaningModels and manual pages
The optional low-temperature heating zone flow probe circuit is shorted.
Vokèra (1)
  • Verve i502012222 — Rev.3 (07/17), stated PDFp3 · PDF p. 32
Which boilers does this cover?

This lookup covers UK domestic gas boiler ranges in our 2016–2026 manual collection. Match the model, output, generation and manual edition to the appliance. PDF page numbers count the cover as page one. Some manuals include optional cylinder, outdoor or room sensors. These entries apply when that equipment is fitted.

Some books are parts lists or cover a different generation. We could verify the Vokèra Pinnacle 20S and 25S, for example. The Pinnacle 30S, several older Vokèra ErP variants, Ideal Logic Code Combi2 38 and Baxi 819 Heat are among the models for which we lack a matching service fault table. Oil and electric boilers fall outside this gas boiler lesson.

Match the model and manual edition to the boiler. A thermostat trip can mean it correctly detected excess heat.

What is the difference between a boiler thermistor and a thermostat?

A thermistor gives the boiler a changing temperature reading. A thermostat has contacts that open or close at a switching point. A multimeter measures resistance in both tests, but a healthy result looks different.

Follow the copper flow pipe away from the heat exchanger in the film. As the pipe warms, the flow NTC’s resistance falls. The PCB measures the resulting signal in its sensing circuit and uses its calibration to estimate the water temperature. The board can then adjust the burner output against the requested temperature. A cold reading alone does not call for heat; the boiler also needs demand and its safety checks to pass.

The room thermostat requests central heating. The high-limit safety thermostat inside the boiler has a different job. Its normally closed contacts open on overheat so the burner is stopped. Measuring those contacts tells you whether the switch is open or closed. It cannot give you a water temperature in degrees.

Where are the temperature sensors on this combi?

Baxi Main Eco Compact Combi with labels pointing to the flow, return, hot-water and flue thermistors and the safety thermostat.
In the HxAR boiler, the flow and return thermistors sit on the heating pipework. The flue sensor sits up by the exhaust. The yellow label identifies the separate overheat thermostat.
Heating flow NTC · E20
Measures the primary water leaving the main heat exchanger. The film shows its clip and wiring back to the PCB.
Heating return NTC · E40
Measures water returning towards the heat exchanger. This is the sensor behind the two central-heating examples below.
Domestic hot-water NTC · E321
Monitors the temperature of the hot water supplied to the taps. A tap running cold can also have a cause elsewhere in the boiler, as the E28 example shows.
Flue NTC · E28
Measures the temperature of the combustion products. Its resistance reference is different from the return sensor’s, even though both are NTCs.
Safety thermostat · E110
Opens the overheat protection circuit when it operates. A trip can be a genuine response to overheating; the code alone does not establish a faulty switch.

These codes refer to the Baxi Main Eco Compact Combi used in HxAR. On another model, check its own wiring diagram, fault table and temperature–resistance data.

What should the multimeter read?

Start with the component, its temperature and where the probes are touching. These are readings across isolated components or the disconnected harness in the training room.

Resistance and continuity on the HxAR testing pad
SampleMeter readingWhat it tells you
Good Baxi return NTC at 25°CAbout 10 kΩResistance falls as the pad warms and rises as it cools. Compare it against the chart at the measured temperature.
PTC comparison sampleResistance rises with heatMove the meter between the samples on the same pad to see the opposite responses. The Baxi NTC chart applies to the NTC sample.
Open thermistor or broken wireOLThe meter finds no continuous path in these examples. Probe contact and where the break sits both matter.
Shorted thermistor at room temperatureNear 0 ΩA very low resistance is unexpected where this NTC should measure thousands of ohms. Bridged wiring can give a similar reading through the harness.
Working, cool safety thermostatNear 0 Ω, then OL when trippedClosed contacts give continuity. In the simulated trip, they open. Stuck-closed contacts can pass the cold check and fail the trip test.

10 kΩ means 10,000 Ω. In the lesson the healthy flue NTC measures about 20 kΩ at 25°C. Using the return sensor’s 10 kΩ reference here could lead you to condemn a working part.

Sensor, wiring harness or PCB? Three faults compared

E28 · The hot tap runs cold

The boiler detects water flow, but the display identifies the flue temperature circuit. In the simulator, the engineer measures OL through the disconnected harness and about 20 kΩ directly at the flue sensor at 25°C. The sensor is within its reference range. Replacing the damaged harness restores the signal, and the tap heats up on the repeat test.

