Heating · HxAR training film
Boiler thermistor and safety thermostat faults
Enter your boiler’s fault code to see which thermistor or thermostat it relates to on your model. To learn how engineers distinguish a sensor fault from a wiring or PCB fault, watch the worked examples on a Baxi Main Eco Compact Combi.
Film chapters
Choose a test to jump to it. Press Play if the film is paused.
- 00:00Find the four thermistors and the safety thermostat
- 01:11How the boiler PCB reads the flow thermistor
- 02:59Multimeter test on the heating pad | NTC vs PTC
- 03:58Where NTC and PTC thermistors are used
- 06:09No hot water | E28 flue sensor wiring fault
- 08:07No central heating | E40 return thermistor fault
- 10:26E40 again | Sensor and wiring test good
- 12:24Open circuit (OL) vs short circuit on a thermistor
- 13:40Safety thermostat continuity and trip tests
- 14:44Try the fault codes yourself in HxAR
Which boilers show this fault code?
Enter the code from the boiler display to see which makes and models use it for a thermistor or thermostat fault. Select a make beside a fault meaning to see the exact models and manual pages.
Browse all thermistor and thermostat fault codes
0
| Fault meaning | Models and manual pages |
|---|---|
| The S1/S2 sensor self-check failed. | Intergas (5)
|
2
| Fault meaning | Models and manual pages |
|---|---|
| The S1 flow and S2 return sensor connections appear interchanged. | Intergas (5)
|
| The safety thermostat has operated and the boiler has locked out. | Biasi (2)
|
6
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the central-heating flow NTC circuit. | Biasi (2)
|
7
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the hot-water cylinder temperature sensor, where fitted. | Viessmann (4)
|
| Fault on the hot-water or cylinder temperature probe, according to the installation. | Biasi (2)
|
8
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the hot-water cylinder temperature sensor, where fitted. | Viessmann (4)
|
| Fault on the outdoor temperature probe circuit. | Biasi (2)
|
8C 373
| Fault meaning | Models and manual pages |
|---|---|
| Repeated overheat indications from the thermostat have triggered lockout. | Worcester Bosch (3)
|
10
| Fault meaning | Models and manual pages |
|---|---|
| The S1 heating flow temperature sensor reports a fault. | Intergas (5)
|
| Short circuit at the outside temperature sensor, where fitted. | Viessmann (4)
|
| Flue probe or thermal-fuse protection has tripped. | Biasi (2)
|
11
| Fault meaning | Models and manual pages |
|---|---|
| The S1 heating flow temperature sensor reports a fault. | Intergas (5)
|
| Open circuit at the solar collector temperature sensor, where fitted. | Viessmann (2)
|
12
| Fault meaning | Models and manual pages |
|---|---|
| The S1 heating flow temperature sensor reports a fault. | Intergas (5)
|
| Fault on the central-heating return NTC circuit. | Biasi (2)
|
| Short circuit at the solar collector temperature sensor, where fitted. | Viessmann (2)
|
13
| Fault meaning | Models and manual pages |
|---|---|
| The S1 heating flow temperature sensor reports a fault. | Intergas (5)
|
| Open circuit at the outdoor temperature sensor, where fitted. | Viessmann (4)
|
14
| Fault meaning | Models and manual pages |
|---|---|
| The S1 heating flow temperature sensor reports a fault. | Intergas (5)
|
| Short circuit at the outdoor temperature sensor, where fitted. | Viessmann (4)
|
15
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the solar hot-water cylinder temperature sensor, where fitted. | Viessmann (2)
|
16
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the solar hot-water cylinder temperature sensor, where fitted. | Viessmann (2)
|
18
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the outside temperature sensor, where fitted. | Viessmann (4)
|
20
| Fault meaning | Models and manual pages |
|---|---|
| The S2 heating return temperature sensor reports a fault. | Intergas (5)
|
| High-limit thermostat or flue thermostat has operated. | Vokèra (1)
|
21
| Fault meaning | Models and manual pages |
|---|---|
| The S2 heating return temperature sensor reports a fault. | Intergas (5)
|
22
| Fault meaning | Models and manual pages |
|---|---|
| The S2 heating return temperature sensor reports a fault. | Intergas (5)
|
23
| Fault meaning | Models and manual pages |
|---|---|
| The S2 heating return temperature sensor reports a fault. | Intergas (5)
|
24
| Fault meaning | Models and manual pages |
|---|---|
| The S2 heating return temperature sensor reports a fault. | Intergas (5)
|
26
| Fault meaning | Models and manual pages |
|---|---|
| The two heating NTC readings disagree beyond the permitted range. | Biasi (2)
|
27
| Fault meaning | Models and manual pages |
|---|---|
| The optional outdoor temperature sensor circuit reads short. | Intergas (5)
|
29
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the low-loss header temperature sensor, where fitted. | Viessmann (2)
|
30
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the boiler water temperature sensor. | Viessmann (4)
|
| Short circuit at the low-loss header temperature sensor, where fitted. | Viessmann (2)
|
38
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the boiler water temperature sensor. | Viessmann (4)
|
49
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the flue gas temperature sensor. | Viessmann (4)
|
50
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the flue gas temperature sensor. | Viessmann (4)
|
| Short circuit at the hot-water cylinder temperature sensor, where fitted. | Viessmann (2)
|
51
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the hot-water outlet temperature sensor, where fitted. | Viessmann (3)
|
57
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the external room temperature sensor, where fitted. | Viessmann (4)
|
58
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the external room temperature sensor, where fitted. | Viessmann (4)
|
| Open circuit at the hot-water cylinder temperature sensor, where fitted. | Viessmann (2)
|
59
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the hot-water outlet temperature sensor, where fitted. | Viessmann (3)
|
60
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the return temperature sensor. | Viessmann (1)
|
| The domestic hot-water temperature probe circuit reports a fault. | Vokèra (1)
|
62
| Fault meaning | Models and manual pages |
|---|---|
| The high-limit safety cut-out has tripped. | Viessmann (4)
|
63
| Fault meaning | Models and manual pages |
|---|---|
| The flue gas temperature limiter has tripped. | Viessmann (4)
|
68
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the return temperature sensor. | Viessmann (1)
|
70
| Fault meaning | Models and manual pages |
|---|---|
| Flow NTC fault on the second heating circuit. | Vokèra (1)
|
71
| Fault meaning | Models and manual pages |
|---|---|
| Flow NTC fault on the second heating circuit. | Vokèra (1)
|
72
| Fault meaning | Models and manual pages |
|---|---|
| Return NTC fault on the second heating circuit. | Vokèra (1)
|
77
| Fault meaning | Models and manual pages |
|---|---|
| Underfloor overheat thermostat has operated on the second heating circuit. | Vokèra (1)
|
182
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the outlet temperature sensor, where fitted. | Viessmann (4)
|
183
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the outlet temperature sensor, where fitted. | Viessmann (4)
|
184
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the combined heating flow sensor and high-limit cut-out circuit. | Viessmann (4)
|
185
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the combined heating flow sensor and high-limit cut-out circuit. | Viessmann (3)
|
222
| Fault meaning | Models and manual pages |
|---|---|
| The fault table groups these codes as an interruption in the heating flow NTC wiring. | Worcester Bosch (1)
|
223
| Fault meaning | Models and manual pages |
|---|---|
| The fault table groups these codes as an interruption in the heating flow NTC wiring. | Worcester Bosch (1)
|
224
| Fault meaning | Models and manual pages |
|---|---|
| The flue or heat exchanger high-limit thermostat circuit has operated. | Worcester Bosch (12)
|
| The safety temperature limiter has tripped. | Worcester Bosch (2)
|
240
| Fault meaning | Models and manual pages |
|---|---|
| The fault table groups these codes as an interruption in the heating return NTC wiring. | Worcester Bosch (1)
|
241
| Fault meaning | Models and manual pages |
|---|---|
| The fault table groups these codes as an interruption in the heating return NTC wiring. | Worcester Bosch (1)
|
324
| Fault meaning | Models and manual pages |
|---|---|
| DHW outlet thermistor fault (information-menu cause code). | Worcester Bosch (2)
|
325
| Fault meaning | Models and manual pages |
|---|---|
| DHW outlet thermistor incorrectly installed (information-menu cause code). | Worcester Bosch (2)
|
345
| Fault meaning | Models and manual pages |
|---|---|
| The temperature limiter has tripped. | Viessmann (3)
|
350
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow temperature sensor circuit reads short. | Worcester Bosch (1)
|
351
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow temperature sensor circuit is interrupted. | Worcester Bosch (2)
|
373
| Fault meaning | Models and manual pages |
|---|---|
| Heat transfer during calibration was insufficient and the temperature limiter shut the burner down. | Viessmann (4)
|
393
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the second flue temperature sensor, where fitted. | Viessmann (3)
|
394
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the second flue temperature sensor, where fitted. | Viessmann (3)
|
416
| Fault meaning | Models and manual pages |
|---|---|
| The flue gas temperature sensor is incorrectly positioned. | Viessmann (4)
|
446
| Fault meaning | Models and manual pages |
|---|---|
| The flow sensor and high-limit channel give inconsistent readings. | Viessmann (4)
|
544
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the mixed heating circuit 2 flow temperature sensor. | Viessmann (3)
|
545
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the mixed heating circuit 2 flow temperature sensor. | Viessmann (3)
|
574
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 1 is unavailable, where fitted. | Viessmann (3)
|
575
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 1 is open-circuit, where fitted. | Viessmann (3)
|
576
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 1 is short-circuited, where fitted. | Viessmann (3)
|
577
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 2 is unavailable, where fitted. | Viessmann (3)
|
578
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 2 is open-circuit, where fitted. | Viessmann (3)
|
579
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 2 is short-circuited, where fitted. | Viessmann (3)
|
694
| Fault meaning | Models and manual pages |
|---|---|
| The flue high-limit safety signals disagree. | Viessmann (3)
|
815
| Fault meaning | Models and manual pages |
|---|---|
| Low-loss header temperature sensor circuit fault, where that accessory is fitted. | Worcester Bosch (10)
|
1021
| Fault meaning | Models and manual pages |
|---|---|
| Domestic hot-water or cylinder charging temperature sensor fault, according to the hot-water arrangement. | Worcester Bosch (8)
|
1022
| Fault meaning | Models and manual pages |
|---|---|
| On a system with a cylinder sensor, the cylinder temperature signal or its connection is faulty. | Worcester Bosch (7)
|
1025
| Fault meaning | Models and manual pages |
|---|---|
| Heating return thermistor circuit fault. | Worcester Bosch (2)
|
1027
| Fault meaning | Models and manual pages |
|---|---|
| The optional DHW preheat kit inlet temperature sensor is disconnected. | Worcester Bosch (1)
|
1037
| Fault meaning | Models and manual pages |
|---|---|
| Outside temperature sensor signal fault on a weather-compensated installation. Heating can enter backup operation. | Worcester Bosch (13)
|
1068
| Fault meaning | Models and manual pages |
|---|---|
| Outside-temperature sensor or lambda probe fault, as applicable to the fitted equipment. | Worcester Bosch (14)
|
1073
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow temperature sensor circuit reads short. | Worcester Bosch (4)
|
1074
| Fault meaning | Models and manual pages |
|---|---|
| No signal reaches the boiler from the flow temperature sensor. | Worcester Bosch (4)
|
1075
| Fault meaning | Models and manual pages |
|---|---|
| Heat exchanger temperature sensor circuit reads short. | Worcester Bosch (13)
|
1076
| Fault meaning | Models and manual pages |
|---|---|
| The heat exchanger temperature sensor circuit is disconnected. | Worcester Bosch (13)
|
2963
| Fault meaning | Models and manual pages |
|---|---|
| Heat exchanger or flow temperature signals are implausible. | Worcester Bosch (14)
|
A02
| Fault meaning | Models and manual pages |
|---|---|
| The high-limit thermostat circuit has triggered a fault. | Vokèra (4)
|
A3
| Fault meaning | Models and manual pages |
|---|---|
| The flue temperature sensor is incorrectly positioned. | Viessmann (2)
|
A06
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water temperature probe circuit reports a fault. | Vokèra (3)
|
A07
| Fault meaning | Models and manual pages |
|---|---|
| Flow-side alarm. The manual lists a probe fault, excessive flow temperature or a flow/return temperature difference. | Vokèra (4)
|
A7
| Fault meaning | Models and manual pages |
|---|---|
| Domestic hot-water thermistor circuit fault. | Worcester Bosch (2)
|
| The hot-water NTC circuit reports a fault, where a cylinder sensor is fitted. | Worcester Bosch (1)
|
A7 808
| Fault meaning | Models and manual pages |
|---|---|
| Domestic hot-water thermistor circuit fault. | Worcester Bosch (3)
|
A08
| Fault meaning | Models and manual pages |
|---|---|
| Return-side alarm. The manual lists a probe fault, excessive return temperature or a flow/return temperature difference. | Vokèra (4)
|
A09
| Fault meaning | Models and manual pages |
|---|---|
| Flue probe alarm. The table includes a probe or counter fault and a high flue-temperature trip. | Vokèra (4)
|
A20
| Fault meaning | Models and manual pages |
|---|---|
| The high-limit thermostat circuit has triggered a fault. | Vokèra (4)
|
A60
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water temperature probe circuit reports a fault. | Vokèra (2)
|
A70
| Fault meaning | Models and manual pages |
|---|---|
| Flow-side alarm. The manual lists a probe fault, excessive flow temperature or a flow/return temperature difference. | Vokèra (4)
|
A77
| Fault meaning | Models and manual pages |
|---|---|
| Low-temperature thermostat circuit alarm. | Vokèra (4)
|
A80
| Fault meaning | Models and manual pages |
|---|---|
| Return-side alarm. The manual lists a probe fault, excessive return temperature or a flow/return temperature difference. | Vokèra (4)
|
A90
| Fault meaning | Models and manual pages |
|---|---|
| The flue temperature probe circuit reports a fault. | Vokèra (4)
|
A 02
| Fault meaning | Models and manual pages |
|---|---|
| The high-limit thermostat circuit has triggered a fault. | Vokèra (1)
|
A 04
| Fault meaning | Models and manual pages |
|---|---|
| Overheating may have tripped the safety thermostat. | Vokèra (1)
|
A 07
| Fault meaning | Models and manual pages |
|---|---|
| Flow-side alarm. The manual lists a probe fault, excessive flow temperature or a flow/return temperature difference. | Vokèra (1)
|
| The low-temperature zone safety thermostat has operated, where fitted. | Vokèra (1)
|
A 08
| Fault meaning | Models and manual pages |
|---|---|
| Return-side alarm. The manual lists a probe fault, excessive return temperature or a flow/return temperature difference. | Vokèra (1)
|
A 09
| Fault meaning | Models and manual pages |
|---|---|
| Flue probe alarm. Its LED pattern distinguishes probe or heat-exchanger cleaning indications from the flue high-limit trip. | Vokèra (1)
|
A 77
| Fault meaning | Models and manual pages |
|---|---|
| The underfloor heating thermostat has raised an alarm. | Vokèra (1)
|
A.00.28
| Fault meaning | Models and manual pages |
|---|---|
| Solar temperature sensor is disconnected or reads below its range, where fitted. | Baxi (4)
|
A.00.29
| Fault meaning | Models and manual pages |
|---|---|
| Solar temperature sensor is short-circuited or reads above its range, where fitted. | Baxi (4)
|
A.00.34
| Fault meaning | Models and manual pages |
|---|---|
| An outdoor temperature sensor is configured but its signal is missing. | Baxi (4)
|
AL20
| Fault meaning | Models and manual pages |
|---|---|
| The high-limit thermostat circuit has triggered a fault. | Vokèra (2)
|
| Limit thermostat or flue thermostat fault. | Vokèra (1)