Two HxAR meter readings: OL through the disconnected flue sensor harness and 20 kΩ directly across the sensor at 25°C.
Baxi E28 in the simulator. The open circuit disappears when the probes move from the harness plug to the sensor terminals. At 25°C the flue sensor reads about 20 kΩ, which points the investigation back to the harness and its connectors.

E40 · The return sensor is open circuit

The room thermostat calls for heat and the radiators stay cold. The meter reads OL through the return circuit and still reads OL directly across the disconnected sensor. The break is inside the sensor in this exercise. After fitting the spare return NTC, the heating runs and the radiator warms.

E40 again · The sensor and harness both test good

This time the return NTC reads about 10 kΩ at 25°C both directly and through its harness. Reconnecting the original PCB brings the code back. In this simulated fault, fitting the spare PCB clears E40, and a fresh heating demand warms the radiator. The two matching readings explain why a second return sensor would have been the wrong spare.

On a real boiler, a plausible static reading is only one piece of evidence. The model’s service procedure also accounts for connections, intermittent faults and test conditions before a board is condemned. Internal boiler tests are for a suitably qualified Gas Safe registered engineer. You can perform every exercise shown here in HxAR.

Read the complete film transcript

00:00 · Find the four thermistors and the safety thermostat

Welcome to this gas combination boiler thermistor and thermostat tutorial. Here are the four thermistors. One on the heating flow, one on the return, one at the hot-water outlet, and one at the flue. Just above the flow thermistor sits the safety thermostat. You can use the same approach on other boilers.

Check the sensor locations and expected readings for that model. This flow thermistor measures the water leaving the heat exchanger. As it warms, its resistance falls. That change tells the board the temperature. This return thermistor measures the water coming back. The board can compare that temperature with the flow.

How hot is the water at the tap? This outlet thermistor tells the board, so it can adjust the heat. Up by the flue, this fourth thermistor measures the temperature of the exhaust gases. The safety thermostat does a different job. If it gets too hot, its contacts open and the burner stops. The board sees a switch change state.

01:11 · How the boiler PCB reads the flow thermistor

Follow the hot water in from the left. See the orange band spreading? That's the copper pipe warming up. The clip grips the pipe, so heat passes straight into it. Heat reaches the ceramic. Watch the queue at the narrow gap. As it warms, the passage opens. Resistance falls, and more current flows.

The board now sees just under one volt. Its fixed resistor lets it work out the sensor resistance. For this sensor, two and a half kilohms means sixty degrees. See the small flame? The room still needs heat. The board has turned the flame down to hold its target. Now the room thermostat is satisfied. The burner goes out, but watch the green power light. The board is still reading.

As the copper and ceramic cool, the gap narrows. The charges queue up again, and fewer get through. Notice the two readings. Resistance is going up. Less current flows around the loop, yet the voltage measured here rises. The board uses that voltage to look up a cooler temperature. Watch it approach twenty-five degrees.

The pipe is cool. The burner stays off because the room is warm enough. Now the room thermostat calls for heat again. Once the start checks pass, the burner lights. Follow the copper as it warms again. The board sees the sensor voltage begin to fall. Now watch the disc in the safety thermostat. We're heating it separately.

The disc snaps. The contacts open, and the board stops the burner.

02:59 · Multimeter test on the heating pad | NTC vs PTC

Let's move over to the testing bay on the left, and see what happens on the meter. The probes are on the blue NTC. At twenty-five degrees, ten thousand ohms. That's ten kilohms. Tap Apply heat. Keep your eye on the meter as the pad warms up. See it falling? By forty degrees, we're down to five point three kilohms. That's nearly half our starting reading.

Both sensors share the same pad. At forty-five degrees, move the probes over to the black PTC. The meter now reads one thousand, one hundred and sixty-six ohms. Leave the heat on. Follow the two readings together. The PTC is climbing, while the NTC beside it is still falling.

At sixty degrees, the NTC is down to about two and a half kilohms. The PTC is up to one point three kilohms.

03:58 · Where NTC and PTC thermistors are used

Back at the testing bay, both parts are measuring the same temperature. Warm the pad. The NTC resistance falls, while the PTC resistance rises. Which one are you likely to meet in a gas boiler? NTCs are commonly used to measure temperature. Let's look inside our Main Eco Compact.

Follow the heating water. The flow sensor clips onto the pipe leaving the heat exchanger. The return sensor clips onto the pipe bringing water back. The hot-water sensor screws into the hot- water manifold. The flue probe uses a bayonet fitting and monitors the temperature of the exhaust.

Watch the flow sensor as the pipe warms. The board converts its signal into a temperature. As the flow approaches the heating target, the burner can turn down. Now look at three jobs a PTC can do elsewhere. The first is a resettable fuse on a circuit board. A short draws extra current and heats the device.

Its resistance rises sharply. See how little current gets through? A small current still passes. Clear the fault, remove power and let it cool, and it can reset. This is a three-phase pump motor. The shaft turns inside a fixed stator. Its copper wires run along slots, then loop back at each end.

Look between the copper bundles. The small probe is one of three winding sensors. If the windings overheat, its PTC resistance rises sharply. The trip unit releases a contactor, which disconnects the motor. The third example is outdoors. This optional heater cable runs along a condensate pipe beneath the insulation.

Here we've cut the insulation away so you can see it. With the cable powered, a colder section draws more current and gives off more heat. As that section warms, it draws less current and its heat output falls. So start with two questions. Which way does the resistance move when warm?

Then, what does this particular circuit do with that change?

06:09 · No hot water | E28 flue sensor wiring fault

Back to the boiler. Let's create a fault. Beside the room thermostat, tap the random fault button. You might first notice it in the shower, or when the radiators stay cold. A fault that stops the burner can leave you without both hot water and heating. Without a fault code, we'd follow the manufacturer's sequence of operation.

Is there a demand? Has the boiler recognised it? At which step does it stop? Let's try the hot tap. Water is flowing. Give it a moment to warm up. Still cold. The tap is open, but the burner hasn't lit. Let's look at the boiler display. E28. On this Main Eco Compact, that points to the flue temperature sensor circuit.

The tap runs cold, but the code takes us to the flue. Compare the codes. E20 points to the heating flow sensor, E40 to the return, and E321 to the hot-water sensor. Our display says E28, so we'll follow the flue sensor wiring. In the simulator, with the circuit isolated, measure through the harness first.

The meter reads OL. There's a break somewhere in the path through the wiring and the sensor. Now put the probes directly on the flue sensor. At twenty-five degrees it reads about twenty kilohms. That's the value Baxi gives for this sensor. What changed between the two tests?

We left the harness and its connectors out. The open reading disappeared. That points us back to the wiring. From the spares tray, choose the flue sensor harness and fit it. The fault code clears. But will the hot tap heat up? Open the hot tap again. This time the burner lights and the water heats up.

We've proved the repair by repeating the same test that first showed the fault.

08:07 · No central heating | E40 return thermistor fault

Here's a different call. The heating is on, but the radiators are cold. Leave the hot tap closed. This time we want the boiler responding to the room thermostat. The room is at eighteen degrees. The thermostat is set to sixteen, so it has no reason to call for heat yet.

Turn the target up to twenty-two. Now look at the status board. The receiver is calling for heating. The burner hasn't lit and the radiator stays cold. Turning the thermostat up any further won't explain that. Look at the boiler display. E40. On this Main Eco Compact, that's the heating return temperature sensor circuit.

Follow the return pipe back from the radiator to the boiler. There's the clip-on thermistor. It tells the board the temperature of water coming back from the heating circuit. E40 points us here, but which part of the circuit has failed? In the simulator, turn the demand down and isolate the boiler.

Unplug the return sensor harness at the board. With the meter across its two contacts, we're measuring the wiring and sensor together. OL. That means there isn't a complete path between the probes. Remember the last fault? If only the harness were broken, what would you expect to see directly on a healthy sensor?

Let's move the probes onto the sensor's own terminals. Still OL. Even with the harness out of the measurement, the sensor itself is open. For comparison, Baxi gives about ten kilohms at twenty-five degrees for this return sensor. At a different temperature you'd expect a different resistance.

Here the meter can't find a path at all. At the tray, choose the heating return sensor. The packet below it is a spare harness. Our second reading tells us which one to fit. With the new sensor fitted and power restored, E40 has cleared. Now repeat the original test. Raise the target to twenty-two again and watch what the boiler does.