|
AL71
| Fault meaning | Models and manual pages |
|---|---|
| The central-heating flow probe circuit reports a fault. | Vokèra (3)
|
AL73
| Fault meaning | Models and manual pages |
|---|---|
| The heating return probe circuit reports a fault. | Vokèra (3)
|
b0
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the flue gas temperature sensor. | Viessmann (4)
|
b8
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the flue gas temperature sensor. | Viessmann (4)
|
CC 800
| Fault meaning | Models and manual pages |
|---|---|
| The optional outdoor sensor reports a fault. | Worcester Bosch (3)
|
| The accessory outside temperature sensor is reporting a fault. | Worcester Bosch (2)
|
D1 240
| Fault meaning | Models and manual pages |
|---|---|
| Return temperature sensor circuit reads short. | Worcester Bosch (3)
|
D1 241
| Fault meaning | Models and manual pages |
|---|---|
| Return temperature sensor circuit is disconnected. | Worcester Bosch (3)
|
d3
| Fault meaning | Models and manual pages |
|---|---|
| The external temperature limiter connection reports an interruption. | Worcester Bosch (2)
|
E02
| Fault meaning | Models and manual pages |
|---|---|
| The safety thermostat has operated and the boiler has locked out. | Biasi (7)
|
E2
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow thermistor circuit fault. | Worcester Bosch (5)
|
E2 222
| Fault meaning | Models and manual pages |
|---|---|
| Flow temperature sensor circuit reads short. | Worcester Bosch (3)
|
| Heating flow temperature sensor circuit reads short. | Worcester Bosch (2)
|
E2 223
| Fault meaning | Models and manual pages |
|---|---|
| Flow temperature sensor circuit is disconnected. | Worcester Bosch (3)
|
| Heating flow temperature sensor circuit is disconnected. | Worcester Bosch (2)
|
E2 350
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow sensor circuit reads short. | Worcester Bosch (3)
|
| Heating flow temperature sensor circuit reads short. | Worcester Bosch (2)
|
E2 351
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow sensor circuit is open. | Worcester Bosch (3)
|
| Heating flow temperature sensor circuit is disconnected. | Worcester Bosch (2)
|
E06
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the central-heating flow NTC circuit. | Biasi (7)
|
E07
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the hot-water NTC circuit. | Biasi (4)
|
| Fault on the hot-water or cylinder temperature probe, according to the installation. | Biasi (2)
|
E08
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the outdoor temperature probe circuit. | Biasi (6)
|
| The outdoor temperature probe reports a fault with weather compensation configured. | Biasi (1)
|
E09
| Fault meaning | Models and manual pages |
|---|---|
| The flue NTC circuit is interrupted. | Biasi (3)
|
| Fault on the flue NTC circuit. | Biasi (2)
|
E9
| Fault meaning | Models and manual pages |
|---|---|
| The heating high-limit thermostat circuit has tripped. | Worcester Bosch (5)
|
E9 220
| Fault meaning | Models and manual pages |
|---|---|
| Heat exchanger safety temperature sensor circuit reads short. | Worcester Bosch (3)
|
E9 221
| Fault meaning | Models and manual pages |
|---|---|
| Heat exchanger safety temperature sensor circuit is open. | Worcester Bosch (3)
|
E9 224
| Fault meaning | Models and manual pages |
|---|---|
| The maximum-temperature safety thermostat circuit has operated. | Worcester Bosch (3)
|
| The flue or high-limit thermostat safety circuit has operated. | Worcester Bosch (2)
|
E10
| Fault meaning | Models and manual pages |
|---|---|
| The flue temperature protection has operated. | Biasi (5)
|
| Flue probe or thermal-fuse protection has tripped. | Biasi (2)
|
E12
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the central-heating return NTC circuit. | Biasi (7)
|
E19
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the hot-water inlet temperature probe, where fitted. | Biasi (2)
|
E020
| Fault meaning | Models and manual pages |
|---|---|
| The high-limit thermostat circuit has triggered a fault. | Vokèra (12)
|
E20
| Fault meaning | Models and manual pages |
|---|---|
| The central heating flow thermistor circuit reports a fault. | Baxi (20)
Potterton (10)
|
E26
| Fault meaning | Models and manual pages |
|---|---|
| The two heating NTC readings disagree beyond the permitted range. | Biasi (2)
|
E28
| Fault meaning | Models and manual pages |
|---|---|
| The flue temperature sensor circuit reports a fault. | Baxi (16)
Potterton (4)
|
| The fault can involve the flue thermistor, air pressure switch, wiring, blocked flue or condensate path. | Baxi (4)
Potterton (5)
|
| Fault on the cylinder temperature probe, where fitted. | Biasi (2)
|
| The model-specific error table identifies the hot-water thermistor circuit. | Potterton (1)
|
E40
| Fault meaning | Models and manual pages |
|---|---|
| The return-water thermistor circuit reports a fault. | Baxi (15)
Potterton (4)
|
E50
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water thermistor circuit reports a fault. | Baxi (3)
Potterton (2)
|
| The model-specific error table identifies the flue thermistor circuit. | Potterton (1)
|
E060
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water temperature probe circuit reports a fault. | Vokèra (7)
|
E070
| Fault meaning | Models and manual pages |
|---|---|
| Flow-side alarm. The manual lists a probe fault, excessive flow temperature or a flow/return temperature difference. | Vokèra (8)
|
| The central-heating flow probe circuit reports a fault. | Vokèra (4)
|
E077
| Fault meaning | Models and manual pages |
|---|---|
| The boiler reports a fault at the main-zone water thermostat. | Vokèra (7)
|
| The main-zone or enabled zone 1 water thermostat has signalled. | Vokèra (3)
|
| The boiler has lost communication with the low-temperature thermostat. | Vokèra (2)
|
E080
| Fault meaning | Models and manual pages |
|---|---|
| Return-side alarm. The manual lists a probe fault, excessive return temperature or a flow/return temperature difference. | Vokèra (8)
|
| The heating return probe circuit reports a fault. | Vokèra (4)
|
E084
| Fault meaning | Models and manual pages |
|---|---|
| Fault at the zone 1 delivery temperature probe. | Vokèra (3)
|
E086
| Fault meaning | Models and manual pages |
|---|---|
| Fault at the main-zone delivery temperature probe. | Vokèra (3)
|
E090
| Fault meaning | Models and manual pages |
|---|---|
| The flue probe can be faulty or can have detected excessive flue temperature. | Vokèra (8)
|
| The flue temperature probe circuit reports a fault. | Vokèra (4)
|
E110
| Fault meaning | Models and manual pages |
|---|---|
| The safety thermostat has tripped on the primary circuit. | Baxi (17)
Potterton (9)
|
| Safety thermostat trip. The manual associates this indication with a pump fault. | Baxi (3)
Potterton (1)
|
E111
| Fault meaning | Models and manual pages |
|---|---|
| The safety thermostat has tripped on excessive temperature. | Baxi (3)
|
E130
| Fault meaning | Models and manual pages |
|---|---|
| Flue temperature protection has operated. | Baxi (20)
Potterton (10)
|
E154
| Fault meaning | Models and manual pages |
|---|---|
| The flow/return sensor temperature comparison has failed. | Baxi (12)
Potterton (4)
|
E321
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water thermistor circuit reports a fault. | Baxi (9)
Potterton (2)
|
E 01
| Fault meaning | Models and manual pages |
|---|---|
| The flow temperature probe circuit is open. | Vokèra (1)
|
E 02
| Fault meaning | Models and manual pages |
|---|---|
| The return temperature probe circuit is open. | Vokèra (1)
|
E 08
| Fault meaning | Models and manual pages |
|---|---|
| The hot-water cylinder sensor circuit is open. | Vokèra (1)
|
E 11
| Fault meaning | Models and manual pages |
|---|---|
| The flow temperature probe circuit is shorted. | Vokèra (1)
|
E 12
| Fault meaning | Models and manual pages |
|---|---|
| The return temperature probe circuit is shorted. | Vokèra (1)
|
E 18
| Fault meaning | Models and manual pages |
|---|---|
| The cylinder temperature probe circuit is shorted. | Vokèra (1)
|
E 35
| Fault meaning | Models and manual pages |
|---|---|
| Flue temperature exceeds 75°C or the flue probe is shorted. | Vokèra (1)
|
E 36
| Fault meaning | Models and manual pages |
|---|---|
| The flue thermostat contact is open. | Vokèra (1)
|
E.00.04
| Fault meaning | Models and manual pages |
|---|---|
| The return temperature sensor input is open. | Baxi (4)
|
E.00.05
| Fault meaning | Models and manual pages |
|---|---|
| The return temperature sensor input is short-circuited. | Baxi (4)
|
E.00.16
| Fault meaning | Models and manual pages |
|---|---|
| The configured hot-water cylinder sensor signal is missing. | Baxi (4)
|
E.00.17
| Fault meaning | Models and manual pages |
|---|---|
| The hot-water cylinder sensor circuit is short-circuited, where fitted. | Baxi (4)
|
E.00.20
| Fault meaning | Models and manual pages |
|---|---|
| The flue sensor is disconnected or reads below its measuring range. | Baxi (4)
|
E.00.21
| Fault meaning | Models and manual pages |
|---|---|
| The flue sensor is short-circuited or reads above its measuring range. | Baxi (4)
|
E.04.01
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow thermistor input is short-circuited. | Baxi (4)
|
E.04.02
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow thermistor input is open. | Baxi (4)
|
E.04.03
| Fault meaning | Models and manual pages |
|---|---|
| Flow temperature is above its limit or the flow sensor is short-circuited. | Baxi (4)
|
E.04.18
| Fault meaning | Models and manual pages |
|---|---|
| The flow reading is below minimum or its sensor is disconnected. | Baxi (4)
|
E:00.04
| Fault meaning | Models and manual pages |
|---|---|
| The return temperature sensor input is open. | Baxi (2)
|
E:00.05
| Fault meaning | Models and manual pages |
|---|---|
| The return temperature sensor input is short-circuited. | Baxi (2)
|
E:04.01
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow thermistor input is short-circuited. | Baxi (2)
|
E:04.02
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow thermistor input is open. | Baxi (2)
|
E:04.04
| Fault meaning | Models and manual pages |
|---|---|
| The flue temperature sensor input is short-circuited. | Baxi (2)
|
E:04.05
| Fault meaning | Models and manual pages |
|---|---|
| The flue temperature sensor input is open. | Baxi (2)
|
E:04.08
| Fault meaning | Models and manual pages |
|---|---|
| The water temperature reached the safety cut-out limit. | Baxi (2)
|
Er 02
| Fault meaning | Models and manual pages |
|---|---|
| The safety thermostat has operated and the boiler has locked out. | Biasi (5)
|
Er 06
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the central-heating flow NTC circuit. | Biasi (5)
|
Er 07
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the hot-water NTC circuit. | Biasi (3)
|
Er 08
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the outdoor temperature probe circuit. | Biasi (5)
|
Er 09
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the flue NTC circuit. | Biasi (5)
|
Er 10
| Fault meaning | Models and manual pages |
|---|---|
| The flue temperature protection has operated. | Biasi (5)
|
Er 12
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the central-heating return NTC circuit. | Biasi (5)
|
Er 19
| Fault meaning | Models and manual pages |
|---|---|
| Fault on the hot-water inlet temperature probe, where fitted. | Biasi (3)
|
F000
| Fault meaning | Models and manual pages |
|---|---|
| Heat exchanger temperature sensor S0 reports a fault. | Intergas (2)
|
F0 278
| Fault meaning | Models and manual pages |
|---|---|
| A safety sensor failed the power-up check. | Worcester Bosch (3)
|
F0b
| Fault meaning | Models and manual pages |
|---|---|
| The heating circuit dual flow temperature sensor is short-circuited. | Viessmann (1)
|
F0C
| Fault meaning | Models and manual pages |
|---|---|
| Domestic hot-water thermistor circuit fault. | Ideal (3)
|
F0t
| Fault meaning | Models and manual pages |
|---|---|
| Fault in the room thermostat or its connection, where fitted. | Ideal (6)
|
F2
| Fault meaning | Models and manual pages |
|---|---|
| The boiler temperature limiter has tripped. | Viessmann (4)
|
F02
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the combined heating flow temperature sensor and high-limit cut-out. | Viessmann (1)
|
F4
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow thermistor circuit fault. | Ideal (18)
|
| The control/no-flow thermistor circuit has reported a fault. | Ideal (8)
|
F04
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow thermistor circuit fault. | Ideal (6)
|
F5
| Fault meaning | Models and manual pages |
|---|---|
| Heating return thermistor circuit fault. | Ideal (26)
|
F05
| Fault meaning | Models and manual pages |
|---|---|
| Heating return thermistor circuit fault. | Ideal (6)
|
F6
| Fault meaning | Models and manual pages |
|---|---|
| Signal fault at the outside temperature sensor, where fitted. | Ideal (23)
|
F06
| Fault meaning | Models and manual pages |
|---|---|
| Signal fault at the outside temperature sensor, where fitted. | Ideal (6)
|
F010
| Fault meaning | Models and manual pages |
|---|---|
| The heat exchanger temperature sensor S0 circuit reports a fault. | Intergas (2)
|
F10
| Fault meaning | Models and manual pages |
|---|---|
| The outdoor temperature sensor is short-circuited. | Viessmann (1)
|
F011
| Fault meaning | Models and manual pages |
|---|---|
| The heat exchanger temperature sensor S0 circuit reports a fault. | Intergas (2)
|
F012
| Fault meaning | Models and manual pages |
|---|---|
| The flue gas sensor S5 circuit reports a fault. | Intergas (2)
|
F014
| Fault meaning | Models and manual pages |
|---|---|
| The heat exchanger temperature sensor S0 is incorrectly seated. | Intergas (2)
|
F015
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow sensor S1 is incorrectly seated. | Intergas (2)
|
F016
| Fault meaning | Models and manual pages |
|---|---|
| Domestic hot water sensor S3 is incorrectly seated. | Intergas (2)
|
F18
| Fault meaning | Models and manual pages |
|---|---|
| The outdoor temperature sensor input is open. | Viessmann (1)
|
F027
| Fault meaning | Models and manual pages |
|---|---|
| The optional outdoor weather-compensation sensor S6 circuit reads short. | Intergas (2)
|
F30
| Fault meaning | Models and manual pages |
|---|---|
| In this BPKB manual, the fault table identifies a short circuit at the outdoor sensor. | Viessmann (1)
|
F031
| Fault meaning | Models and manual pages |
|---|---|
| Central heating flow temperature sensor S1 reports a fault. | Intergas (2)
|
F31
| Fault meaning | Models and manual pages |
|---|---|
| The room temperature sensor is short-circuited. | Viessmann (1)
|
F38
| Fault meaning | Models and manual pages |
|---|---|
| In this BPKB manual, the fault table identifies an open circuit at the outdoor sensor. | Viessmann (1)
|
F39
| Fault meaning | Models and manual pages |
|---|---|
| The room temperature sensor input is open. | Viessmann (1)
|
F51
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water temperature sensor is short-circuited. | Viessmann (1)
|
F58
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water temperature sensor input is open. | Viessmann (1)
|
F.00
| Fault meaning | Models and manual pages |
|---|---|
| The boiler has lost the signal from the heating flow temperature sensor. The sensor, its plug and wiring are on this circuit. | Glow-worm (13)
Vaillant (15)
|
F.000
| Fault meaning | Models and manual pages |
|---|---|
| The boiler has lost the signal from the heating flow temperature sensor. The sensor, its plug and wiring are on this circuit. | Vaillant (2)
|
F.01
| Fault meaning | Models and manual pages |
|---|---|
| The boiler has lost the signal from the heating return temperature sensor. The sensor, plug, wiring or PCB connection can interrupt it. | Glow-worm (13)
Vaillant (15)
|
F.001
| Fault meaning | Models and manual pages |
|---|---|
| The boiler has lost the signal from the heating return temperature sensor. The sensor, plug, wiring or PCB connection can interrupt it. | Vaillant (2)
|
F.02
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water outlet temperature signal is interrupted. Applies to the hot-water sensor configuration specified in this manual. The manual specifies this indication together with F.91. | Vaillant (4)
|
F.002
| Fault meaning | Models and manual pages |
|---|---|
| The temperature signal from the domestic hot-water connection has been interrupted, where this sensor is fitted. | Vaillant (2)
|
F.03
| Fault meaning | Models and manual pages |
|---|---|
| The boiler has lost the cylinder temperature signal on installations equipped with this sensor. The manual specifies this indication together with F.91. | Vaillant (4)