This time, the burner lights. Hot water circulates through the radiator, and the room temperature starts to rise. The hot tap stayed closed. That's how we know we've restored central heating.

10:26 · E40 again | Sensor and wiring test good

E40 again. Last time, the return sensor itself read open circuit. Does the same code mean we need another sensor? Let's find out. The room is at eighteen degrees. Turn the thermostat up to twenty-two. The receiver picks up the call, but the burner stays off. The hot tap is closed.

Turn the demand down and isolate the boiler in the simulator. Leave the sensor connected to its wiring. Unplug the harness at the board and put the probes across the two plug contacts. About ten kilohms. That's the expected resistance for this return sensor at twenty-five degrees.

This reading includes the sensor, its wiring and the connections along that path. Now move the probes directly onto the isolated sensor. About ten kilohms again. This time the sensor reads correctly on its own, and we get the same result through its harness. Those readings check the circuit at this moment.

A loose connection could still come and go. Reconnect the plug on the original board, restore power and look at the display. E40 is still there. In this exercise, it's the return sensor input on the printed circuit board, or PCB, that's faulty. That's why the boiler displays E40 even though the meter sees a healthy circuit.

Isolate the supply again. Beside the spares tray is the wrapped boiler control board. Select it and tap Fit spare. We're keeping the sensor and harness we just tested. Restore power. E40 has cleared. Let's prove the repair the same way we found the problem. Turn the thermostat back up to twenty-two.

There's the flame. Heat is spreading down the radiator, and the room thermometer is climbing. With the hot tap closed, that's the central heating back in service.

12:24 · Open circuit (OL) vs short circuit on a thermistor

Back at the testing table, here's a question. If the meter reads almost zero ohms, have you found a fault? Let's try that reading on two different parts. Start with the return thermistor from our last exercise. These are isolated training samples. Put the probes straight onto the two terminals of the good one.

At twenty-five degrees, this Baxi sensor reads about ten kilohms. Same pad, same temperature. Move the probes to the middle sensor. OL. Both tips are touching metal, but the path inside this sample is broken. Try the one on the right. Almost zero ohms. At this temperature we expected ten kilohms, so this sensor has an internal Watch what happens when we get that same reading on a thermostat.

short. First, one quick wiring puzzle. This time the probes are at the harness plug. The meter says OL. Is the break in the sensor or in its wiring? Where would you move the probes? Lift the harness and test the sensor terminals directly. Ten kilohms. Look at the loose wire on the harness we just tested.

The sensor is good in this example. Changing it would leave the break in place.

13:40 · Safety thermostat continuity and trip tests

Now swap to the safety thermostat. This is a switch. On the cool, working sample, the contacts are closed. There's our near-zero reading again. What should the meter show when the switch trips? Tap Simulate trip. OL. The contacts have opened, exactly as they should. Release the trip here on the table.

Back to nearly zero. We have seen this switch both open and close. Try the middle thermostat. OL even at rest. Simulating a trip still gives OL. This sample is stuck open. Compare that with the working switch, which gave OL only while it was tripped. Last one. Cold, this thermostat reads almost zero, just like the working one.

Predict what you'll see when we trip it. Still almost zero. The contacts are stuck closed. A cold test alone would have missed it. On the thermistor we checked resistance at a known temperature. On the thermostat we checked whether the contacts actually changed state.

14:44 · Try the fault codes yourself in HxAR

Let's step back and turn the heating on. Watch the boiler. The burner lights, the radiator warms up, and there's no fault code on the display. You can visit this room yourself in HxAR. Look for the Baxi Main Eco Compact Combi in the Catalogue. Open the fault code field, type E20 and press Enter.

See the yellow ring? That's the heating flow sensor. Now try E28. This time it picks out the flue sensor. Want to test yourself? Choose Practise E28 to start that fault in the simulator. Or try Random fault beside the room thermostat. Read the display and decide what you'd test first.

We've got more boiler tutorials on the way. Subscribe for the next one, and have a look at the other videos on this channel. You'll find more heating guides at ephg.limited. Thanks for watching.

Technical references and simulation

Baxi, Main Eco Compact Combi Installation and Service Manual, 7908748 v01. See the wiring diagram on page 15, fault codes on page 58 and component checks on page 61. The heating pad, PTC comparison and three repair scenarios are HxAR training demonstrations.