|
F.003
| Fault meaning | Models and manual pages |
|---|---|
| The boiler has lost the cylinder temperature signal on installations equipped with this sensor. | Vaillant (2)
|
F.7
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the hot-water cylinder temperature sensor, where fitted. | Viessmann (5)
|
F.8
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the hot-water cylinder temperature sensor, where fitted. | Viessmann (5)
|
F.9
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the domestic hot-water outlet temperature sensor. | Viessmann (1)
|
F.10
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow temperature sensor circuit is shorted. | Glow-worm (13)
Vaillant (15)
|
| Short circuit at the domestic hot-water outlet temperature sensor. | Viessmann (1)
|
F.010
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow temperature sensor circuit is shorted. | Vaillant (2)
|
F.11
| Fault meaning | Models and manual pages |
|---|---|
| The heating return temperature sensor circuit is shorted. | Glow-worm (13)
Vaillant (15)
|
| Open circuit at the solar collector temperature sensor, where fitted. | Viessmann (5)
|
F.011
| Fault meaning | Models and manual pages |
|---|---|
| The heating return temperature sensor circuit is shorted. | Vaillant (2)
|
F.12
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the solar collector temperature sensor, where fitted. | Viessmann (5)
|
| The hot-water outlet temperature sensor circuit is shorted on installations equipped with this sensor. The manual specifies this indication together with F.91. | Vaillant (4)
|
F.012
| Fault meaning | Models and manual pages |
|---|---|
| The temperature sensor circuit at the domestic hot-water connection has shorted, where fitted. | Vaillant (2)
|
F.12 and F.91
| Fault meaning | Models and manual pages |
|---|---|
| Both codes appear together for a shorted cylinder temperature sensor circuit, where this sensor is fitted. | Glow-worm (6)
Vaillant (5)
|
F.13
| Fault meaning | Models and manual pages |
|---|---|
| The cylinder temperature sensor circuit has shorted, where this sensor is fitted. | Glow-worm (13)
Vaillant (5)
|
| Open circuit at the outdoor temperature sensor, where fitted. | Viessmann (5)
|
| The cylinder or warm-start sensor circuit is shorted, depending on equipment. For the actoSTOR cylinder, the manual specifies F.13 with F.91. | Vaillant (4)
|
| A short is reported on the hot-water temperature sensor circuit (cylinder or warm-start sensor, depending on equipment). | Vaillant (3)
|
F.013
| Fault meaning | Models and manual pages |
|---|---|
| The cylinder temperature sensor circuit is shorted, where a cylinder sensor is fitted. | Vaillant (2)
|
F.14
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the outdoor temperature sensor, where fitted. | Viessmann (5)
|
F.15
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the solar hot-water cylinder temperature sensor, where fitted. | Viessmann (5)
|
F.16
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the solar hot-water cylinder temperature sensor, where fitted. | Viessmann (5)
|
F.19
| Fault meaning | Models and manual pages |
|---|---|
| The lower cylinder temperature sensor circuit is open, where fitted. | Viessmann (2)
|
F.20
| Fault meaning | Models and manual pages |
|---|---|
| The temperature limiter has stopped the burner. The listed causes include problems with temperature sensing. | Glow-worm (2)
Vaillant (6)
|
F.020
| Fault meaning | Models and manual pages |
|---|---|
| Overheat protection has closed the gas valve because the flow or return temperature reading exceeded the limit. | Vaillant (2)
|
F.29
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the low-loss header temperature sensor, where fitted. | Viessmann (5)
|
F.30
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the low-loss header temperature sensor, where fitted. | Viessmann (5)
|
F.46
| Fault meaning | Models and manual pages |
|---|---|
| A short is reported on the cold-water inlet temperature sensor circuit. | Glow-worm (2)
|
| A short is reported on the cold-water inlet temperature sensor circuit. This applies to the optional solar inlet sensor. | Vaillant (1)
|
F.047
| Fault meaning | Models and manual pages |
|---|---|
| The hot-water outlet temperature signal from the internal cylinder is implausible, where this cylinder is fitted. | Vaillant (1)
|
F.49
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the flue gas temperature sensor. | Viessmann (5)
|
F.50
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the flue gas temperature sensor. | Viessmann (5)
|
F.57
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the external room temperature sensor, where fitted. | Viessmann (5)
|
F.58
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the external room temperature sensor, where fitted. | Viessmann (5)
|
F.62
| Fault meaning | Models and manual pages |
|---|---|
| The high-limit safety cut-out has tripped. | Viessmann (5)
|
F.63
| Fault meaning | Models and manual pages |
|---|---|
| The flue gas temperature limiter has tripped. | Viessmann (5)
|
F.64
| Fault meaning | Models and manual pages |
|---|---|
| The control electronics report a sensor or electronics fault. The temperature-sensing circuit and PCB are possible causes. | Glow-worm (13)
Vaillant (15)
|
F.71
| Fault meaning | Models and manual pages |
|---|---|
| The flow temperature signal stays at a constant value. Poor pipe contact or a defective sensor can cause this. | Glow-worm (13)
Vaillant (11)
|
| The heating flow temperature signal is implausible. Poor contact with the pipe can affect this reading. | Vaillant (4)
|
F.071
| Fault meaning | Models and manual pages |
|---|---|
| The heating flow temperature signal is implausible. Poor contact with the pipe can affect this reading. | Vaillant (2)
|
F.72
| Fault meaning | Models and manual pages |
|---|---|
| The fault table lists an excessive difference between the flow and return NTC readings among the possible causes. | Glow-worm (11)
Vaillant (6)
|
| The flow and return sensor readings disagree. The manual identifies both temperature sensors in this check. | Vaillant (9)
|
| The return temperature reading is faulty. The manual lists both the flow and return temperature sensors as possible causes. | Glow-worm (2)
|
F.072
| Fault meaning | Models and manual pages |
|---|---|
| The difference between flow and return temperature readings is implausible. | Vaillant (2)
|
F.78
| Fault meaning | Models and manual pages |
|---|---|
| The domestic hot-water outlet temperature input is interrupted with external controls connected. | Glow-worm (13)
Vaillant (11)
|
F.80
| Fault meaning | Models and manual pages |
|---|---|
| The actoSTOR cylinder inlet temperature signal is missing or faulty. Applies to installations equipped with this cylinder. The manual specifies this indication together with F.91. | Vaillant (4)
|
F.080
| Fault meaning | Models and manual pages |
|---|---|
| The internal cylinder cold-water inlet sensor is faulty or disconnected. Its plug and wiring are part of the signal path. | Vaillant (1)
|
F.83
| Fault meaning | Models and manual pages |
|---|---|
| The flow or return sensor registers too little temperature change when the burner starts. Water quantity and sensor contact affect this check. | Vaillant (5)
|
| The difference between the flow and return sensor temperatures is too small. Sensor contact and water volume affect this check. | Vaillant (4)
|
| The boiler reports a fault in the way the NTC temperatures change. Water pressure and sensor contact with the pipes are among the listed causes. | Glow-worm (2)
|
F.84
| Fault meaning | Models and manual pages |
|---|---|
| The temperature difference between flow and return is implausible. | Glow-worm (13)
Vaillant (13)
|
F.084
| Fault meaning | Models and manual pages |
|---|---|
| The temperature difference between flow and return is implausible. | Vaillant (2)
|
F.85
| Fault meaning | Models and manual pages |
|---|---|
| The positions or pipe contact of the flow and return temperature sensors are inconsistent with the expected readings. | Glow-worm (13)
Vaillant (15)
|
F.085
| Fault meaning | Models and manual pages |
|---|---|
| The positions or pipe contact of the flow and return temperature sensors are inconsistent with the expected readings. | Vaillant (2)
|
F.86
| Fault meaning | Models and manual pages |
|---|---|
| The underfloor heating safety contact is open, or its sensor circuit is disconnected or faulty, where fitted. | Glow-worm (11)
Vaillant (5)
|
F.91
| Fault meaning | Models and manual pages |
|---|---|
| A sensor fault is reported by the connected actoSTOR cylinder. Applies where this accessory is fitted. | Vaillant (2)
|
F.182
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the outlet temperature sensor, where fitted. | Viessmann (5)
|
F.183
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the outlet temperature sensor, where fitted. | Viessmann (5)
|
F.184
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the combined heating flow sensor and high-limit cut-out circuit. | Viessmann (5)
|
F.185
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the combined heating flow sensor and high-limit cut-out circuit. | Viessmann (5)
|
F.345
| Fault meaning | Models and manual pages |
|---|---|
| The temperature limiter has tripped. | Viessmann (5)
|
F.373
| Fault meaning | Models and manual pages |
|---|---|
| Heat transfer during calibration was insufficient and the temperature limiter shut the burner down. | Viessmann (5)
|
F.394
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the second flue temperature sensor, where fitted. | Viessmann (2)
|
F.416
| Fault meaning | Models and manual pages |
|---|---|
| The flue gas temperature sensor is incorrectly positioned. | Viessmann (5)
|
F.446
| Fault meaning | Models and manual pages |
|---|---|
| The flow sensor and high-limit channel give inconsistent readings. | Viessmann (5)
|
F.530
| Fault meaning | Models and manual pages |
|---|---|
| The solar controller is missing one or more sensor readings, where fitted. | Viessmann (5)
|
F.538
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the system return temperature sensor, where fitted. | Viessmann (3)
|
F.539
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the system return temperature sensor, where fitted. | Viessmann (3)
|
F.542
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the mixed heating circuit 1 flow temperature sensor. | Viessmann (1)
|
F.543
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the mixed heating circuit 1 flow temperature sensor. | Viessmann (1)
|
F.544
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the mixed heating circuit 2 flow temperature sensor. | Viessmann (5)
|
F.545
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the mixed heating circuit 2 flow temperature sensor. | Viessmann (5)
|
F.546
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the mixed heating circuit 3 flow temperature sensor. | Viessmann (5)
|
F.547
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the mixed heating circuit 3 flow temperature sensor. | Viessmann (5)
|
F.548
| Fault meaning | Models and manual pages |
|---|---|
| The manual lists a fault at the flow temperature sensor for mixed heating circuit 4. | Viessmann (4)
|
F.549
| Fault meaning | Models and manual pages |
|---|---|
| The flow temperature sensor for mixed heating circuit 4 is short-circuited. | Viessmann (4)
|
F.574
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 1 is unavailable, where fitted. | Viessmann (3)
|
F.575
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 1 is open-circuit, where fitted. | Viessmann (3)
|
F.576
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 1 is short-circuited, where fitted. | Viessmann (3)
|
F.577
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 2 is unavailable, where fitted. | Viessmann (3)
|
F.578
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 2 is open-circuit, where fitted. | Viessmann (3)
|
F.579
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 2 is short-circuited, where fitted. | Viessmann (3)
|
F.580
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 3 is unavailable, where fitted. | Viessmann (3)
|
F.581
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 3 is open-circuit, where fitted. | Viessmann (3)
|
F.582
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 3 is short-circuited, where fitted. | Viessmann (3)
|
F.583
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 4 is unavailable, where fitted. | Viessmann (2)
|
F.584
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 4 is open-circuit, where fitted. | Viessmann (2)
|
F.585
| Fault meaning | Models and manual pages |
|---|---|
| The room sensor for heating circuit 4 is short-circuited, where fitted. | Viessmann (2)
|
F.666
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the TS3 domestic hot-water preheating sensor, where fitted. | Viessmann (3)
|
F.667
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the TS3 domestic hot-water preheating sensor, where fitted. | Viessmann (3)
|
F.668
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the TS4 hot-water temperature sensor in the solar installation. | Viessmann (3)
|
F.669
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the TS4 hot-water temperature sensor in the solar installation. | Viessmann (3)
|
F.670
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the TS3 buffer temperature sensor, where fitted. | Viessmann (3)
|
F.671
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the TS3 buffer temperature sensor, where fitted. | Viessmann (3)
|
F.672
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the TS3 thermostat-function temperature sensor, where fitted. | Viessmann (3)
|
F.673
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the TS3 thermostat-function temperature sensor, where fitted. | Viessmann (3)
|
F.693
| Fault meaning | Models and manual pages |
|---|---|
| Open circuit at the flue gas temperature sensor. | Viessmann (2)
|
F.694
| Fault meaning | Models and manual pages |
|---|---|
| The flue high-limit safety signals disagree. | Viessmann (2)
|
F.696
| Fault meaning | Models and manual pages |
|---|---|
| Short circuit at the flue gas temperature sensor. | Viessmann (2)
|
Fb0
| Fault meaning | Models and manual pages |
|---|---|
| The flue temperature sensor circuit is short-circuited. | Viessmann (1)
|
Fb8
| Fault meaning | Models and manual pages |
|---|---|
| The second flue temperature sensor circuit is open. | Viessmann (1)
|
FF1
| Fault meaning | Models and manual pages |
|---|---|
| The flue gas temperature limiter has tripped. | Viessmann (1)
|
H1
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow thermistor circuit fault. | Ideal (1)
|
H4
| Fault meaning | Models and manual pages |
|---|---|
| Dry-fire thermistor circuit fault. | Ideal (1)
|
H:03.00
| Fault meaning | Models and manual pages |
|---|---|
| Communication with the flue thermistor has failed. | Baxi (2)
|
L4
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow thermistor circuit fault. | Ideal (11)
|
| The control/no-flow thermistor circuit has reported a fault. | Ideal (7)
|
L04
| Fault meaning | Models and manual pages |
|---|---|
| Heating flow thermistor circuit fault. | Ideal (6)
|
L5
| Fault meaning | Models and manual pages |
|---|---|
| Heating return thermistor circuit fault. | Ideal (18)
|
L05
| Fault meaning | Models and manual pages |
|---|---|
| Heating return thermistor circuit fault. | Ideal (6)
|
L.025
| Fault meaning | Models and manual pages |
|---|---|
| Reversible reduced operation. The cold-water inlet temperature sensor circuit is shorted, where fitted. | Vaillant (2)
|
N.027
| Fault meaning | Models and manual pages |
|---|---|
| Reduced operation requiring attention. The temperature signal at the domestic hot-water connection is implausible, where fitted. | Vaillant (2)
|
N.100
| Fault meaning | Models and manual pages |
|---|---|
| Reduced operation requiring attention. The signal from the outdoor temperature sensor has been interrupted on a weather-compensated installation. | Vaillant (2)
|
U 10
| Fault meaning | Models and manual pages |
|---|---|
| The low-temperature heating zone flow probe circuit is interrupted, where fitted. | Vokèra (1)
|
U 11
| Fault meaning | Models and manual pages |
|---|---|
| The optional low-temperature heating zone flow probe circuit is shorted. | Vokèra (1)
|
Which boilers does this cover?
This lookup covers UK domestic gas boiler ranges in our 2016–2026 manual collection. Match the model, output, generation and manual edition to the appliance. PDF page numbers count the cover as page one. Some manuals include optional cylinder, outdoor or room sensors. These entries apply when that equipment is fitted.
Some books are parts lists or cover a different generation. We could verify the Vokèra Pinnacle 20S and 25S, for example. The Pinnacle 30S, several older Vokèra ErP variants, Ideal Logic Code Combi2 38 and Baxi 819 Heat are among the models for which we lack a matching service fault table. Oil and electric boilers fall outside this gas boiler lesson.
Match the model and manual edition to the boiler. A thermostat trip can mean it correctly detected excess heat.
What is the difference between a boiler thermistor and a thermostat?
A thermistor gives the boiler a changing temperature reading. A thermostat has contacts that open or close at a switching point. A multimeter measures resistance in both tests, but a healthy result looks different.
Follow the copper flow pipe away from the heat exchanger in the film. As the pipe warms, the flow NTC’s resistance falls. The PCB measures the resulting signal in its sensing circuit and uses its calibration to estimate the water temperature. The board can then adjust the burner output against the requested temperature. A cold reading alone does not call for heat; the boiler also needs demand and its safety checks to pass.
The room thermostat requests central heating. The high-limit safety thermostat inside the boiler has a different job. Its normally closed contacts open on overheat so the burner is stopped. Measuring those contacts tells you whether the switch is open or closed. It cannot give you a water temperature in degrees.
Where are the temperature sensors on this combi?

- Heating flow NTC · E20
- Measures the primary water leaving the main heat exchanger. The film shows its clip and wiring back to the PCB.
- Heating return NTC · E40
- Measures water returning towards the heat exchanger. This is the sensor behind the two central-heating examples below.
- Domestic hot-water NTC · E321
- Monitors the temperature of the hot water supplied to the taps. A tap running cold can also have a cause elsewhere in the boiler, as the E28 example shows.
- Flue NTC · E28
- Measures the temperature of the combustion products. Its resistance reference is different from the return sensor’s, even though both are NTCs.
- Safety thermostat · E110
- Opens the overheat protection circuit when it operates. A trip can be a genuine response to overheating; the code alone does not establish a faulty switch.
These codes refer to the Baxi Main Eco Compact Combi used in HxAR. On another model, check its own wiring diagram, fault table and temperature–resistance data.
What should the multimeter read?
Start with the component, its temperature and where the probes are touching. These are readings across isolated components or the disconnected harness in the training room.
| Sample | Meter reading | What it tells you |
|---|---|---|
| Good Baxi return NTC at 25°C | About 10 kΩ | Resistance falls as the pad warms and rises as it cools. Compare it against the chart at the measured temperature. |
| PTC comparison sample | Resistance rises with heat | Move the meter between the samples on the same pad to see the opposite responses. The Baxi NTC chart applies to the NTC sample. |
| Open thermistor or broken wire | OL | The meter finds no continuous path in these examples. Probe contact and where the break sits both matter. |
| Shorted thermistor at room temperature | Near 0 Ω | A very low resistance is unexpected where this NTC should measure thousands of ohms. Bridged wiring can give a similar reading through the harness. |
| Working, cool safety thermostat | Near 0 Ω, then OL when tripped | Closed contacts give continuity. In the simulated trip, they open. Stuck-closed contacts can pass the cold check and fail the trip test. |
10 kΩ means 10,000 Ω. In the lesson the healthy flue NTC measures about 20 kΩ at 25°C. Using the return sensor’s 10 kΩ reference here could lead you to condemn a working part.
Sensor, wiring harness or PCB? Three faults compared
E28 · The hot tap runs cold
The boiler detects water flow, but the display identifies the flue temperature circuit. In the simulator, the engineer measures OL through the disconnected harness and about 20 kΩ directly at the flue sensor at 25°C. The sensor is within its reference range. Replacing the damaged harness restores the signal, and the tap heats up on the repeat test.

E40 · The return sensor is open circuit
The room thermostat calls for heat and the radiators stay cold. The meter reads OL through the return circuit and still reads OL directly across the disconnected sensor. The break is inside the sensor in this exercise. After fitting the spare return NTC, the heating runs and the radiator warms.
E40 again · The sensor and harness both test good
This time the return NTC reads about 10 kΩ at 25°C both directly and through its harness. Reconnecting the original PCB brings the code back. In this simulated fault, fitting the spare PCB clears E40, and a fresh heating demand warms the radiator. The two matching readings explain why a second return sensor would have been the wrong spare.
On a real boiler, a plausible static reading is only one piece of evidence. The model’s service procedure also accounts for connections, intermittent faults and test conditions before a board is condemned. Internal boiler tests are for a suitably qualified Gas Safe registered engineer. You can perform every exercise shown here in HxAR.
Read the complete film transcript
00:00 · Find the four thermistors and the safety thermostat
Welcome to this gas combination boiler thermistor and thermostat tutorial. Here are the four thermistors. One on the heating flow, one on the return, one at the hot-water outlet, and one at the flue. Just above the flow thermistor sits the safety thermostat. You can use the same approach on other boilers.
Check the sensor locations and expected readings for that model. This flow thermistor measures the water leaving the heat exchanger. As it warms, its resistance falls. That change tells the board the temperature. This return thermistor measures the water coming back. The board can compare that temperature with the flow.
How hot is the water at the tap? This outlet thermistor tells the board, so it can adjust the heat. Up by the flue, this fourth thermistor measures the temperature of the exhaust gases. The safety thermostat does a different job. If it gets too hot, its contacts open and the burner stops. The board sees a switch change state.
01:11 · How the boiler PCB reads the flow thermistor
Follow the hot water in from the left. See the orange band spreading? That's the copper pipe warming up. The clip grips the pipe, so heat passes straight into it. Heat reaches the ceramic. Watch the queue at the narrow gap. As it warms, the passage opens. Resistance falls, and more current flows.
The board now sees just under one volt. Its fixed resistor lets it work out the sensor resistance. For this sensor, two and a half kilohms means sixty degrees. See the small flame? The room still needs heat. The board has turned the flame down to hold its target. Now the room thermostat is satisfied. The burner goes out, but watch the green power light. The board is still reading.
As the copper and ceramic cool, the gap narrows. The charges queue up again, and fewer get through. Notice the two readings. Resistance is going up. Less current flows around the loop, yet the voltage measured here rises. The board uses that voltage to look up a cooler temperature. Watch it approach twenty-five degrees.
The pipe is cool. The burner stays off because the room is warm enough. Now the room thermostat calls for heat again. Once the start checks pass, the burner lights. Follow the copper as it warms again. The board sees the sensor voltage begin to fall. Now watch the disc in the safety thermostat. We're heating it separately.
The disc snaps. The contacts open, and the board stops the burner.
02:59 · Multimeter test on the heating pad | NTC vs PTC
Let's move over to the testing bay on the left, and see what happens on the meter. The probes are on the blue NTC. At twenty-five degrees, ten thousand ohms. That's ten kilohms. Tap Apply heat. Keep your eye on the meter as the pad warms up. See it falling? By forty degrees, we're down to five point three kilohms. That's nearly half our starting reading.
Both sensors share the same pad. At forty-five degrees, move the probes over to the black PTC. The meter now reads one thousand, one hundred and sixty-six ohms. Leave the heat on. Follow the two readings together. The PTC is climbing, while the NTC beside it is still falling.
At sixty degrees, the NTC is down to about two and a half kilohms. The PTC is up to one point three kilohms.
03:58 · Where NTC and PTC thermistors are used
Back at the testing bay, both parts are measuring the same temperature. Warm the pad. The NTC resistance falls, while the PTC resistance rises. Which one are you likely to meet in a gas boiler? NTCs are commonly used to measure temperature. Let's look inside our Main Eco Compact.
Follow the heating water. The flow sensor clips onto the pipe leaving the heat exchanger. The return sensor clips onto the pipe bringing water back. The hot-water sensor screws into the hot- water manifold. The flue probe uses a bayonet fitting and monitors the temperature of the exhaust.
Watch the flow sensor as the pipe warms. The board converts its signal into a temperature. As the flow approaches the heating target, the burner can turn down. Now look at three jobs a PTC can do elsewhere. The first is a resettable fuse on a circuit board. A short draws extra current and heats the device.
Its resistance rises sharply. See how little current gets through? A small current still passes. Clear the fault, remove power and let it cool, and it can reset. This is a three-phase pump motor. The shaft turns inside a fixed stator. Its copper wires run along slots, then loop back at each end.
Look between the copper bundles. The small probe is one of three winding sensors. If the windings overheat, its PTC resistance rises sharply. The trip unit releases a contactor, which disconnects the motor. The third example is outdoors. This optional heater cable runs along a condensate pipe beneath the insulation.
Here we've cut the insulation away so you can see it. With the cable powered, a colder section draws more current and gives off more heat. As that section warms, it draws less current and its heat output falls. So start with two questions. Which way does the resistance move when warm?
Then, what does this particular circuit do with that change?
06:09 · No hot water | E28 flue sensor wiring fault
Back to the boiler. Let's create a fault. Beside the room thermostat, tap the random fault button. You might first notice it in the shower, or when the radiators stay cold. A fault that stops the burner can leave you without both hot water and heating. Without a fault code, we'd follow the manufacturer's sequence of operation.
Is there a demand? Has the boiler recognised it? At which step does it stop? Let's try the hot tap. Water is flowing. Give it a moment to warm up. Still cold. The tap is open, but the burner hasn't lit. Let's look at the boiler display. E28. On this Main Eco Compact, that points to the flue temperature sensor circuit.
The tap runs cold, but the code takes us to the flue. Compare the codes. E20 points to the heating flow sensor, E40 to the return, and E321 to the hot-water sensor. Our display says E28, so we'll follow the flue sensor wiring. In the simulator, with the circuit isolated, measure through the harness first.
The meter reads OL. There's a break somewhere in the path through the wiring and the sensor. Now put the probes directly on the flue sensor. At twenty-five degrees it reads about twenty kilohms. That's the value Baxi gives for this sensor. What changed between the two tests?
We left the harness and its connectors out. The open reading disappeared. That points us back to the wiring. From the spares tray, choose the flue sensor harness and fit it. The fault code clears. But will the hot tap heat up? Open the hot tap again. This time the burner lights and the water heats up.
We've proved the repair by repeating the same test that first showed the fault.
08:07 · No central heating | E40 return thermistor fault
Here's a different call. The heating is on, but the radiators are cold. Leave the hot tap closed. This time we want the boiler responding to the room thermostat. The room is at eighteen degrees. The thermostat is set to sixteen, so it has no reason to call for heat yet.
Turn the target up to twenty-two. Now look at the status board. The receiver is calling for heating. The burner hasn't lit and the radiator stays cold. Turning the thermostat up any further won't explain that. Look at the boiler display. E40. On this Main Eco Compact, that's the heating return temperature sensor circuit.
Follow the return pipe back from the radiator to the boiler. There's the clip-on thermistor. It tells the board the temperature of water coming back from the heating circuit. E40 points us here, but which part of the circuit has failed? In the simulator, turn the demand down and isolate the boiler.
Unplug the return sensor harness at the board. With the meter across its two contacts, we're measuring the wiring and sensor together. OL. That means there isn't a complete path between the probes. Remember the last fault? If only the harness were broken, what would you expect to see directly on a healthy sensor?
Let's move the probes onto the sensor's own terminals. Still OL. Even with the harness out of the measurement, the sensor itself is open. For comparison, Baxi gives about ten kilohms at twenty-five degrees for this return sensor. At a different temperature you'd expect a different resistance.
Here the meter can't find a path at all. At the tray, choose the heating return sensor. The packet below it is a spare harness. Our second reading tells us which one to fit. With the new sensor fitted and power restored, E40 has cleared. Now repeat the original test. Raise the target to twenty-two again and watch what the boiler does.
This time, the burner lights. Hot water circulates through the radiator, and the room temperature starts to rise. The hot tap stayed closed. That's how we know we've restored central heating.
10:26 · E40 again | Sensor and wiring test good
E40 again. Last time, the return sensor itself read open circuit. Does the same code mean we need another sensor? Let's find out. The room is at eighteen degrees. Turn the thermostat up to twenty-two. The receiver picks up the call, but the burner stays off. The hot tap is closed.
Turn the demand down and isolate the boiler in the simulator. Leave the sensor connected to its wiring. Unplug the harness at the board and put the probes across the two plug contacts. About ten kilohms. That's the expected resistance for this return sensor at twenty-five degrees.
This reading includes the sensor, its wiring and the connections along that path. Now move the probes directly onto the isolated sensor. About ten kilohms again. This time the sensor reads correctly on its own, and we get the same result through its harness. Those readings check the circuit at this moment.
A loose connection could still come and go. Reconnect the plug on the original board, restore power and look at the display. E40 is still there. In this exercise, it's the return sensor input on the printed circuit board, or PCB, that's faulty. That's why the boiler displays E40 even though the meter sees a healthy circuit.
Isolate the supply again. Beside the spares tray is the wrapped boiler control board. Select it and tap Fit spare. We're keeping the sensor and harness we just tested. Restore power. E40 has cleared. Let's prove the repair the same way we found the problem. Turn the thermostat back up to twenty-two.
There's the flame. Heat is spreading down the radiator, and the room thermometer is climbing. With the hot tap closed, that's the central heating back in service.
12:24 · Open circuit (OL) vs short circuit on a thermistor
Back at the testing table, here's a question. If the meter reads almost zero ohms, have you found a fault? Let's try that reading on two different parts. Start with the return thermistor from our last exercise. These are isolated training samples. Put the probes straight onto the two terminals of the good one.
At twenty-five degrees, this Baxi sensor reads about ten kilohms. Same pad, same temperature. Move the probes to the middle sensor. OL. Both tips are touching metal, but the path inside this sample is broken. Try the one on the right. Almost zero ohms. At this temperature we expected ten kilohms, so this sensor has an internal Watch what happens when we get that same reading on a thermostat.
short. First, one quick wiring puzzle. This time the probes are at the harness plug. The meter says OL. Is the break in the sensor or in its wiring? Where would you move the probes? Lift the harness and test the sensor terminals directly. Ten kilohms. Look at the loose wire on the harness we just tested.
The sensor is good in this example. Changing it would leave the break in place.
13:40 · Safety thermostat continuity and trip tests
Now swap to the safety thermostat. This is a switch. On the cool, working sample, the contacts are closed. There's our near-zero reading again. What should the meter show when the switch trips? Tap Simulate trip. OL. The contacts have opened, exactly as they should. Release the trip here on the table.
Back to nearly zero. We have seen this switch both open and close. Try the middle thermostat. OL even at rest. Simulating a trip still gives OL. This sample is stuck open. Compare that with the working switch, which gave OL only while it was tripped. Last one. Cold, this thermostat reads almost zero, just like the working one.
Predict what you'll see when we trip it. Still almost zero. The contacts are stuck closed. A cold test alone would have missed it. On the thermistor we checked resistance at a known temperature. On the thermostat we checked whether the contacts actually changed state.
14:44 · Try the fault codes yourself in HxAR
Let's step back and turn the heating on. Watch the boiler. The burner lights, the radiator warms up, and there's no fault code on the display. You can visit this room yourself in HxAR. Look for the Baxi Main Eco Compact Combi in the Catalogue. Open the fault code field, type E20 and press Enter.
See the yellow ring? That's the heating flow sensor. Now try E28. This time it picks out the flue sensor. Want to test yourself? Choose Practise E28 to start that fault in the simulator. Or try Random fault beside the room thermostat. Read the display and decide what you'd test first.
We've got more boiler tutorials on the way. Subscribe for the next one, and have a look at the other videos on this channel. You'll find more heating guides at ephg.limited. Thanks for watching.
Technical references and simulation
Baxi, Main Eco Compact Combi Installation and Service Manual, 7908748 v01. See the wiring diagram on page 15, fault codes on page 58 and component checks on page 61. The heating pad, PTC comparison and three repair scenarios are HxAR training demonstrations.